  • AEG PROTECT C. 10000, 38 The LED bargraph (LED chain on the left hand side of the ON / OFF button) show during operation the actual utilization of the UPS (chapter 8.1.1, page 45 ff). 6.1.3 Bypass Operation If the inverter is overloaded or if overtemperature is detected, e.g. also if an inverter defect is detected, voltage is supplied to the load via the bypass that switches on automatically. This is signalled by the bypass symbol. This function is also referred to as passive redundancy. It protects against total failure of the voltage supply on the protected busbar, however in the operating status that is now attained, mains faults would have a direct effect on the load.

  • AEG PROTECT C. 10000, 11 Parallel system with PROTECT C. 6000 (S) Number of UPS units Available Power 1 2 3 0 6 kVA 12 kVA 18 kVA 1 --- 6 kVA 12 kVA Active redundancy level 2 --- --- 6 kVA Parallel system with PROTECT C. 10000 (S) Number of UPS units Available Power 1 2 3 0 10 kVA 20 kVA 30 kVA 1 --- 10 kVA 20 kVA Active redundancy level 2 --- --- 10 kVA

  • AEG PROTECT C. 10000, 45 8.1.1 Table overview of LED display / alarm signals LED Display (see chapter 8 on page 42) No. Operation status Alarm signal 1 0% – 35% Utilization none 2 36% – 55% Utilization none 3 56% – 75% Utilization none 4 76% – 95% Utilization none 5 Norm,al operation (Mains there) 96% – 105% Utilization none 6 0% – 20% Capacity 1 signal per second 7 21% – 40% Capacity 1 signal every 4 seconds 8 4

  • AEG PROTECT C. 10000, 54 bypass for the loads is done, i.e. activation of the manual bypass operation, suspension of the supply for the load by the UPS bus-bar. The clearance of the voltage of each UPS is realised in the low voltage distribution. Now the expansion resp. the reduction of the parallel compound can be executed now. Watch out for the bridge between “JP1” and JP2” and the parallel operation line. The activation follows the steps in chapter 9.3.1. i For deactivating the UPS in the parallel compound just press the „OFF“ switch twice behind each other. Like this the UPS-Systems can be removed from the parallel operation

  • AEG PROTECT C. 10000, 46 Continuation overview of LED display / alarm signals LED Display (see chapter 8 on page 42) No. Operation status Alarm signal 19 Output short circuit Continous alarm signal 20 BUS voltage anomalous Continous alarm signal 21 DC circuit faulty; pos. battery error 1 signal per second 22 Battery charger faulty Continous alarm signal 23 Vent error 1 signal per second 24 Fault of inverter output relay Continous alarm signal 25 Communication interrupted Continous alarm

  • 19 ♦ Do not block the air vents of the unit! Keep children away from the unit and ensure that objects are never inserted through the air vents! ♦ Do not connect household appliances such as hairdryers to the UPS! Also take care when working with motor loads. It is essential to avoid back-feeding the inverter, e.g. if the load is intermittently operated in regenerative mode.

  • AEG PROTECT C. 10000, 42 In conjunction with the "intelligent" UPS, this ensures that the availability of IT components and data security is guaranteed. The "CompuWatch" shutdown software supports different operating systems: Windows 98SE/ME, Windows NT/2000/XP, Linux SUSE, Linux RedHat, Novell Netware, IBM AIX, HP-UX, SUN Solaris, Mac OS, and others. Refer to the manual on the CD for details about installing the software on the various operating systems. Updates can be downloaded under www.aegpss.de >> Download

  • 13 Overload behaviour up to 105 % continuous; in battery mode > 105 % for 10 s Short circuit behaviour 3 x I N for 300 ms Battery Autonomy time (full load with internal battery) PROTECT C. 6000 8 min. PROTECT C. 10000 5 min. Autonomy times with external optional battery expansions (only for PROTECT C. models): Autonomy times (full load) Coupled battery modules C.

  • AEG PROTECT C. 10000, 40 depending on the level of the overload. However, the connected load must be reduced without delay. Non-observance of the "Unit overload" condition may cause the total loss of all UPS functions! Also avoid short-term unit overloads, which may, for example, occur when connecting a laser printer or laser fax machine. Do not connect any household appliances or machine tools to the UPS. Never connect or switch on any additional loads to the UPS if there is a mains failure, i.e. if the UPS is working in emergency power operation! As a rule, if there has never been an o

  • AEG PROTECT C. 10000, 47 8.2 Fault Diagnosis / Fault Rectification The PROTEC C. generates detailed error messages. Support personal can localise and interpret faults quickly and precisely. Search for the right method and solutions recommendations referring to the errors according to chapter 8.1.1. 8.2.1 Error Messages Problem Cause Solution UPS does not start. No indication, no warning tone even though system is connected to mains power supply. Mains and battery voltage not in the tolerance range, possible battery deep discharge. Check building wiring socket outlet and input cable. LED “Line” blinks and audible signal sounding every 3 minutes. (Error No. 14) Pha

  • AEG PROTECT C. 10000, 55 10 Maintenance The PROTECT C. consists of advanced and resistant components. To guarantee a continuous and high availability it is recommended to check the unit (especially the batteries and the fans) in regular intervals (at least every 6 months). CAUTION: Before going through the next step disconnect the PROTECT C. from the mains. 10.1 Charging the Battery The battery is automatically charged when the mains is present, irrespective of the operating mode. This is signalled by the

  • 25 4.4.2 Display Explanations 1. OFF - Pushbutton 2. ON / Alarm off - Pushbutton 3. Orange LED bypass 4. Green LED inverter 5. Orange LED for battery mode (Battery) 6. Green LED for net state (Line) 7. - 11. Bar graph LEDs for UPS battery utilization resp. capacity (remaining autonomy time) 7. LED load (0-35%) battery capacity (81-100%) 8. LED l

  • AEG PROTECT C. 10000, 37 6.1.2 Battery Operation / Autonomy Operation The mains is not within the required tolerance range or has failed. In this case power is supplied to the inverter from the charged battery without interruption. The power supply to the loads is therefore also ensured in the event of a mains failure. This drains the capacity of the battery and it is discharged. This status is signalled by the battery symbol (LED Battery) lighting up, as well as an intermittent acoustic signal every 4 seconds and every second before switching off. Th

  • 27 Comments: 1. Connectors for mains input and output, additional connectors for setting single and parallel operation 2. Manual bypass switch 3. Mains input circuit breaker 4. Connection for external battery module 5. Connector for parallel operation 6. Communication slot for optional expansion cards, e.g. SNMP, USB, AS/400, … 7. Communication interface

  • AEG PROTECT C. 10000, 4 1 Notes on these Operating Instructions Duty to Provide Information These operating instructions will help you to install and operate the U ninterruptible Power Supply (UPS) PROTECT C. 6000 (S) or PROTECT C. 10000 (S) as well as the associated external battery units PROTECT C. 6000BP or PROTECT C. 10000BP – all referred to as PROTECT C. in this document – safely and properly, and for its intended purpose. These operating instructions contain important information necessary to avoid dangers during operation. Please read these instructi

  • AEG PROTECT C. 10000, 39 As a result, the electronics continuously attempt to switch back to "online" / normal operating status (e.g. when the overload or overtemperature no longer applies). The bypass is a mechanical link that switches extremely rapidly. It is located between the load and the mains. The associated synchronisation unit in the bypass ensures that the frequency and phase of the inverter voltage is synchronised with the mains. i The LED bar graph functions as display for USP utilisation. The signal goes off during this operations status every 2 seconds. 6.1

  • AEG PROTECT C. 10000, 10 voltage system on the protected busbar is of the highest quality and availability. In the event of mains faults (e.g. current failures), the voltage continues to be supplied from the inverter to the load without any interruption. From this point onwards, the inverter draws its power from the battery instead of the inverter. No switching operations are necessary; this means there is no interruption in the supply to the load. The automatic electronic bypass serves to increase the security of supply further. It switches the public mains directly through to the load if there is an inverter malfunction. As a result, the automatic bypass represents

  • AEG PROTECT C. 10000, 41 7 Interfaces and communication 7.1 Computer interfaces RS232 The UPS offers various interfaces to manage the system and to comfortable readout state information and important parameters. The communication protocol is optimized for operation with the shutdown and UPS management software “CompuWatch” from AEG. To connect the UPS to your computer use the provided RS232 communication cable by attaching them to a free port of your pc. RS232 interface: The interface is connected via a 9 pole Sub-D connector on the back of the unit (pos. 4 p. 26). PINs: 2 = Rx

  • AEG PROTECT C. 10000, 57 11 Storage, Dismantling and Disposal 11.1 Storage Long storage times without charging o r discharging the battery at regular intervals may lead to permanent damage of the battery. If the battery is stored at room temperature (20° C to 30° C) it will automatically discharge at a rate of 3 - 6% per month due to internal reactions. Storing the battery at temperatures above room temperature should be avoided. A high storage temperature also means greater battery self-discharge. Batteries

  • AEG PROTECT C. 10000, 49 9 Parallel operation 9.1 Functionality PROTECT C. 6000 (S) and C. 10000 (S) was developed for the parallel operation in n+x technology (”n“ stands for the number of necessary appliances for load supply, “x“ stands for the redundancy level). Up to three appliances of the same type can be connected in parallel to raise the output power and/or to receive a higher availability. The following constellations are possible according to the n+x technology: 1 + 0 Use of 1 unit max. 6 or 10 kVA No redundancy 1 + 1 Use of 2 units max. 6 or 10 kVA

  • AEG PROTECT C. 10000, 50 The active redundant parallel operation will switch automatically to the increase power mode if more power is required at the output of the UPS. This implements that the redundancy level decreases or will diminish completely. On the other hand the level of redundancy of the UPS will increase if the power consumption on the output decreases. The distribution generally is realised in the low voltage main distribution (LVMD) where the external and the following sub distribution for connected load circuits takes place. Such parallel control panels in wall cabinets including an external HU as

Related Products and Documents (UPS):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 Sony MPK-THA O-ring Operating instructions sony/mpk-tha-o-ring-YKU.pdf 04 Mar 2023 2 0.38 Mb
2 Philips PD7032T Operation & user’s manual philips/pd7032t-8AZ.pdf 28 Aug 2023 22 0.82 Mb
3 Mitsubishi DPSB70 Operation & user’s manual nec/dpsb70-3MC.pdf 09 Jan 2023 40
4 Craftsman 917.376164 Owner's manual craftsman/917-376164-G77.pdf 04 Dec 2023 44
5 Gionee g4 Operation & user’s manual gionee/g4-AX9.pdf 02 Feb 2024 16
6 Lenovo 440128U Hardware maintenance manual lenovo/440128u-KR8.pdf 21 Sep 2022 104

Similar Resources:

  • HP

    -380467-003 - COMPAQ PRESARIO C300 C500 C700 F500 F700 LAPTOP CHARGER

    (26 pages)
    Warranty and Support Guide  1 Year Parts and Labor  1 Year Technical Telephone Support  24 Hours a Day, 7 Days a Week Before contacting HP Total Care, it’s important to have the following information handy. Please take a moment to write down your product information for future reference. Product Name: ________________________________________ …
  • Rockwell Automation

    Allen-Bradley Bulletin 1609

    (8 pages)
    Installation Instructions(Cat 1609-D)Bulletin 1609 Industrial Uninterruptible Power Supply ATTENTION: Please read and save these instructions. This manual contains important instructions for the Bulletin 1609 Uninterrupt-ible Power Supply. Follow these instructions during the unpacking, installation and maintenance of the UPS. If you have a problem with t …
  • Tripp Lite

    SmartPro ST700HGL

    (44 pages)
    1Owner’s ManualSmartPro® Medical-Grade UPS Systems (with Lithium Iron Phosphate Batteries)Models: Important Safety Instructions 2Package Contents 5Connecting the Batteries 6Quick Installation 7Basic Operation 9Guidance and Manufacturer’s Declaration 12Storage and Service 13Regulatory Compliance and 14 Product Registration Español 15Français …
  • socomec

    MASTERYS BC 15

    (48 pages)
    MASTERYS BC15-40 kVAInstallations- und bedienungsanleitung DEInstallation and operating manual EN Manual de instalación y uso ES Asennus- ja käyttöohje FI Manuel d’installation et d’utilisation FR Manuale di installazione e uso IT Installatie– en bedieningshandleiding NLDokumentacja Techniczno-Ruchowa PLManual de instalação e funcionamento PTManua …
  • Tripp Lite

    SU3000XLCD

    (8 pages)
    Tripp Lite1111 West 35th StreetChicago, IL 60609 USATelephone: +(773) 869 1234E-mail: [email protected] #: SU3000XLCDSmartOnline 3kVA On-Line Double-Conversion UPS, Tower, Interactive LCD display, 100/110/120/127V, NEMA5-15/20R & L5-30R outlets Highlights3000VA / 3kVA / 2700 watt on-line double-conversion tower UPS 100/110/120/127V 50/60Hz ou …
  • Phasak

    KRYPTOS Series

    (28 pages)
    SERIE KRYPTOS [ES]PH 9478LEA AL MENOS ESTOSiga estrictamente todas las advertencias e instrucciones de estemanual.Antes de instalar esta unidad, lea todas las instruccionesatentamente.No utilice este SAI antes de leer atentamente toda la informaciónde seguridad y las instrucciones de uso.PELO MENOS LEIA ISTOSiga estritamente todas as advertências e instru� …

Comments, Questions and Opinions: