ADEMCO 5110XM Operation & User’s Manual

ADEMCO 5110XM Manual Online:

3.1, 1808 votes
ADEMCO 5110XM User Manual
ADEMCO 5110XM User Guide
ADEMCO 5110XM Online Manual

Text of ADEMCO 5110XM User Guide:

  • ADEMCO 5110XM, –9– FIXED-WORD KEYPAD DISPLAYS FIRE Appears when a fire alarm is detected. Accompanied by a display of the zone # in alarm. ALARM Appears when any type of alarm is detected. "FIRE" also appears when a fire alarm is detected. Accompanied by a display of the zone # in alarm. SUPV Appears when a fire sprinkler system supervisory condition is detected. Accompanied by a display of the zone # having the supervisory condition. CHECK Appears when a fire zone wiring fault is detected at any time. Also appears when certain system problems such as phone line problems are detec

  • ADEMCO 5110XM, –21– ACTIVATING A FIRE DRILL TEST Using the # +6+9 Keys This feature can be activated only while no alarm, supervisory, or trouble condition is present. This test requires that a keypad and external fire alarm sounder be installed with the system. Note: Only User Number 2's code can activate this test. This test activates the external fire alarm sounders for the purpose of conducting a fire alarm drill. Your system will remain operational for fire alarm signaling while this test is active ( although no me

  • ADEMCO 5110XM, –14– FIRE ALARM PROTECTION General Your system may have sensors which detect fire alarm conditions such as smoke detectors, heat detectors, sprinkler waterflow sensors, etc. You system monitors these sensors 24 hours a day for continuous protection and provides a number of indications when a fire alarm condition is detected. In Case Of Fire WHEN A FIRE ALARM CONDITION IS DETECTED, EVACUATE ALL OCCUPANTS FROM THE PREMISES IMMEDIATELY AND NOTIFY YOUR LOCAL FIRE DEPARTMENT. Your system provides the following indications when a fire alarm condition is detected: • The control's buzzer and keypad buzzer produces a slow on/off pulsing sound. • The external fire alarm sounders

  • ADEMCO 5110XM, –22– QUICK GUIDE TO SYSTEM FUNCTIONS FUNCTION PROCEDURE COMMENTS Silence Alarm, Supervisory or Trouble sounds Press the SILENCE/RESET button or Enter user Code + OFF key. SILENCED LED lights. Memory of fault remains until cleared. Keypad displays # of faulted zone. Reset Smoke Detectors & Displays Press the SILENCE/RESET button a second time or Re-enter user Code + OFF key. Will reset only if fault corrected. Manually Trip Emergency Alarms Press key [A], [B], or [C] for at least 2 sec., or press keys [1]&[Q], or [Q]&[#], or [3]&[#], both at same time

  • ADEMCO 5110XM, –7– ABOUT THE OPTIONAL KEYPADS General The keypads feature a telephone style (digital) keypad and a Liquid Crystal Display (LCD) which shows the nature and location of all occurrences. The keypads feature a built-in sounder which emits the same alarm sounds as the control's built-in warning buzzer during alarm conditions. The keypad's display screen displays the same indications as the control's built-in LED indicators, and in addition, displays the zone number of faulted zones as well as the type of fault (i.e. alarm, supervisory or trouble) present. The telephone style keypad keys allow entry of commands for silencing the warning sounds, resetting faulted smoke de

  • –5– ABOUT THE BUILT-IN INDICATORS The LED indicators, SILENCE/RESET button and WARNING buzzer (shown below) are located on the control's main board inside the control's enclosure. The AC POWER, BATTERY TROUBLE, COMMUNICATION FAIL, LINE DEFAULT and SILENCED LED indicators are visible through a viewing window on the door of the enclosure. The enclosure door must be opened wit

  • ADEMCO 5110XM, –17– BYPASSING PROTECTION ZONES Using the 6 BYPASS Key This feature can only be used if a remote keypad has been installed with the system. User code numbers 2-6 can only be used to bypass emergency and 24 hour non-fire protected zones. This key is used when you want to bypass one or more zones, thus leaving them intentionally unprotected. For example, a protected stock room door can be bypassed when it is necessary to open the door without causing an alarm. To bypass an emergency zone, do the

  • ADEMCO 5110XM, –10– REMOTE KEYPAD USER CODES General If your system has a remote keypad installed, your installer will have programmed a 4-digit user code (known as User Number 2 code) that can be entered at your keypad to silence/reset alarms, bypass protection zones and activate the fire drill test. This code may also be used to assign up to four other user codes (known as User Number 3–6 codes). The User Number 3–6 codes are intended for users who need limited and/or temporary control over system ope

  • ADEMCO 5110XM, –27– WARNING! THE LIMITATIONS OF THIS ALARM SYSTEM While this system is an advanced design security system, it does not offer guaranteed protection against burglary or fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons. For example: • Intruders may gain access through unprotected openings or have the technical sophistication to bypass an alarm sensor or disconnect an alarm warning device. • Intrusion detectors (e.g. passive infrared detectors), smoke detectors, and many other sensing devices will not work without power. Battery operated devices will not work without batteries, wit

  • ADEMCO 5110XM, –26– FEDERAL COMMUNICATIONS COMMISSION (FCC) Part 68 STATEMENT This equipment complies with Part 68 of the FCC rules. On the front cover of this equipment is a label that contains, among other information, the FCC registration number and ringer equivalence number (REN) for this equipment. If requested, this information must be provided to the telephone company. This equipment uses the following jacks: An RJ31X is used to connect this equipment to the telephone network. The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs on the telephone line may result in the devices not ringing i

  • –24– PROTECTION ZONES LIST One or more sensing devices will have been assigned by the installer of your alarm system to protection zones 01–05 in your system . For example, fire sensing devices may have been assigned to zone 05, air conditioning temperature sensors to zone 02, and so on. Zone numbers 07, 95 and 96 represent Keypad "emergency" a

  • ADEMCO 5110XM, –18– SUPERVISORY CONDITIONS General If your building has a fire sprinkler system, your installer may have installed a sensor which monitors the sprinkler system (e.g., to determine whether the main water gate valve is open or that there is adequate water pressure, etc.). Your system provides the following indications when a supervisory condition is detected. CALL YOUR INSTALLER IMMEDIATELY FOR SERVICE WHEN A SUPERVISORY INDICATION APPEARS! • The control's buzzer and the keypad buzzer both produ

  • ADEMCO 5110XM, –23– SUMMARY OF AUDIBLE/VISUAL NOTIFICATION ALPHA & FIXED-WORD DISPLAY KEYPADS SOUND CAUSE DISPLAY (Fixed-Word displays are shown in parentheses) SLOW PULSING Keypad and, as selected by installer: SLOW PULSING or STEADY External, a. FIRE ALARM b. FIRE DRILL a. FIRE plus number and descriptor of zone in alarm (FIRE ALARM plus zone #). b. FIRE DRILL ACTIVE (TEST dF) STEADY Keypad & External a. AUDIBLE EMERGENCY ALARM a. ALARM plus number and descriptor of zone in alarm (ALARM plus zone #). RAPID PULSING Keypad a. SUPERVISORY b. TROUBLE, Fire zone problem

  • –13– NORMAL STANDBY OPERATION Your system provides the following indications when in normal operation and there are no alarm, supervisory, or trouble conditions present: • The control's AC POWER LED is lit. • The control's built-in buzzer and keypad warning buzzer and external alarm sounders are off. • The Alpha keypad's LCD displays

  • –15– FIRE ALARM PROTECTION Silencing and Resetting a Fire Alarm To silence the control's buzzer, the keypad buzzer and external alarm sounders: Press the control's SILENCE/RESET button or enter your User Code followed by the OFF key at the keypad. The control's "SILENCED" LED lights and the keypad's LCD will display "FIRE AL

  • ADEMCO 5110XM, –11– REMOTE KEYPAD EMERGENCY KEYS Using Emergency Keys (for manually activating silent and/or audible alarms) Your installer may have programmed the keypad's A, B, or C keys to allow manual activation of fire and/or emergency alarms. The functions that might be programmed are: Fire, Silent Emergency, Audible Emergency, and Personal Emergency. A fire alarm sends a fire alarm message to the central station and uniquely sounds at the control and at keypad(s) and external bells and sirens. A FIRE message plus a zone number (see table on next page) is also displayed on the keypad. A sile

  • ADEMCO 5110XM, –8– FUNCTIONS OF THE REMOTE KEYPAD 1. DISPLAY WINDOW: Displays zone number and system status messages. 2. 1 OFF Key: Silences audible alarm, supervisory and trouble sounds, and clears visual display after problem's correction. 3. 6 BYPASS Key: Removes individual protection zones from being monitored by the system. 4. 8 CODE Key: Used to assign additional 4-digit user codes. 5. # Key: Used to activate fire drill. (enter user 2's code + # + 69) 6. 0 –9 Keys: Used to enter your 4-digit user code, which must be entered before pressing the OFF, BYPASS, CODE or [#] keys. 7.

  • ADEMCO 5110XM, –29– ADEMCO ONE YEAR LIMITED WARRANTY Alarm Device Manufacturing Company, a Division of Pittway Corporation, and its divisions, subsidiaries and affiliates ("Seller"), 165 Eileen Way, Syosset, New York 11791, warrants its security equipment (the "product") to be free from defects in materials and workmanship for one year from date of original purchase, under normal use and service. Seller's obligation is limited to repairing or replacing, at its option, free of charge for parts, labor, or transportation, any product proven to be defective in

More Instructions:

DOWNLOAD

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 NEC NP4001-07ZL Installation nec/np4001-07zl-996.pdf 20 Jul 2023 2
2 Kenwood TK-7100H Service manual kenwood/tk-7100h-A3O.pdf 29 Dec 2023 75
3 Migatronic SCOUT 130 E Instruction manual migatronic/scout-130-e-831.pdf 19 Dec 2023 96
4 Barefoot Sound MiniMain12 Owner's manual barefoot-sound/minimain12-L4O.pdf 28 Apr 2023 18
5 Magic Chef 6498XRA s Safety instructions magic-chef/6498xra-s-995.pdf 18 Jan 2024 17
6 D-Link DES-3526 - Switch - Stackable Operation & user’s manual d-link/des-3526-switch-stackable-Q84.pdf 29 Aug 2022 230 17.49 Mb

Similar Resources:

  • GEZE

    GC 172

    (2 pages)
    GC 172Wireless ceiling-mounted smoke detector183121-00EN Supplementary sheet1 Brief description of wireless kitThe wireless kit is part of the GEZE hold-open system FA GC 150 or FA GC 160.The wireless module GC 171, ID 163051, makes wireless communication possible between the lintel-mounted smoke switch and the various wireless devices: à Wireless ceiling- …
  • Apollo

    51000-001

    (2 pages)
    Theory of Operation The 51000-001 wireless CO detector is a low power wireless transmitter which is intended to operate on a single fixed frequency of 345.000MHz. This device operates from 3 volts DC, supplied by the Apollo CO detector CR123A battery. The Apollo CO Detector has four status bits to indicate the status of the sensor assembly. The devic …
  • System Sensor

    2112

    (4 pages)
    D200-61-00 1 I56-930-022112/24TSRB Photoelectronic Smoke DetectorINSTALLATION AND MAINTENANCE INSTRUCTIONSA Division of Pittway 3825 Ohio Avenue, St. Charles, Illinois …
  • UniPOS

    6130L

    (2 pages)
    OPTICAL SMOKE DETECTORWITH ADDRESS MODULEOPTI^KO DIMNI JAVLJA^ PO@ARA 6130L1. INTRODUCTION The Optical Smoke Detector is designed to provide early warning of a fire condition, by reacting upon a fixed smoke concentration level in the protected area. 1. UVOD Opti~ko dimni detektor je namenjen za otkrivanje po`ara u ranoj fazi, reaguju}i posle odre|enog p …
  • ESL

    700 Series

    (6 pages)
    © 2014 UTC Fire & Security Americas Corporation, Inc. 1 / 6 P/N 13083-EN • REV J • ISS 10APR14 ESL 700 Series Conventional Smoke and Heat Detector Installation Sheet Description The ESL 700 Series smoke or smoke with rate-of-rise heat detectors have field-replaceable optical chambers. The detector uses an optical sensing chamber to detect smoke …
  • Kidde

    RF-SM-DC

    (15 pages)
    READ AND SAVE THIS USER’S GUIDEWirelessSmoke Alarm• Battery-poweredThank you for purchasing a Kidde Wireless Interconnected Smoke Alarm, part of theKidde Wireless System. It is an important part of your family’s home safety plan. Youcan trust this product to provide the highest level of quality and performance. Weknow you expect nothing less when the l …

Smoke Alarm Instructions:

Comments, Questions and Opinions: