Allen-Bradley 1609-P8000E Operation & User’s Manual

Allen-Bradley 1609-P8000E Manual Online:

4.3, 2588 votes
Allen-Bradley 1609-P8000E User Manual
Allen-Bradley 1609-P8000E User Guide
Allen-Bradley 1609-P8000E Online Manual

Text of Allen-Bradley 1609-P8000E User Guide:

  • Allen-Bradley 1609-P8000E, 41063-261-01(1) 990-2672 09/2005 Allen-Bradley User Manual for 8000/10000 VA UPS 1609-P8000E 8000 VA 200-240 VAC 1609-P10000E 10000 VA 200240 VAC Tower/Rack-Mount 6U Uninterruptible Power Supply

  • 1 INSTALLATION Read the safety information sheet before installation. Unpacking Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The packaging is recyclable; save it for reuse or dispose of it properly. Check the package contents: q UPS q Two front bezels q Literature kit containing: q PowerChute ® B

  • Allen-Bradley 1609-P8000E, 2 Hardwiring Wiring must be performed by a qualified electrician. 1. Install a utility circuit breaker in accordance with local electrical codes (see tables below) for input wiring only. 2. Switch the UPS input circuit breaker and utility circuit breakers OFF. 3. Remove the access panel. 4. Remove circular knockouts. 5. Run wires through access panel to terminal blocks. Wire to ground block first. Adhere to all national and local electrical codes. 6. Use appropriate glands to achieve strain-relief on the hardwired input and output power cables. Input Connection Output Connection (optional) Wire to L1, L2, Wire to L1A, L2A, System Wiring Voltage

  • Allen-Bradley 1609-P8000E, 4 Connecting Power and Equipment to the UPS 1. Hardwire the UPS (see Hardwiring). 2. Connect equipment to the UPS. 3. Turn on all connected equipment. To use the UPS as a master on/off switch, be sure that all connected equipment is switched ON. 4. Press the button on the front panel to power up the UPS. • The battery charges to 90% capacity during the first three hours of normal operation. Do not expect full battery run capability during this initial charge period. OPTIONS q External Battery Pac

  • Allen-Bradley 1609-P8000E, 5 BASIC CONNECTORS serial port Power management software and interface cable can be used with the UPS. Use only a supplied or approved interface cable. Any other serial interface cable will be incompatible with the UPS connector. EPO Terminal The optional Emergency Power Off (EPO) feature allows connected loads to be immediately de-energized from a remote location, without switching to battery operation (see EPO Option). TVSS Screw The UPS features a transient voltage surge-suppression (TVSS) screw for connecting the ground lead on

  • Allen-Bradley 1609-P8000E, 6 OPERATION FRONT DISPLAY PANEL Indicator Description Online The UPS is drawing utility power and performing double conversion to supply power to connected equipment (see Troubleshooting). On Battery The UPS is supplying battery power to the connected equipment. Bypass The UPS is in bypass mode, sending utility power directly to connected equipment. Bypass mode operation is the result of an internal UPS fault, an overload condition or a user initiated command either through an accessory or the manual bypass switch. Battery operation is not available while the

  • Allen-Bradley 1609-P8000E, 7 Cold Start This is not a normal condition. Supply immediate battery power to the UPS and connected equipment (see Troubleshooting). Press and hold the button to power up the UPS and connected equipment. The UPS will emit two beeps. During the second beep, release the button. Self-Test Automatic: The UPS performs a self-test automatically when turned on, and every two weeks thereafter (by default). During the self-test, the UPS briefly operates the connected equipment on battery. Manual: Press and hold the button for a few seconds to initiate th

  • 8 USER CONFIGURABLE ITEMS NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, OPTIONAL NETWORK MANAGEMENT CARDS, OR TERMINAL MODE. FUNCTION FACTORY DEFAULT USER SELECTABLE CHOICES DESCRIPTION Automatic Self-Test Every 14 days (336 hours) Every 7 days (168 hours), Every 14 days (336 hours), On Startup Only, No Self-Test Set the interval at which the UPS will e

  • Allen-Bradley 1609-P8000E, 9 NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, OPTIONAL NETWORK MANAGEMENT CARDS, OR TERMINAL MODE. FUNCTION FACTORY DEFAULT USER SELECTABLE CHOICES DESCRIPTION Low Bypass Point -30% of output voltage setting -15%, -20%, -25%, -30% Minimum voltage that the UPS will pass to connected equipment during internal bypass operation. Output Voltage 208/230 V models: 230 VAC 208/230 V models: 200, 208, 220, 230, 240 VAC Allows the user to select the

  • Allen-Bradley 1609-P8000E, 10 EPO (Emergency Power Off) Option The output power can be disabled in an emergency by closing a switch connected to the EPO. Adhere to national and local electrical codes when wiring. Rockwell Automation recommends Allen-Bradley Catalog Number 800F Emergency Stop Operator as the interface to the EPO to connector. The switch should be connected in a normally open switch contact. External voltage is not required; the switch is driven by 12 V internal supply. In closed condition, 2m A of current are drawn. The EPO switch is internally powered by t

  • 11 Terminal Mode to Configure UPS Parameters Terminal Mode is a menu driven interface that enables enhanced configuration of the UPS. Connect the serial cable to the serial port on the back of the UPS. When using PowerChute ® Network Shutdown software: 1. Open a terminal program. Example: HyperTerminal • From the Desktop, go to Start => Programs => Acce

  • Allen-Bradley 1609-P8000E, 12 MAINTENANCE, AND TRANSPORTING Replacing the Battery Module(s) This UPS has easy to replace, hot-swappable battery modules. Replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and connected equipment on during the procedure. The battery replacement procedure must include replacing all battery modules in the UPS and connected external battery pack (s). Typical Battery life expectancy is two to four years. Upon battery disconnection, equipment is not protected from power outages. Use caution when handling heavy battery modules. Refer to Installing and Connecting the Bat

  • Allen-Bradley 1609-P8000E, 13 TROUBLESHOOTING PROBLEM AND POSSIBLE CAUSE SOLUTION UPS WILL NOT TURN ON Batteries are not connected properly. Check that the battery connectors are fully engaged. button not pushed. Press the button once to power the UPS and the connected equipment. UPS not connected to utility power supply. Check that the power cable from the UPS to the utility power supply is securely connected at both ends. Very low or no utility voltage. Check the utility power supply to ensure proper voltage at the receptacle. UPS WILL NOT TURN OFF bu

  • Allen-Bradley 1609-P8000E, 14 PROBLEM AND POSSIBLE CAUSE SOLUTION BYPASS LED ILLUMINATES The bypass switch has been turned on manually or through an accessory. If bypass is the chosen mode of operation, ignore the illuminated LED. If bypass is not the chosen mode of operation move the bypass switch on the back of the UPS, to the normal position. FAULT AND OVERLOAD LEDS ILLUMINATE; UPS EMITS A SUSTAINED ALARM TONE The UPS has ceased sending power to connected equipment. The connected equipment exceeds the specified “maximum l

  • Allen-Bradley 1609-P8000E, 15 Service If the UPS requires service do not return it to the dealer. Follow these steps: 1. Review the problems discussed in the Troubleshooting section of this manual to eliminate common problems. 2. If the problem persists, contact Rockwell Automation Customer Support. Refer to Contact Information below. 3. Pack the UPS in its original packaging. § Pack the UPS properly to avoid damage in transit. Never use Styrofoam beads for packaging. § Damage sustained in transit is not covered under warranty. Always DISCONNECT THE BATTERY(S) before shipping in compliance wit

  • Allen-Bradley 1609-P8000E, 16 Safety Information - SAVE THIS GUIDE This Safety Guide contains important instructions that should be followed during installation and maintenance of the equipment and batteries. It is intended for customers who setup, install, relocate, or maintain equipment. Changes and modifications to this unit not expressly approved could void the warranty. Handling Safety <18 kg (<40 lb) 32–55 kg (70–120 lb) 18–32 kg (40–70 lb) >55 kg (>120 lb) >10º CAUTION! Electrical Safety • Do not work alone under hazardous conditions. • High current through conductive materials could cause

Related Products and Documents (UPS):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 Conair inFiniti NE158CS Instruction manual conair/infiniti-ne158cs-GB2.pdf 12 Dec 2022 2 0.54 Mb
2 JVC XL-PG3S Instruction manual jvc/xl-pg3s-379.pdf 16 Dec 2023 2
3 AT&T MERLIN 820 Installation manual at-t/merlin-820-BK3.pdf 04 Jul 2023 40 0.62 Mb
4 Iiyama Pro Lite H511S Specifications iiyama/pro-lite-h511s-8KP.pdf 19 Feb 2023 1
5 3Com 2103R-CSDI Installation manual 3com/2103r-csdi-KYL.pdf 29 Nov 2023 92 0.82 Mb
6 Toshiba P875-S7102 Specifications toshiba/p875-s7102-M64.pdf 10 Aug 2022 4

Similar Resources:

  • INFOSEC

    X1 EX 500

    (31 pages)
    User guide ________________________ 2 Notice d’utilisation ________________ 12   _________________________ 22 500 / 700 /1000 / 1250 / 1600 / 2000 Schuko/FR Questo manuale d’istruzione è fornito da trovaprezzi.it. Scopri tutte le offerte per Infosec X1 EX1000 o cerca il tuo prodotto tra le migli …
  • Liebert

    Hinet 10kVA

    (43 pages)
    Manual Reference number : 6390001 H - 2 (12/01) Rev ENP Au 07/2002 HHIINNEETT UUPPSS SSYYSSTTEEMM 1100 –– 3300 kkVVAA 33xx11 UUsseerr MMaannuuaall …
  • Silicon Solar

    Aquajet-Pro-Kit-24V-Battery

    (2 pages)
    SOLAR BATTERY BACK-UP USER’S MANUALDesign for solar fountain pumpItem No.: Aquajet-Pro-Kit-24V-Battery1. OVERVIEW1) This special solar battery back-up is designed specifically for solar fountain pump. It canstore solar energy for day or night use.2) The input power should be from a solar module or DC power supply with an outputvoltage of 18V. 3) The …
  • Huawei

    UPS2000-G-3KRTLL

    (20 pages)
    1Issue: 01Date: 2020-10-26UPS2000-G-3KRTLL Quick GuideCopyright © Huawei Technologies Co., Ltd. 2020. All Rights Reserved.1OverviewUPS Model Represented By Weight Dimensions (H x W x D)UPS2000-G-3KRTLL3kVA15 kg88 mm x 438 mm x 480 mm(1) Liquid crystal display (LCD)(2) Maintenance bypass (MBS) port(3) Optional card slot(4) Battery management system (BMS) po …
  • Tripp Lite

    SmartPro SLT SMX1050SLT

    (9 pages)
    Owner’s Manual1111 W. 35th Street Chicago, IL 60609 USACustomer Support: (773) 869-1234 • www.tripplite.comImportant Safety Instructions2Quick Installation3Basic Operation5Storage and Service8EspañolCopyright © 2006 Tripp Lite. All rights reserved. SmartPro®is a trademark of Tripp LiteSmartPro®SLTIntelligent, Line-Interactive UPS System• 220/230/2 …
  • Huawei

    UPS5000-E Series

    (16 pages)
    1Issue: 04Part Number: 31508115Date: 2019-06-20UPS5000-E-(25 kVA–125 kVA)-FM Quick GuideCopyright © Huawei Technologies Co., Ltd. 2019. All rights reserved.1OverviewUPS Model Capacity ConfigurationWeight (Full Configuration)Dimensions (H x W x D)UPS5000-E-125K-FM25 kVA, 50 kVA, 75 kVA, 100 kVA, 125 kVA330 kg2000 mm x 600 mm x 850 mm(1) Mains input switch …

Comments, Questions and Opinions: