  • Installation Instructions These instructions must be read in conjunction with the Installation instructions supplied with the boiler. Only flue components supplied by Alpha may be used with Alpha boilers, failure to comply will invalidate the boiler's warranty and CE approval, and may be unsafe. Suitable for use with the Alpha CB 24/28, C and SY range of g

  • Alpha Alpha Twin Pipe Flue Systems, 2 Twin Pipe Flue Systems 1 COMPONENTS AVAILABLE TO ORDER 1. The flue system must be installed in accordance with BS 5440:1. 2. The boiler must be installed in accordance with the Installation and Servicing instructions supplied with the boiler. 3. The maximum equivalent flue lengths are as given below. (Refer to illustrations in section 3). Alpha Boiler Horizontal Flue Vertical Flue (Inc. Terminal) CB/SY range 10 m 7 m Note: Ensure the flue length does not exceed the equivalent shown in the table abov

  • Alpha Alpha Twin Pipe Flue Systems, 3 Twin Pipe Flue Systems 3 FLUE OPTIONS 3.1 HORIZONTAL FLUE OPTIONS - Lmax = 10 m L = Equivalent length of flue or air duct (a 90° bend is equivalent to 1.0 m of flue length and a 45° bend is equivalent to 0.5 m of flue length). Note: No more than four bends (90° or 45°) must be used on the flue exhaust or air inlet duct. A = Total length of flue/air ducting required. Fig. 1 Fig. 2

  • Alpha Alpha Twin Pipe Flue Systems, 4 Twin Pipe Flue Systems 3.2 VERTICAL FLUE OPTION - Flat or pitched roof The vertical flue terminal is equivalent to 1 m of flue length. Note: A 90° bend must not be used with a vertical flue. No more than four bends (90° or 45°) must be used on the flue exhaust or air inlet duct. Fig. 4 3.3 VERTICAL FLUE OPTION - Ridge tile Fig. 3

  • 5 Twin Pipe Flue Systems 4 INSTALLATION 4.1 INSTALL THE BOILER Mount the boiler on the wall and connect the pipework as described in the Installation and Servicing instructions supplied with the boiler. 4.2 CONVERT THE BOILER (see Fig. 5) Modify the top of the boiler to enable a 2-pipe flue system to be connected using conversion kit 6.1000368 as follows:- 1. Place the flue duct adaptor in pos

  • Alpha Alpha Twin Pipe Flue Systems, 6 Twin Pipe Flue Systems 4.3 ASSEMBLE THE FLUE DUCTS Particular site conditions will dictate the sequence in which the flue is assembled. However, start assembling the flue system at the boiler noting the following:- 1. Cut 85 mm holes for plain flue/air ducts. Cut 100 mm holes for flue/air ducts with connection sockets. Note: All parts of the flue duct must be at least 25 mm from combustible material. 2. Depending on the type of socket, sockets take a full engagement of either 50 mm or 40 mm. Always fully engage flue/air ducts into the socket. 3. Cut only plain ends of the duct and always deburr. 4 When assembled it must not be possible to disengage any part of the flue

  • Alpha Alpha Twin Pipe Flue Systems, 7 Twin Pipe Flue Systems HORIZONTAL TERMINAL POSITIONING Separated flue duct terminal Separated air duct terminal Flue and air ducts located together on the same wall Fig. 10 Fig. 8 Fig. 9 2. Vertical terminal (see Fig. 3) i) Refer to Fig. 3 for positioning of the vertical terminal in the roof. Note: Under no circumstances must the terminal be shortened in length. ii) To enable direct connection of the flue and air ducts to the terminal the duct centres must be 120 mm apart. iii) At the required position cut a hole

  • Alpha Alpha Twin Pipe Flue Systems, FLUE TERMINAL LOCATION The flue terminal must be exposed to the external air and the position must allow the free passage of air across it at all times. In certain weather conditions the terminal may emit a plume of steam. Avoid positioning the terminal where this may cause a nuisance. If the terminal is fitted within 850 mm of a plastic or painted gutter or 450 mm of painted eaves or 300 mm of a plastic car port roof or drain/soil pipe, an aluminium shield at least 1 m long should be fitted to the underside of the gutter, roof or painted surface. If the ter

Related Products and Documents (Boiler):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 Sony DAV-X1 Specifications sony/dav-x1-833.pdf 17 Apr 2023 2 1.28 Mb
2 Toa N-VR2010 Product catalog toa/n-vr2010-6G2.pdf 14 Jan 2023 3 0.21 Mb
3 Barracuda Networks Network Router Operation & user’s manual barracuda-networks/network-router-YJ4.pdf 19 Jul 2022 2 0.28 Mb
4 Philips AJ3910 Specifications philips/aj3910-VX5.pdf 03 Aug 2022 2 0.48 Mb
5 Sherwin-Williams Tradeworks Operation manual sherwin-williams/tradeworks-ZM5.pdf 03 Sep 2022 42 2.83 Mb
6 Blackberry 7510 - iDEN Safety and product information blackberry/7510-iden-93S.pdf 25 Jun 2022 9 0.17 Mb

Similar Resources:

  • Aerco

    KC Series

    (106 pages)
    Printed in U.S.A. REVISED 12/10 AERCO International, Inc. • 159 Paris Ave. • Northvale, New Jersey 07647 • Phone: 201-768-2400 • FAX: 201-768-7789 KC Series Gas Fired Water Heater GF-111 OMM-xxxx-xx Operation and Maintenance Manual Applicable to Serial Numbers G-02-530 and above KC Series Gas Fired Water Heating System Natu …
  • ferolli

    DIVA HF24

    (80 pages)
    DIVA HFUA - ȱɇɋɌɊɍɄɐȱə Ɂ ȿɄɋɉɅɍȺɌȺɐȱȲ, ɆɈɇɌȺɀɍ ɌȺ ɈȻɋɅɍȽɈȼɍȼȺɇɇəEN - INSTRUCTIONS FOR USE, INSTALLATION AND MAINTENANCEFR - INSTRUCTIONS D'UTILISATION, D'INSTALLATION ET D'ENTRETIENPL - INSTRUKCJA OBSáUGI, INSTALACJI I KONSERWACJIRO - INSTRUCğIUNI DE UTILIZARE, INSTALARE ùI ÎNTRETINERE TR - KUL …
  • Baxi

    Combi 133 HE Plus

    (12 pages)
    © Baxi Heating UK Limited 2005Please keep these instructions in a safe place.If you move house, please hand them over to the next occupier.Baxi Combi 133 HE PlusBaxi Combi 100 HE PlusBaxi Combi 80 HE PlusGas Fired Wall Mounted CondensingCombination BoilerUser’s Operating Instructions &Important Warranty Information …
  • MHS Boilers

    MONOMAX N Series

    (30 pages)
    PRESSURISED STEEL BOILERGAS, LIGHT OIL AND DUAL FUELSERIES: INSTRUCTIONS FOR INSTALLATION AND USEMONOMAXN/NSNC/NCSDUOMAXN/NSPN/PNSiMHSLB1957 • 23/03/2009 …
  • Keston

    System s30

    (72 pages)
    August 2016UIN 215352 A01When replacing any part on this appliance, use only spare parts that you can beassured conform to the safety and performance specication that we require.Do not use reconditioned or copy parts that have not been clearly authorised by Keston.For the very latest copy of literature for specication and maintenance practices visit ou …
  • Alpha

    Alpha 240 Boiler Range

    (2 pages)
    Instructions for setting the burnerpressures on the gas valveAlpha 240, 280 and 500 Boiler Range1. GENERALThe maximum and minimum burner pressures are factory set and should not require adjusting. However, if the gas valvehas been replaced, then these burner pressures must be set by adjustment on the gas valve. Refer to the Installation andServicing instruct …

Comments, Questions and Opinions: