Manualios.com

Paradox Digiplex EVO EVO192 Installation Manual

Paradox Digiplex EVO EVO192 Manual Online:

3.35, 533 votes
Paradox Digiplex EVO EVO192 User Manual
Paradox Digiplex EVO EVO192 User Guide
Paradox Digiplex EVO EVO192 Online Manual

Text of Paradox Digiplex EVO EVO192 User Guide:

  • Paradox Digiplex EVO EVO192, 78 EVO Installation Guide Dialer Options 11 11.1 Telephone Line Monitoring SECTION [3036]: OPTIONS [1] AND [2] When enabled, the system verifies the existence of the main telephone line once every second. After each successful test, the Status LED on the control panel flashes briefly. A line test failure occurs when the TLM detects less than 3 volts for the period defined by the TLM Fail Timer (see section 11.1.1). If the line test fails, the control panel will generate one or more conditions as defined by the TLM settings below, until it detects the tele

  • Paradox Digiplex EVO EVO192, EVO Installation Guide 11 Introduction 1 1.1 EVO192 – Residential Fire and Burglar Alarm and Commercial Burglar Alarm System 1.1.1 System Description The EVO192 is a Residential Fire and Burglar Alarm and Commercial Burglar Alarm System consisting of Controller EVO192, 8-Zone Expansion Module ZX8, HUB Module HUB2, IP Communication Module IP150, Hardwired Keypads K641and TM50, Wireless Expansion Module RTX3. The EVO192 Controller consists of 8 on-board zone inputs (16 with zone doubling) that is expandable to a maximum of 192 zones via the 4-wire combus. The EVO Cont

  • Paradox Digiplex EVO EVO192, 110 EVO Installation Guide After entering the section corresponding to the desired message, use the Message Programming Keys (refer to Table 8) and Table 7 on page 93 to change the message to suit your installation needs. K641 Programming C.0.7 Partition Assignment SECTION [001]: OPTIONS [1] TO [8] To assign the keypad to a partition, simply enable the option that corresponds to the desired partition. By default, partitions 1 to 8 are enabled. C.0.8 Display Access Code Entry SECTION [003]: OPTION [1] C.0.9 Display Exit Delay Timer SECTION [003]: OPTION [2] C.0.10 Display Entry Delay Timer SECTION [003]: OPTION [

  • Paradox Digiplex EVO EVO192, EVO Installation Guide 109 Programming C.0.5 Entering Module Programming Mode The keypad is programmed through the control panel. To do so, you must first enter Module Programming Mode: 1. From Normal Mode press and hold the [0] key. 2. Enter the [ INSTALLER CODE] (Default: 000000). 3. Enter section [4003]. 4. Enter the keypad’s 8-digit [ SERIAL NUMBER]. 5. Enter the 3-digit [ SECTION] you want to program. 6. Enter the required [ DATA]. The control panel will then redirect all programming to the selected keypad. Every time the [CLEAR] key is pressed it will revert to the preceding step, unless ente

  • Paradox Digiplex EVO EVO192, EVO Installation Guide 81 VDMP3 Voice Module 12 12.1 VDMP3 Installation Instructions 12.2 Feature activation (PGMs) Using the VDMP3, it is possible to activate the PGM utility keys or PGM groups that are programmed in the EVO panel. VDMP3 feature numbers do not necessarily correspond to EVO utility key numbers. For example: Step English 1 Install •Power down the EVO control panel. •Install the VDMP3 directly onto the EVO control panel’s SERIAL and DIALER connectors as shown in "VDMP3 Installation Instructions"12.1. •If using a 307USB or CONV4USB, connect to the COM PORT connector as shown in "VDMP3 Insta

  • Paradox Digiplex EVO EVO192, 28 EVO Installation Guide Programming Methods 3 3.1 Paradox Memory Key The Paradox Memory Key can copy the programmed contents of one control panel into as many others. Note: Not to be used with UL Listed systems. Copy to Memory Key 1. Insert the Memory Key (PMC-4) onto the control panel’s connector labelled “MEM KEY”. 2. To copy the contents to the Memory Key except zone numbering and sections [0501] to [0532], enter installer programming mode, then enter section [4020]. (Depending on the memory key, the labels may or may not be included.) To copy the contents to the Memory Key in

  • EVO Installation Guide 117 C.0.57 PIN Entry ON Keypad SECTION [006]: OPTION [4] If the Card and Code Access option is enabled in the EVO control panel, users must present their access control card and then enter their PIN on the K641R keypad to gain access. The PIN Entry on Keypad option cannot be turned ON and will always be OFF. DGP2-648BL Programming C.0.58

  • Paradox Digiplex EVO EVO192, 74 EVO Installation Guide * UL Note: Installer must verify the compatibility with of the DACR. Use listed compatible DACRs. 10.7.1 Standard Pulse Formats The control panel can use the Ademco slow, Silent Knight fast and Sescoa standard pulse reporting formats (see Table 6). 10.7.2 Ademco Express The Ademco Express is a high-speed reporting format that communicates 2-digit (00 to FF) report codes. The Ademco Express does not use the Contact ID Report Codes. 10.7.3 Contact ID Pager The control panel will transmit a Contact ID report instead of a user g

  • Paradox Digiplex EVO EVO192, 70 EVO Installation Guide 10.2.10 Special Alarm Report Codes 10.2.11 System Trouble Codes [3930] Emergency Panic (non-medical) the panic keys [1] and [3] were pressed (see section 9.6 on page 63) [3931] Auxiliary Panic the panic keys [4] and [6] were pressed (see section 9.6 on page 63) [3932] Fire Panic the panic keys [7] and [9] were pressed (see section 9.6 on page 63) [3933] Recent Closing an alarm is generated within the Recent Close Delay (see section 10.10 on page 75) [3934] Police Code Confirmation of an alarm condition occurr

  • Paradox Digiplex EVO EVO192, EVO Installation Guide 141 Index Numerics 24Hr Zones 34 A AC Failure not Displayed 92 AC Power 17 Access Code Length 97 Access Codes 97 Account Number 73 Account Number Transmission 73 Ademco Contact ID 73, 74 Ademco Express 74 Ademco slow 73 Advanced Technology Zoning (ATZ) 33 Alarm Transmission Delay. See Delay Alarm Transmission Alarm Types 36 Alternate Dialing Option 75 Always Force Arm 57 Answer WinLoad 90 Arming Follows Partition 55 Arming/Disarming Reporting 71 Arming/Disarming Schedule Tolerance Window 72 Assigning keyswitches to partitions 43 Audible Alarm 64 Bell C

  • Paradox Digiplex EVO EVO192, EVO Installation Guide 33 4. Press Grafica’s center action key (Save) to save and exit. 4.3 Zone Doubling (ATZ) SECTION [3033]: OPTION [8] (default = disabled) Fire Zones cannot be doubled. 4.4 Zone Definitions 4.4.1 Zone Disabled section [0400]: First digit = 0 SECTIONS [0101] TO [0196]: FIRST DIGIT = 0 Disables the corresponding zone. Zones are disabled by default. 4.4.2 Entry Delays 1 and 2 section [0400]: First digit = 1 and 2 SECTIONS [0101] TO [0196]: FIRST DIGIT = 1 AND 2 (default Entry Delay 1= 030, Entry Delay 2 = 060) A zone defined as Entry Delay 1 follows th

  • Paradox Digiplex EVO EVO192, EVO Installation Guide 25 2.21.1 Connecting the Combus in Noisy Environments When installing the combus wires in proximity to high electrical interferences or across separate buildings, use shielded cables: Within the Same Building: Strip the outer jacket at one end of the shielded cable to expose the shield and connect the shield to the control panel ground (not the dialer ground), while leaving the shield at the other end of the cable open (floating). Across Separate Buildings: Strip the oute

  • Paradox Digiplex EVO EVO192, EVO Installation Guide 51 Note: Using any non-UL approved components will invalidate the UL certification of this system. Figure 17 – Typical System Layout Ground Floor Installation Up Den Living room Dining room Kitchen Toilet Utility room Entrance Control panel NVX80 NVX80 HD77 HD77 CO HD77 Smoke Ethernet Switch NV5 Door contact Window contacts Window contacts Window contacts Window contacts RTX3 SR130 LCD Keypad CAT5e 22 AWG Ethernet Cable Touchpad Smoke Smoke Required Recommended Smoke Smoke Smoke

  • Paradox Digiplex EVO EVO192, EVO Installation Guide 15 Figure 2 – Mounting the EVO Panel and the HUB2 in an 11 x 11 metal box 2.5 Mounting the K641 Waiting for Daniel 2.6 Mounting the TM50 For mounting instructions refer to the TM50 manual TM50-EI01. 2.7 Mounting the RTX3 For mounting instructions refer to the RTX3 manual RTX3-EI11. 2.8 Wiring Location for the EVO192 board mounting pins. There are 5 mounting pins. Location for the Tamper switch. Location for the HUB2 /ZX8 board mounting pins. There are 4 mounting pins. Use either the

  • 106 EVO Installation Guide Appendix C: Keypad Installation Instructions Connecting the Keypads The keypads are connected to the control panel's combus in a star and/or daisy chain configuration. Connect the four terminals labeled red, black, green and yellow of each keypad to the corresponding terminals on the control panel. Connecting Keypad Zones Each ke

  • Paradox Digiplex EVO EVO192, 122 EVO Installation Guide Figure 29 – Recommendations for Smoke Detector Locations 4" min to 12 “ max 4" min to 12 “ max 4" min to 12 “ max 4" min to 12 “ max 4" min to 12 “ max Bedroom Bedroom Hallway

  • Paradox Digiplex EVO EVO192, 64 EVO Installation Guide Audible Alarm The control panel activates the BELL output until a user cancels the alarm or when the Bell Cut-Off Timer elapses . Fire Alarm Same as audible operation, except that the bell/siren output will be pulsed. * UL Note: For UL Listed systems, all emergency non-medical and auxiliary panic alarms will be report only.

  • Paradox Digiplex EVO EVO192, 18 EVO Installation Guide Note:For connection of self-contained bell/siren, see Figure 7 on page 22. When the bell output is not used, the “Bell Absent” message appears in the Trouble Display. To avoid this, connect a 1k Ω resistor across the bell output. UL Note: The keypads must be programmed to beep with all troubles. The metal housing which enclosed the Fire and Burglary system housing has knockouts on the sides and in the back enclosure and shall accommodate conduit of the trade size according to NEC. WARNING: “To prevent risk of electric shock, disconnect AC battery and phone cord BEFORE Servicing”. 2.14 False Alarm Reduction In an effort to deter false

  • Paradox Digiplex EVO EVO192, 116 EVO Installation Guide Option [3] ON=Pre-Alarm is enabled (default) C.0.51 Door Left Open Pre-Alarm Timer SECTION [011] This timer will trigger the Door Left Open Pre-Alarm before the end of the Door Left Open Interval. Enter any value between 001 and 255 to determine the seconds before the expiry of the Door Left Open Interval that the reader will beep. Default = 15 seconds. C.0.52 Door Left Open Alarm Feedback SECTION [004]: OPTIONS [5] AND [6] Option [5] OFF=The Door Left Open Alarm is silent Option [5] ON=The Door Left Open Alarm is audible (default) If option [5] is enabled: Option [6] OFF=Beep as long as the Door Left Open

  • Paradox Digiplex EVO EVO192, 14 EVO Installation Guide 2.4 Mounting the EVO192 Controller, HUB2, ZX8, IP150 2.4.1 Tamper Switch 1. Insert the tamper kit TK278 into the slot in the box. 2. Mark the hole. 3. Drill the hole in the switch bracket. 4. Using a metal washer screw the switch bracket to the wall (you may need an anchor). 5. Wire one of the switch wires to one of the on board zone inputs and the other to COM. 6. Configure this zone to a 24h burglary zone. 7. Screw the cabinet to the wall using the proper screws (and anchors if required). Make sure the Anti-tamper switch is installed befor

  • Paradox Digiplex EVO EVO192, EVO Installation Guide 63 9.5.1 Tamper Bypass Options SECTION [3034]: OPTION [7] (default = enabled) When enabled in section [3034], the control panel will ignore the zone’s bypass definition and will follow the option set in section 9.5 (page 62) if a tamper or wire fault occurs on a bypassed zone. When disabled, Tamper Recognition follows the zone’s bypass definition. This means that the control panel will not perform any action if a tamper or wire fault occurs on a bypassed zone. 9.6 Keypad Panic Options (default = disabled) The control panel can generate an alarm (audible, fire or report only) by pressing the keypad

  • Paradox Digiplex EVO EVO192, EVO Installation Guide 105 200 Fire Supervisory 32 372 Protection Loop short 67 453 Failed to Open 9C 201 Low Water Pressure 33 373 Fire Trouble 68 454 Failed to Close 9D 455 Auto-Arm Failed 9E COMMUNICATION DISABLES - 550 & 560 609 Video Xmitter Active C5 456 Partial Arm 9F 551 Dialer Disabled B3 611 Point Test Ok C6 457 User Exit Error A0 552 Radio Transmitter Disabled B4 612 Point Not Tested C7 458 User on Premises A1 BYPASSES - 570 613 Intrusion Zone Walk Tested C8 459 Recent Close A2 570 Zone Bypass B5 614 Fire Zone Walk Tested C9 461 Wrong Code Entry A3 571 Fire Bypass B6 615 Panic Zone Walk Tested CA 462 Legal Code Entry A4 572 24

  • 128 EVO Installation Guide • Maximum loop voltage (open loop): 5.0 VDC • See installation manual for zone input connections. ADD THESE SECTIONS IN THE PROGRAMMING GUIDE, INSTALLER MANUAL AND/OR USER MANUAL 5. CP-01 options a. Section [3028] : i Option 3 : CP-01 Enabled (Default enabled). Note: If that option is ‘Enabled’ while performing a manual panel re

  • 68 EVO Installation Guide 10.2.5 Access Codes Arming SECTIONS [2001] TO [2099] A report code can be programmed for each user access code from 01 to 98 in sections [2001] to [2098]. User access codes from 99 to 999 use a common report code in section [2099]. The control panel can send the report code identifying which access code was used to arm the system

Related Products and Documents (Smoke Alarm):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 JVC KD-AR390 Instructions manual jvc/kd-ar390-9M3.pdf 08 Nov 2022 35
2 SanDisk Sansa Fuze+ Manual  sandisk/sansa-fuze-8P9.pdf 06 Jun 2023 265
3 TYAN GT20 (B5502) Service manual tyan/gt20-b5502-SJI.pdf 25 Jan 2024 70 20 Mb
4 Multitech MVPFX2-2 Cabling manual multitech/mvpfx2-2-C72.pdf 17 Feb 2023 8
5 NEC TCM380 Quick start manual nec/tcm380-WZ2.pdf 02 Jan 2024 47
6 Newer Technology miniStack v2 Owner's manual newer-technology/ministack-v2-77P.pdf 22 Sep 2022 2

Similar Resources:

  • System Sensor

    B402B

    (4 pages)
    D450-03-00 1 I56-0374-006RB402B Plug-in Detector BaseFor use with the following smoke detectors: 1451, 2451, and 2451THINSTALLATION AND MAINTENANCE INSTRUCTIONSBEFORE INSTALLING Please read the System Sensor manual I56-407, Guide for Proper Use of Sys-tem Smoke Detectors, which provides detailed information on detector spacing, placement, zoning, wiring …
  • Greenheck

    Smoke Dampers SMD-203

    (7 pages)
    Model SMD-203 meets the requirements for smoke dampers established by:National Fire Protection Association NFPA Standards 92A, 92B, 101 & 105 IBC International Building CodesNew York City (MEA listing #260-91-M)CSFM California State Fire Marshal Leakage (Smoke) Damper Listing (#3230-0981:104)ApplicationModel SMD-203 is a leakage rated smoke damper …
  • Sealey

    Auto Service Series

    (2 pages)
    INSTRUCTIONS FOR:DIGITAL TACHOMETER(CONTACT / NON-CONTACT)MODEL No: TA050Thank you for purchasing a Sealey product. Manufactured to a high standard this product will, if used according to these instructions and properly maintained, give you years of trouble free performance.IMPORTANT: PLEASE READ THESE INSTRUCTIONS CAREFULLY. NOTE THE SAF …
  • Honeywell

    SiX Series

    (2 pages)
    SiXHEAT Wireless Rate of Rise Heat Detector QUICK INSTALLATION GUIDE GUIDE D'INSTALLATION RAPIDE This wireless SiXHEAT detector is intended for use with Honeywell controls that support SiX™ series devices. For Lyric Controller: Enroll on Controller version v01.00.05920.468 or later. Ce détecteur de SiXHEAT sans fil est conçu pour être utilisé …
  • Panasonic

    Units for Hazardous

    (2 pages)
    Panasonic Electric Works Fire & Security Technology Europe AB Citadellsvägen 23, SE-211 18 Malmö, Sweden Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 [email protected] • www.panasonic-fire-security.com Fire alarm systems Units for Hazardous (Ex) areas • Approved isolator and Intrinsically Safe detectors for conventiona …
  • System Sensor

    1151

    (4 pages)
    D100-51-00 1 I56-546-07R1151 Low Profile IonizationPlug-in Smoke DetectorsINSTALLATION AND MAINTENANCE INSTRUCTIONS 3825 Ohio Avenue, St. Charles, Illinois 601741-800-SENSOR2, FAX: …

Comments, Questions and Opinions: