  • Siemens SED2, SED2 AOP Operating Instructions Siemens Building Technologies, Inc. 1000 Deerfield Parkway Buffalo Grove, IL 60089-4513 Tel: +1 847-215-1000 Fax +1 847-215-1093 Siemens Building Technologies, Ltd.. 2 Kenview Blvd. Brampton, Ontario Canada L6T 5E4 Tel: +1 905-799-9937 Siemens Building Technologies AG Gubelstrasse 22 CH-6301 Zug Tel: +41 41 724 24 24 Fax +41 41 724 35 22 Siemens Building Technologies Ltd. 16/F, Laford Centre 838 Lai Chi Kok Road Kowloon, Hong Kong Tel: +852 2917 5700

  • Siemens SED2, Editing Parameters Siemens Building Technologies, Inc. 17 1. From the main menu, use and to scroll through the list of options and to highlight the Upread item. Press to confirm the selection. Press to cancel the upload process. The AOP displays an upload/upread menu. NOTE: In master mode, the AOP prompts for selection of a specific SED2 VFD from a list of the networked SED2 VFDs. 2. Use and to scroll through the list of parameter sets and to highlight the parameter set into which information will be writt

  • SED2 AOP Operating Instructions 12 Siemens Building Technologies 2. Configure the SED2 VFDs for network use. a. Set the Command Source P0700[1]=5 (USS on Com link). This sets the control over the USS link on the communications port. b. Assign each drive a unique RS-485 USS address in the range of 0 to 30. To do this set User Access Level P0003=3 (expert) and use U

  • AOP Overview Siemens Building Technologies 3 AOP Overview AOP Menu Structure The menus available on the AOP display depend on the currently active operating mode. The following diagram shows the menu structure when the AOP is in either the Local or Master operating mode. OPERATE DIAGNOSTICS PARAMETERS MODE UPREAD DOWNLOAD LANGUAGE SETUP TIMER SELECT GROUP: ALL PARAMETERS NOT D

  • Siemens SED2, Editing Parameters Siemens Building Technologies, Inc. 15 6. Press to access the index value. Use and to scroll through the index values and to highlight the desired index value. 7. Press to confirm the new index value. The AOP returns to the parameter selection screen so you can select another parameter, if desired. 8. To edit another indexed parameter, repeat Steps 3 to 6. NOTES: 1. Simultaneously press and , at any time, to return to the main menu. 2. Simultaneously pres

  • Siemens SED2, SED2 AOP Operating Instructions 26 Siemens Building Technologies 2. Use and to select the desired cursor type (blinking underline or inverse-video [default]). Press to confirm the selection and the AOP returns to the setup menu. NOTE: Simultaneously press and at any time to display relevant help screens. Start Help NOTE: By default, the Start Help function is set ON. To change this setting, select Start Help from the setup menu. 1. Use and to highlight the Start Help option on the setup menu. Press to confirm the selectio

  • Siemens SED2, SED2 AOP Operating Instructions 6 Siemens Building Technologies AOP Start-Up & Initialization Important Notes CAUTION: • You can mount or remove the AOP while power is applied to the SED2 VFD. • You must set Command Source P0700[1]=4 (USS on BOP link or AOP) before the AOP can start or stop an attached SED2 VFD. • On setting the AOP as the command source, you must set USS Telegram Off Time for Serial Interface BOP Link P2014[1]=5000 (5 seconds) to prevent unexpected drive operation. In

  • Siemens SED2, AOP Setup & Configuration Siemens Building Technologies, Inc. 27 2. Use and to select an ON or OFF user text status. Press to cancel this selection and to return to the setup menu. Press to confirm the selection and the AOP displays a text screen with the first character highlighted. The text string can contain a maximum of 20 characters. 3. Use and to scroll through the characters until the desired character is shown. Press to accept the character and to advance to the next character. Repeat this step until the desired text is entered. 4. Press and hold to except the text string and to return to the setup men

  • Siemens SED2, SED2 AOP Operating Instructions 14 Siemens Building Technologies 5. Press to confirm the new parameter value. The AOP returns to the parameter screen so you can select another parameter, if desired. Press to return to the r0000 display. Press again to return to the previous menu. Press for several seconds to return to the status screen (normal operating mode). The parameter value that has been changed is retained within the AOP’s internal memory, but not sent to the SED2. Should power to the SED2 or AOP be interrupted, all changes are lost. TIP: How to quickly change parameter values? T

  • Siemens SED2, AOP Faults & Warnings Siemens Building Technologies 29 AOP Faults & Warnings NOTE: If a fault/warning condition occurs on a SED2 VFD(s) to which an AOP connects, a fault/warning code displays with a description of the relevant fault/warning. For a list of fault/warning codes, see the SED2 VFD Operations & Maintenance Manual, Document No. 125-3202. Fault Indication/Fault Screen 1. If a fault condition occurs on a connected SED2 VFD(s), the AOP provides a fault message with specific information about the fault condition such as: − Identity

  • Siemens SED2, SED2 AOP Operating Instructions 4 Siemens Building Technologies Key Functions NOTE: This symbol is used throughout this manual to indicate a special keypad function. Key/ Function Functional Description Stops the motor. OFF1 Press this button to stop the SED2 within the selected ramp-down time. As part of the factory setting, this function is enabled for manual mode. OFF2 Press this button twice (or once with sustained pressure) to cause the motor to coast freely to a standst

  • Siemens SED2, SED2 AOP Operating Instructions 22 Siemens Building Technologies Timer Function NOTES: 1. Before using the timer function as a control method, set the AOP real time clock as described in the Set Time/Date section. 2. Setting a timing event for ‘every day’, configures the same event for each day of the week separately. To clear an ‘every day’ event, you must clear the event individually from each day. 3. When multiple events must be cleared from the Timer function, it may

  • Siemens SED2, SED2 AOP Operating Instructions 18 Siemens Building Technologies 1. From the main menu, use and to scroll through the list of options and to highlight the Download item. Press to confirm the selection. Press to cancel the download process. The AOP displays a download menu. NOTE: In master mode, the AOP prompts for selection of a specific SED2 VFD from a list of the networked SED2 VFDs. 2. Use and to scroll through the list of parameter sets and to highlight the parameter set from which information will be copied. Press to confirm the selection. 3. The AOP displays a

  • Siemens SED2, European Low Voltage Directive The SED2 VFD product range complies with the requirements of the Low Voltage Directive 73/23/EEC as amended by Directive 98/68/EEC. The units are certified for compliance with the following standards: EN 60146-1-1 Semiconductor VFDs - General requirements and line commutated VFDs EN 60204-1 Safety of machinery - Electrical equipment of machine European Machinery Directive The SED2 VFD series does not fall under the scope of the Machinery Directive. However, the products have been f

  • Siemens SED2, SED2 AOP Operating Instructions 16 Siemens Building Technologies 2. In the Internal mode, scroll through the list of parameter sets until the AOP parameter set appears. Press to confirm the selection. 3. Press again to select All parameters. 4. Use to access the internal AOP parameters. Internal parameters that display AOP information include: Parameter Description Parameter Description P0964 Software Version Information P8562 Free Memory P8552 Base slave address P8563 Enable Text Scrolling P8553 Default baud rate P8564 RS-232 Error count P8564 Enable Autobaud P8565 RS-485 Error count

  • Siemens SED2, AOP Operating Modes Siemens Building Technologies 19 AOP Operating Modes Selecting an Operating Mode The mode menu allows you to select the desired AOP operating mode. The following table summarizes the AOP operating modes and lists associated main menu items. Main Menu Items Operating Mode Operate Diagnostics Parameters Mode Upload Download Language Setup Timer Engineering Description Local • • • • • • • • • In Local

  • Siemens SED2, SED2 AOP Operating Instructions 20 Siemens Building Technologies 2. Press to confirm the selected operating mode (press to return to the main menu.) NOTE: To exit an operating mode, either follow the on-screen instructions or return to the main menu and select the mode menu to choose a different operating mode. Operating in Local Mode On initial power-up or after a reset, the AOP defaults to the Local operating mode. The Local mode operates only with one SED2. You can change the operating mode via the mode menu. You can control the SED2 VFD by acces

  • Siemens SED2, How to Use this Manual Siemens Building Technologies 1 How to Use this Manual The Advanced Operator Panel (AOP) enhances the user interface and communications capability of the SED2 Variable Frequency Drives (“SED2 VFD”). Manual Organization This manual contains the following sections: − How to Use this Manual, describes the organization of this manual and symbols used throughout this manual. − AOP Overview, shows the AOP main menu and details the AOP function keys. − AOP Startup & Initialization, describes AOP power-on and initialization procedures and discuss

  • Siemens SED2, Timer Function Siemens Building Technologies, Inc. 23 In general, use the following keys to set the timer: • Press to confirm the input. • and to scroll through input ranges. • Press to cancel the input and to return to the previous entry. 1. From the main menu, use and to scroll through the list of options and to highlight the Timer item. Press to confirm the selection. The AOP displays the timer screen. 2. Use and to enable (ON) or disable (OFF) the AOP timer function. If the timer is enabled, the cursor advances to the day-of-week field. Continue with the next step.

  • Siemens SED2, SED2 AOP Operating Instructions 30 Siemens Building Technologies Multiple Faults If a SED2 VFD or network of VFDs reports more than one fault condition, the AOP displays all fault messages by cycling through them until they are all cleared. See Fault Indication/Fault Screen in this chapter to acknowledge each fault message. Multiple Warnings If a SED2 VFD or network of SED2 VFDs reports more than one warning condition, the AOP displays all warning messages by cycling through them until the conditio

  • Siemens SED2, SED2 AOP Operating Instructions 8 Siemens Building Technologies Quick Commissioning NOTE: Simultaneously press and , at any time, to display the main menu. The following table describes the main menu items. Menu Item Description Operate Displays the current status of the SED2 VFD/motor. Diagnostics Displays a recent fault history. Parameters Allows you to select a parameter group (similar to Parameter Filter P0004) and to configure individual parameters. Mode Allows you to select the AOP mode of operation as follows: − Local − Master − Internal − Slave − PC Mode Upread (upload) Allows you to read a parameter set from a SED2

Related Products and Documents (Monitor):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 Berkley Tool BT-5020 Owner's manual berkley-tool/bt-5020-93K.pdf 11 Sep 2023 11
2 Pullman Holt GB-1500 Specifications pullman-holt/gb-1500-L63.pdf 05 May 2023 2
3 Albrecht CB Radio AE 6490 Operation & user’s manual albrecht/cb-radio-ae-6490-3Y2.pdf 06 Nov 2023 20
4 Electro-Voice Compact Precision CP3000S Specifications electro-voice/compact-precision-cp3000s-F7W.pdf 14 Mar 2024 4 0.25 Mb
5 Poulan Pro HDR500L Owner's manual poulan-pro/hdr500l-Q7A.pdf 27 Sep 2022 28
6 Honda GXV120 Owner's manual honda/gxv120-974.pdf 23 Feb 2024 32 1.1 Mb

Similar Resources:

  • Air Weigh

    BinMaxx

    (24 pages)
    Calibration and Operations Manual PN: 901-0147-000 Rev. 001BinMaxx™ Scale The Leader in Onboard Weighing Technology TM …
  • Philips

    191EW9FB/00

    (79 pages)
    19" LCD Color Monitor Chassis: HUDSON 9 Service Service Service …
  • Fujitsu Siemens Computers

    SCALEOVIEW L17-6

    (19 pages)
    Monitor Erste Schritte / Getting Started Deutsch, English, Français, Español, Português, Italiano, Svenska, Nederlands, Dansk, Suomi, Pycckий, Norsk, Eesti keel, Ελληνικά, Lietuviškas, Latviski, Polski, Slovensko, Slovenský, Česky, Magyar SCALEOVIEW L17-6 …
  • HP

    2210

    (2 pages)
    1296312963121START HEREWindows desktopTurn your PC on and wait for the Windows desktop to appear. Close any open programs, including virus-checking programs.2Attach the coverInsert the two bottom tabs of the cover into the slots on the unit.Tilt the cover down and press firmly. Make sure the tabs lock into place and the cover is even with the unit.4Remove o …
  • Dell

    S2309WFP

    (30 pages)
    Dell™S2309WFlatPanelMonitorUser'sGuide Notes, Notices, and Cautions    Information in this document is subject to change without notice. ©2008DellInc.Allrightsreserved. Reproduction of these materials in any manner whatsoever without the written permission of Dell Inc. is strictly forbidden. Trademarks …
  • Philips

    150P3A

    (13 pages)
    FCC ID: A3KM108 Product Information Product Features • Technical Specifications • Resolution & PresetModes • Philips Pixel Defect Policy • Automatic Power Saving • Physical Specification • Pin Assignment • Product Views • PhysicalFunctionProduct Features150P3A / 150P3C Ultra Slim Framel 15-inch color LCD monitor with excellent display pe …

Comments, Questions and Opinions: