  • Acson AWM 07G2, 47 Engineering & Physical Data AWM-G2_(i) General Data - Cooling Only (R22) MODEL INDOOR UNIT A5WM 07G2 A5WM 09G2 OUTDOOR UNIT A5LC 07C A5LC 10C NOMINAL CAPACITY Btu/h 7500 9000 W 2200 2640 NOMINAL TOTAL INPUT POWER W 620 860 NOMINAL RUNNING CURRENT A 2.90 3.90 POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50 EER W/W 3.55 3.07 REFRIGERANT TYPE R410A R410A REFRIGERANT CONTROL (E

  • Acson AWM 07G2, 14 AWM-G2_(i) Application Information Model: A5WM 20/25G2 - A5LC 20/25C (With Low Ambient Kit) A5WM 301 - A5LC 28C (With Low Ambient Kit) 

  • Acson AWM 07G2, 10 AWM-G2_(i) Application Information Application Information Operating Range Ensure the operating temperature is in allowable range. Cooling only Note : Standard operating range. With Low ambient kit. (Optional item) Please refer to local dealer for unit of this specification. Indoor temp. (°CDB) Cooling Outdoor temp. (°CDB) Indoor temp. (°CWB) Outdoor temp. (°CDB) Indoor temp. (°CWB) Heating Outdoor temp. (°CWB) -9 16 21 6 30 -5 19 35 14 46 23 Standard point Low ambient kit

  • Acson AWM 07G2, 63 Engineering & Physical Data AWM-G2_(i) Component Data - Heat Pump (R22) MODEL INDOOR UNIT AWM 301R AWM 301R OUTDOOR UNIT ALC 28CR ALC 30CR INDOOR FAN TYPE ANTI FUNGUS CROSS FLOW FAN ANTI FUNGUS CROSS FLOW FAN QUANTITY 1 1 MATERIAL ACRYLO NITRILE STYRENE ACRYLO NITRILE STYRENE DRIVE DIRECT DIRECT DIAMETER mm/in 106 / 4.17 106 / 4.17 LENGTH mm/in 950 / 37.4 950 /

  • 48 AWM-G2_(i) Engineering & Physical Data General Data - Cooling Only (R410A) MODEL INDOOR UNIT A5WM 10G2 A5WM 15G2 OUTDOOR UNIT A5LC 10C A5LC 15C NOMINAL CAPACITY Btu/h 9500 12000 W 2780 3520 NOMINAL TOTAL INPUT POWER W 910 12

  • Acson AWM 07G2, Wall Mounted Split Systems AWM-G2_(i) Models: AWM 07G2 AWM 09G2/G2R AWM 10G2/G2R AWM 152G/G2R AWM 20G2/G2R AWM 25G2/G2R AWM 301/301R A5WM 07G2/G2R A5WM 09G2/G2R A5WM 10G2/G2R A5WM 15G2/G2R A5WM 20G2/G2R A5WM 25G2/G2R A5WM 311/301R

  • Acson AWM 07G2, 147 Wiring Diagram AWM-G2_(i) Cooling Only Indoor Unit Outdoor Unit Model: AWM 15G2 Model: ALC 15C

  • Acson AWM 07G2, 22 AWM-G2_(i) Application Information Selection of Location and Space Indoor Unit Install the fan coil (indoor) unit at a location with the following requirements Location is suitable for wiring, piping and drainage. No obstruction of air ow into and out of unit where cooler air can be evenly distributed.(See g. 1) Ensure that air discharge is not s

  • Acson AWM 07G2, 112 AWM-G2_(i) Performance Data Cooling Only (R410A ) Model: A5WM 311 - A5LC 28C (3 Phase) Cooling Mode AFR (CFM) EWB EDB Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 500 16°C 21°C 7.18 4.68 2.00 6.93 4.55 2.16 6.67 4.43 2.34 6.40 4.30 2.54 5.88 4.01 2.75 5.43 3.77 3.04 24°C 7.19 5.60 2.00 6.94 5.47 2.16 6.68 5.34 2.34 6.41 5.21

  • Acson AWM 07G2, Nomenclature AWM-G2_(i) 1 Nomenclature Indoor Unit AWM10G2R Brand A : Acson Refrigerant “ “ 4 5 : Omitted if R22 : R407C : R410A Model Name WM : Wall Mounted Capacity Index 10 20 : 10,000 Btu/h : 20,000 Btu/h Chassis G2 : G + Series Model Type “ “ R : Omitted if cooling only : Heatpump

  • Acson AWM 07G2, 16 AWM-G2_(i) Application Information Model: AWM 15G2R - ALC 15CR A5WM 15G2R - A5LC 15CR Model: AWM 20G2R - ALC 20CR A5WM 20G2R - A5LC 20CR A5WM 25G2R - A5LC 25CR

  • Acson AWM 07G2, 142 AWM-G2_(i) Electrical Data Electrical Data - Cooling Only (R410A) MODEL INDOOR UNIT A5WM 07G2 A5WM 09G2 OUTDOOR UNIT A5LC 07C A5LC 10C INDOOR MOTOR INSULATION GRADE CLASS E CLASS E POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50 RATED INPUT POWER W 24 24 RATED RUNNING CURRENT A 0.11 0.11 MOTOR OUTPUT W 8 8 POLES 4 4 OUTDOOR MOTOR INSULATION GRADE CLASS B CLASS B POWER SOURCE V/Ph/Hz 220 - 24

  • Acson AWM 07G2, 172 AWM-G2_(i) Exploded View and Part List Note: All exploded view and part list are subjected to change by the manufacturer without prior notice INDOOR UNIT MODEL: AWM/A5WM 10/15G2/G2R     RGRB RTRG   R   RE RG RG No Description 1 ASSY., CHASIS 2 FAN, MOTOR 3 CROSS FLOW FAN 4 FAN, BUSH 5 ASSY., COIL 6 PIPING, CLAMP 7 ASSY., DRAIN PAN No Description 8 DRAIN HOSE 9 ASSY., CONTROL BOX 10 ASSY., CONTROL BOX COVER 11 ASSY., FRONT COVER 1

  • Acson AWM 07G2, 80 AWM-G2_(i) Performance Data Cooling Only (R22) Model: AWM 10G2 - ALC 10C Cooling Mode AFR (CFM) EWB EDB Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 200 16°C 21°C 2.62 1.90 0.65 2.53 1.85 0.71 2.43 1.80 0.77 2.34 1.75 0.83 2.15 1.63 0.90 1.98 1.53 0.99 24°C 2.62 2.28 0.65 2.53 2.23 0.71 2.44 2.17 0.77 2.34 2.12 0.83 2.15 1.98 0.90 1.99 1.87 0.99 27°C 2.64 2.58 0.65 2.56 2.53 0.71 2.47 2.47 0.77 2.37 2.37 0.83 2.19 2.19 0.90 2.04 2.04 1.00 30�

  • Acson AWM 07G2, 118 AWM-G2_(i) Performance Data Model: A5WM 10G2R - A5LC 10CR Heating Mode ID WB°C Outdoor WB°C -9 -6 -5 6 12 15 18 TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) 15 1.683 1.683 1.905 1.905 1.979 1.979 2.793 2.793 3.236 3.236 3.458 3.458 3.680 3.680 17 1.639 1.639 1.870 1.870 1.932 1.932 2.789 2.789 3.175 3.175 3.394 3.394 3.614 3.614 19 1.595 1.595 1.835 1.835 1.884 1.884 2.786 2.786 3.114 3.114 3.331 3.331 3.548 3.548 21 1.551 1.551 1.790 1.790 1.837 1.83

  • Acson AWM 07G2, 59 Engineering & Physical Data AWM-G2_(i) Component Data - Heat Pump (R22) MODEL INDOOR UNIT AWM 301 OUTDOOR UNIT ALC 30C INDOOR FAN TYPE CROSS FLOW FAN QUANTITY 1 MATERIAL ACRYLO NITRILE STYRENE DRIVE DIRECT DIAMETER mm/in 106 / 4.17 LENGTH mm/in 950 / 37.4 INDOOR FAN MOTOR TYPE INDUCTION QUANTITY 1 INDEX OF PROTECTION (IP) IP24 OUTDOOR FAN TYPE PROPELLER QUANTITY 1 MATERIAL GLASS REINFORCED ACRYL STYRENE RESIN DRIVE DIRECT DIAMETER mm/in 610 / 24 OUTDOOR FAN MOTOR TYPE I

  • 51 Engineering & Physical Data AWM-G2_(i) General Data - Heat pump (R410A) MODEL INDOOR UNIT A5WM 07G2R A5WM 09G2R OUTDOOR UNIT A5LC 07CR A5LC 10CR NOMINAL COOLING CAPACITY Btu/h 7500 9000 W 2200 2640 NOMINAL HEATING CAPACITY Btu/h 7500

  • Acson AWM 07G2, 107 Performance Data AWM-G2_(i) Cooling Only (R410A ) Model: A5WM 20G2 - A5LC 20C Cooling Mode AFR (CFM) EWB EDB Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 340 16°C 21°C 4.93 3.30 1.24 4.76 3.22 1.34 4.58 3.13 1.45 4.40 3.04 1.57 4.04 2.83 1.71 3.73 2.66 1.88 24°C 4.94 3.95 1.24 4.76 3.86 1.34 4.59 3.77 1.45 4.40 3.68 1.57 4.04 3.44 1.71 3.74 3.24 1.88 27°C 4.98 4.48 1.24 4.81 4.38 1.34 4.64 4.28 1.45 4.47 4.17 1.58 4.12 3.88 1.71 3.83 3.64 1.89 30

  • 93 Performance Data AWM-G2_(i) Heat Pump (R22) Model: AWM 20G2R - ALC 18CR Cooling Mode AFR (CFM) EWB EDB Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SH

Related Products and Documents (Air Conditioner):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 Legacy LW1057D Specifications legacy/lw1057d-T2R.pdf 06 Dec 2023 2
2 Regency Fireplace Products HZ42E-NG Owners & installation manual regency-fireplace-products/hz42e-ng-J2V.pdf 29 Aug 2022 60
3 Avaya S8700 Series Installing and configuring avaya/s8700-series-83N.pdf 11 Nov 2023 94
4 Mitsubishi Electric PUMY-P112VKM3 Technical service manual mitsubishi-electric/pumy-p112vkm3-S63.pdf 10 Aug 2022 158
5 Flotec FP5410 Owner's manual flotec/fp5410-676.pdf 04 Nov 2022 16
6 Color Kinetics ColorBurst 6 Installation manual color-kinetics/colorburst-6-3G2.pdf 17 Mar 2024 2

Similar Resources:

  • Hessaire

    H Series

    (16 pages)
    DUCTLESS MINI-SPLIT AC H SERIES USER MANUAL Please read and keep these instructions for future reference. Models: H12E1(1Ton, 115v, 22 SEER), H18E2(1.5 Ton, 230v, 23 SEER) H12HP1A(1 Ton, 115v, 17 SEER), H18HP2A(1.5 Ton, 230v, 17 SEER) …
  • Seifert

    871500201USL

    (23 pages)
    Version Nr. 1-10 - 07.03.2022 Doc. No. 99871500201USL 1 / 23Table of Content 871500201USL1. User manual 2 .................................................................................................................................. 2. Legal regulations 2 .................................................................................................. …
  • Hella

    Pergola VENTUR

    (43 pages)
    Installation Instructions and Instructions for Use These instructions must be read prior to installation and use! Pergola VENTUR Operating guidelines Installation Instructions and Instructions for Use Table of Contents Preliminary remarks HELLA Pergola VENTUR .................................................................... 1 Gener …
  • Haier

    H2SM-14HB03/R2

    (21 pages)
    SPLIT TYPE ROOM AIR CONDITIONEROPERATION MANUALPlease read this operation manual before using the air conditioner.HSU-07HC03/R2HSU-09HC03/R2HSU-12HC03/R2HSU-14HB03/R2HSU-18HB03/R2H2SM-14HB03/R2H2SM-18HB03/R2No.0010556062HSU-22HD03/R2 …
  • Domair

    MASTERCOOL9

    (50 pages)
    Rev 0-21 11 19 Fabriqué en ChinePage 1manuelMANUEL D’UTILISATIONES INSTRUCCIONES DE USO P11EN USER MANUAL P21DE BENUTZERHANDBUCH P31NL GEBRUIKSAANWIJZING P41d’utilisationFRRafraichisseur d’airRef: MASTERCOOL9Mod: MIK-08EX …
  • GE

    Appliances AKQ24DNT1

    (56 pages)
    GEAppliances.comSafety Instructions ............. 2, 3Operating InstructionsControls ...................... 4-6Care and CleaningAir Filter ........................ 6Otltdoor Coils .................... 6Installation Instructions ....... 7-13Troubleshooting Tips ........... 14Normal Operating Sounds ........ 14Consumer SupportConsumer Support ....... Back Cove …

Comments, Questions and Opinions: