Plumis Automist Series Technical Manual
|
Plumis Automist Series, Page 27 of 27 12.5 Overview Below a summary of the results: Test Description Test criteria reached (time in minutes, seconds) FED = 1 @ 1.8 m FED = 2 @ 1.8 m FED = 1 @ 0.6 m FED = 2 @ 0.6 m 8m x 4m room with open doors Automist @ 5m* Not reached Not reached Not reached Not reached Automist @ 8 m 3 m 3 s (heat) 3 m 13 s (heat) Not reached Not reached Free Burn 2 m 19 s (heat) 2 m 27 s (heat) Not reached Not reached 8m x 4m room with closed doors Automist @ 8 m 23 m (heat) Not reached Not reached Not reached Free Burn 3 m 40 s (heat) 12 m 53 s (heat) 7 m 30 s (heat) 21 m 3 s (heat) 4m x 4m room with closed doors Automist @ 3 m 25 m (asp
Plumis Automist Series, Page 8 of 27 The Automist unit will be activated by an alarm which will ensure that: • Audible warning is provided throughout the protected area. • In addition to Automist’s integrated sounder, we recommend that the detector or alarm system that activates Automist also includes its own sounder.Guidance on re detection in dwellings is contained in BS 5839: Part 6. • Automist must not be activated by an early warning interlinked system (which might include smoke alarms). A separate alarm circuit should be used or provisions should be made so t
Plumis Automist Series, Page 9 of 27 A re suppression device like Automist aims to control and suppress res, signicantly reducing the risk of injury, life loss and property damage by maintaining tenable conditions for as long as possible while occupants evacuate. This is achieved in several ways: • Reduction of room temperature in the region of the re. Water mist devices achieve this by consuming much of the re’s energy in converting water to steam. • Reduction of smoke and toxic gases. Water mist devices achieve this by the production of copious amounts of steam in the immediate vicinity
Page 20 of 27 12 Appendix 12.1 Fire Testing at BRE In one of the most comprehensive test suites ever run on a mist product at the Building Research Establishment (BRE), Plumis veried the effectiveness of Automist with live burns in a series of different scenarios. The test was based on BS EN 1869:1997, DD 8458 1:2010, and the criteria of Scandinavian SRSA/
Plumis Automist Series, Page 6 of 27 In the event of a re, the system is triggered automatically by a heat alarm or a re panel output. Heat detection is recommended for kitchens in Approved Document B, and effectively eliminates nuisance activation. Unlike conventional sprinklers, Automist can be stopped manually by pressing a button on its control panel or by cutting power to the independent circuit on the consumer unit (marked with an indicator sticker). As Automist uses much less water than a traditional sprinkler system, water damage
Plumis Automist Series, Page 7 of 27 Automist should be mains fed with a reliable water supply: • 6 l/min ow • 1-10 bar pressure at pump inlet • Standard BSP ¾” connection. For life safety applications exposed or partially exposed pipework must be in copper or steel for robustness. The Automist pump should be: • Proper air circulation must be provided. The system requires there to be a minimum 100 mm gaps are gap between the pump perimeter and the enclosures. • Protected electrically by suitable fusing and powered by an independent circuit either
Plumis Automist Series, Page 2 of 27 1 This Document Page 3 2 Introduction to Automist Page 3 3 System Diagram Page 4 4 Automist Operation Page 6 5 Quality Assurance Page 6 6 Components and conguration Page 7 7 Fire suppression within a holistic approach Page 9 8 Fire Performance and Regulations Compliance Page 10 9 Use of Automist Page 15 10 Specifying Automist Page 17 1
Page 25 of 27 4.0 FED Heat 3.5 3.0 2.5 2.0 1.5 1.0 0.5 0.0 Time (mins) 8m x 4m x 2.5m Open Room FED Heat - when it reaches 1.0 it is assumed that an occupant will be incapacitated due to pain. Third degree burns are predicted at an FED of approximately 3.0 control automist @ 5m automist @ 8m 0.0 5.0 10.0 15.0 20.0 25.0 30.0 4.0 FED Asphyxia 3.5 3.0 2.5 2.0 1.5 1.0 0
Plumis Automist Series, Page 12 of 27 The application of Automist is carefully controlled to ensure that the application does not extend beyond the system capabilities that were established during the BRE re tests. The general rules developed from these tests are included in Section 10 of this document and form the basis of proof of concept for the suppression performance for all actual applications. Where the focus of the Automist application is not something that was directly considered during the BRE re tests the behaviour has been further validated by independent re engineering consultants following recognised re engineering principles discussed in BS7974 to demonstrate suitabilit
Plumis Automist Series, Page 14 of 27 Electrical supplies A separately fused connection to the re pump taken after the meter and from the supply side of the domestic fuse box using re resisting cable. All other devices on the system should continue to function in the event of a complete failure of mains power (as per BS5839 Part 6) Automist must remain powered in the event of a re and therefore must not share a mains circuit or RCD with appliance and sockets. The pump unit electrical supply will adopt the BS9251 installation recommendations. Achieved. An identical level of design redundancy is included into the Automist system as would be expected of a residential
Plumis Automist Series, Page 28 of 27 Automist’s Technical Guide Version 2.5 © Plumis Ltd. 2011 - All rights reserved. Ref: Plu6/v.1 (LABC) For further information, please contact: Plumis Ltd. HMS President (1918) Victoria Embankment London United Kingdom EC4Y 0HJ www.plumis.co.uk [email protected] C O M M I S S I O N S P E C I F I C A T I O N I N S T A L L A T I O N ACCREDITED INSTALLER Automist
Plumis Automist Series, Page 5 of 27 b) Automist under-tap kit (4N) Assembled Automist emitter - outer cover and o-ring - manifold and two o-rings (base & upper) - six protective caps - four watermist nozzles High pressure hose Stainless steel braided 3/4” water supply hot & cold water supply pipes Fused connection unit on a separate circuit Automist supply label & cable tie Wired or wireless heat alarm with NC and NO relay functionality Standard monobloc tap ¾” single check valve ¾” washin
Plumis Automist Series, Page 22 of 27 12.2 Simulatedfurniturereinaclosedroom The graph below details the FED measurements at 1.8 m high in the 8 m x 4 m closed room scenario. In an unsuppressed re an occupant 3 m from the re would be incapacitated due to pain in less than 4 minutes from ignition. After 13 minutes survivability is highly unlikely due to excessive burns. In the same scenario with Automist 8 m from the re, incapacitation and unconsciousness are delayed until 23 minutes
Plumis Automist Series, Page 4 of 27 Two examples of generic system layouts are detailed on the following pages. As an “pre-engineered” solution which is not covered within any one British Standard the following system layouts are proposed as our recommendations, however these may need modication during the course of negotiation with approving authorities with regard to a specic project specication. a) Automist wall-mount kit (3N) 3 System Diagram A discreet single-gang wall box holds the water mist spray head in place. The pump can be housed in a cupboard, under a
Page 26 of 27 Automist can also be effectively used for ashover prevention; in the graph below you can see how it reduces the temperature in the room from 410°C to 155°C at its peak on the higher thermocouple. This allows a compartment to comply with a 60 minute re containment requirement without any passive re protection devices. 12.4 Sim
Plumis Automist Series, Page 16 of 27 • Providingadequateprotectionwhenredoorsareeitherremovedordowngraded In the example of a re engineered solution, where the plans are compliant with Approved Document B principles, the suppression capabilities of Automist can be used in conjunction with an analysis of the proposed doors material properties and comparative re and temperature performance, where the client wished to either use a door which was not re resistance certied or was inherently non-
Page 17 of 27 Automist design specication guidelines state that a single pump can cover an area of up to 32m 2 , with a maximum ceiling height of 5m. Based on Plumis’s experimental data from BRE, spray heads must be located within 5m line of sight of any possible re location. 10 Specifying Automist 5m 5m Correct Incorrect
Plumis Automist Series, Page 3 of 27 Automist is a re suppression appliance designed for residential use. Its primary application is in the gap between standardised sprinkler systems, which are designed to provide suppression to every room in a property, and building and housing regulations, which in many circumstances require re suppression in a single open-plan “access room”. All major UK guidance documents on residential re safety, including Approved Document B, The LACoRS guide, and Scottish Building Regulations, recognise
Plumis Automist Series, Page 15 of 27 In this section we detail typical applications for Automist, how it should be specied, and present some additional points of comparison with conventional sprinklers. • Providingseparationfromriskareas The guidance in Approved Document B recommends for studio ats that the kitchen should be ‘remote’ from the entrance door and escape route. Although it is preferable if the cooking facilities are away from the at entrance the lack of clearly dened guidance on the meaning of ‘remote’ can lead to inconsistency. Looking at the UK national
Plumis Automist Series, Page 19 of 27 Automist should be specied, commissioned and signed-off by Plumis or an Accredited Reseller. Each reseller is fully trained to ensure that every project is installed to a high standard, receiving a Plumis Certicate of Accreditation on successful completion of the training. Automist is an innovative re suppression unit which can be installed as a compensatory measure for layouts that don’t match the conventional prescriptive guidance from Approved Document B or supporting guidance for the Regulatory Ref
Plumis Automist Series, Page 18 of 27 Small potentially blocked or shadowed oor areas shall be permitted on a horizontal plane in compartments of 64 m 2 (two pump units) or less as long as the maximum area of the total contiguous shadowed oor area, regardless of geometric conguration, does not exceed 2 m 2 . Preliminary Automist designs can be recommended by speciers by following these recommendations, however, Plumis accredited installers are trained to specify, install, commission and maintain the Automist system. Their early involvement in the project is recommended as they are required to verify installation proposals, provide critical supporting techni
Page 23 of 27 The graphs below show the results for the same test but at a lower height of 0.6 m. This height could represent an inhabitant who is sleeping, sitting or has fallen unconscious. After 21 mins and 22.5 mins both heat and asphyxia threaten survivability in the unsuppressed scenarios. However in the room with Automist operating, FED asphyxia does n
Plumis Automist Series, Page 1 of 27 Automist TM Technical Guide Product specication and technical results from a test suite at BRE Global to enable building control and re industry professionals to assess or specify Automist. Plumis Ltd. Seamless Fire Protecon www.plumis.co.uk A technical guide for: - Building Control - Fire Industry Professionals New Edition Version 2.5.0 RD171
Mircom RAM-300LCD Series Fire Alarms Installation and operation manual
RAM-300LCD Series |
Siemens FS-250 Fire Alarms Programming manual
FS-250 |
Plumis Automist Fire Alarms User handbook manual
Automist |
ELRO RM335 Fire Alarms Operation & user’s manual
RM335 |
DSC PC1550 Fire Alarms Instruction manual
PC1550 |
FlameStop PFSIFP8 Fire Alarms Installation and operation manual
PFSIFP8 |
Siemens MSI-30B Fire Alarms Installation instructions
MSI-30B |
Simplex 4010ES Fire Alarms Operator's manual
4010ES |
# | Manufacturer | Model | Document Type | File | Updated | Pages | Size |
---|---|---|---|---|---|---|---|
1 | Vortex | ROK DVS J | Owner's manual | vortex/rok-dvs-j-L4O.pdf | 01 Jun 2023 | 45 | |
2 | Fisher & Paykel | CMOH30SS | Use and care manual | fisher-paykel/cmoh30ss-N35.pdf | 26 Jul 2023 | 76 | 1.05 Mb |
3 | Milwaukee | M18 | Operator's manual | milwaukee/m18-67E.pdf | 25 Apr 2023 | 20 | |
4 | Whirlpool | LA6090XT | Use & care manual | whirlpool/la6090xt-KG7.pdf | 18 Mar 2024 | 16 | 0.77 Mb |
5 | moyno | 300 SERIES | Service manual | moyno/300-series-7QZ.pdf | 08 May 2023 | 5 | |
6 | AVM | OVATION CD8 | Operating instructions manual | avm/ovation-cd8-273.pdf | 29 Jul 2023 | 14 |
Notifier
Simplex 4010 NIONA151998:A1 ECN 02-298Document 5199803/26/03 RevUniNet™ 2000Simplex 4010 NIONInstallation and Operation ManualVersion 2Technical Manuals Online! - http://www.tech-man.comfirealarmresources.com
…
UniNet 2000 Simplex 4010 NION(24 pages) |
Secutron
Installation and Operation ManualLT-951SEC Rev. 5.3November 2018MR-2320 SeriesPre-Action/Deluge and Agent Release Control PanelFM APPLICATIONS MUST HAVE CLASS A INITIATING CIRCUITS ONLY (FOR RELEASING) AND 90 HOUR BATTERY STANDBY OPERATION
…
MR-2320 Series(92 pages) |
C-TEC
HUSH-ACTIV KITS BS 5839-6 Grade C Domestic Fire Alarm KitsINSTALLER’S GUIDE Approved Document No. DFU0005086 Rev 3The Hush-ActiV standalone domestic fire alarm kits have been designed to reduce the incidence of false alarms in HMOs, dwellings, flats, etc., by providing a reliable, fully monitored fire detection and alarm system complete with hush (silence …
HUSH-ACTIV KITS(2 pages) |
MEDC
© MEDC 2015 07/15 Please note that every care has been taken to ensure the accuracy of our technical manual. We do not, how-ever, accept responsibility for damage, loss or expense result-ing from any error or omission. We reserve the right to make alterations in line with techn …
SM87BG(28 pages) |
Simplex
-7© 1995 Simplex Time Recorder Co. FA4-31-201 (574-018)All specifications and other information shown were current as of publication, and are subject to change without notice. Ed 5 954100/4100+ Fire AlarmOperating Instructionsfirealarmresources.com
…
SafeLINC 4100(97 pages) |
Simplex
1/2 Doc. version 1.0 Indoor Isolated Callpoint InstallationThe Indoor Isolated Callpoint is an addressable indoor manual callpoint.The callpoint signals the condition of a switch contact that is operated by pressing on a deformable element. After activation the deformable element is not destroyed and the callpoint can be reset.The unit features a short-circu …
4099-5210(2 pages) |
Stamina Fitness Equipment AeroPilates Performer 272#OEOK35 AeroPilates Performer 272: Stamina Fitness Equipment Owner Documentation AeroPilates Performer 272, 23 |
Buffalo Adapter WLI-CB-G240WLI-CB-G240 (Adapter ePDF User Manual, #SQK34H) WLI-CB-G240, 2 |
Philips DVD Player DVD952DVD Player #Q1EHTO DVD952, 24 |
RCA CRT TV F19420RCA Product Guide: F19420 PDF Operation & user’s manual - E1CEE4 F19420, 48 |
Memphis Grill EliteMemphis Product User Guide: Elite PDF Owner's manual - JY479Z Elite, 44 |
Callaway Golf GPS EclipseGuide: Callaway Golf Eclipse (5SX68C, Upd.Monday 19-02-2024) Eclipse, 76 |
CFM Fan DVK-0910CFM Fan DVK-0910 Brochure DVK-0910, 4 |
Philips Micro Music System MCD395/58PDF Guide (@YT41G3), Philips MCD395/58 Micro Music System (30.12.2023) MCD395/58, 41 |
Sony Stereo Receiver ST-RDE597Stereo Receiver Operating instructions manual (Sony ST-RDE597) ST-RDE597, 56 |
Viking Telephone K-1500-6AViking Product User Guide: K-1500-6A PDF Technical practice - WGHTH7 K-1500-6A, 2 |
Dean Fryer SM20 GMDean SM20 GM User Manual (Installation & operation manual), @87N9F4 SM20 GM, 44 |
Ericsson Telephone MD110#SR6DLC: MD110 Telephone Operation & user’s manual MD110, 10 |