  • Siemens SIPROTEC 7SD610, Appendix A.7 Settings SIPROTEC, 7SD610, Manual C53000-G1176-C145-6, Release date 02.2011 391 2686 I>Dir.Telep/BI Back-Up O/C NO YES NO Instantaneous trip via Tele- prot./BI 2687 I> Dir. SOTF Back-Up O/C NO YES NO Instantaneous trip after Switch- OnToFault 2688 Direction IP Back-Up O/C Forward Reverse Forward Direction of stage Ip> Dir. 2689 Ip> Dir. Back-Up O/C 1A 0.10 .. 4.00 A; ∞∞A Ip> directional Pickup 5A 0.50 .. 20.00 A; ∞∞A 2690 T Ip Dir. Back-Up O/C 0.05 .. 3.00 sec; ∞ 0.50 sec T Ip Dir.: Inv.-Time delay for IEC- Char. 2691 D Ip Dir. Back-Up O/C 0.50 .. 15.00 ; ∞ 5.00 D 3I0p Dir.:Inv.-Time delay for

  • Functions 2.2 Protection Data Interfaces and Protection Data Topology SIPROTEC, 7SD610, Manual C53000-G1176-C145-6, Release date 02.2011 63 2.2.4 Differential Protection Topology 2.2.4.1 Setting Notes Protection data topology First of all, define your protection data communication topology: Number the devices consecutively. This num- bering is a serial device index that serve

  • Siemens SIPROTEC 7SD610, Functions 2.17 Additional Functions SIPROTEC, 7SD610, Manual C53000-G1176-C145-6, Release date 02.2011 243 Figure 2-112 WEB-Monitor – Example of voltages and currents Furthermore, the browser enables a clear display of the most important measured data. The measured values list can be selected from the navigation toolbar separately for the local and the remote device. In each case a list with the desired information is displayed (see Figures 2-112 and 2-114). Figure 2-113 Local measured values in the WEB-Monitor — Examples for measured values

  • Siemens SIPROTEC 7SD610, Mounting and Commissioning 3.1 Mounting and Connections SIPROTEC, 7SD610, Manual C53000-G1176-C145-6, Release date 02.2011 286 3.1.2.5 Reassembly The device is assembled in the following steps: • Insert the modules carefully in the housing. The mounting locations are shown in figure 3-3. For the model of the device designed for surface mounting, use the metal lever to insert the C-CPU-2 board. The installa- tion is easier with the lever. • First insert the plug connectors of the ribbon cable on the input/output

  • Siemens SIPROTEC 7SD610, Technical Data 4.15 User defined functions (CFC) SIPROTEC, 7SD610, Manual C53000-G1176-C145-6, Release date 02.2011 360 4.15 User defined functions (CFC) Function Blocks and their Possible Allocation to the Priority Classes Function Module Explanation Task Level MW_BEARB PLC1_BEARB PLC_BEARB SFS_BEARB ABSVALUE Magnitude Calculation X – – – ADD Addition X X X X ALARM Alarm clock X X X X AND AND - Gate X X X X BLINK Flash block X X X X BOOL_TO_CO Boolean to Control (conversion) – X X – BOOL_TO_DI Boolean to Double Point (conversion) –X X X BOOL_TO_IC Bool to Internal SI, Conversion – X X X BUILD_DI Create Double Point Annunciation –X X X CMD_CANCEL Cancel command

  • Introduction 1.3 Characteristics SIPROTEC, 7SD610, Manual C53000-G1176-C145-6, Release date 02.2011 24 1.3 Characteristics General Features • Powerful 32-bit microprocessor system • Complete digital processing of measured values and control, from the sampling of the analog input values, the processing and organization of the communication between devices up to the closi

  • Siemens SIPROTEC 7SD610, Functions 2.17 Additional Functions SIPROTEC, 7SD610, Manual C53000-G1176-C145-6, Release date 02.2011 250 2.17.4 Measurement During Operation 2.17.4.1 Function Description A series of measured values and the values derived from them are available for on-site retrieval or for data transfer. A precondition for the correct display of primary and percentage values is the complete and correct entry of the nominal values of the instrument transformers and the power system as well as the transformation ratio of the current and voltage transformers in the earth paths. Display of measured values Operational measured values and metered

  • Siemens SIPROTEC 7SD610, Functions 2.15 Monitoring Functions SIPROTEC, 7SD610, Manual C53000-G1176-C145-6, Release date 02.2011 216 2.15.1.7 Settings Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings. The table indicates region-specific presettings. Column C (configuration) indicates the corresponding second- ary nominal current of the current transformer. Addr. Parameter C Setting Options Default Setting Comments 2901 MEASURE. SUPERV ON OFF ON Measurement Supervision 2902A BALANCE U-LIMIT 10 .. 100 V 50 V Voltage Threshold for Balance Monitoring 2903A BAL. FACTOR U 0.58 .. 0.95 0.75 Balance Fac

  • Siemens SIPROTEC 7SD610, Technical Data 4.1 General SIPROTEC, 7SD610, Manual C53000-G1176-C145-6, Release date 02.2011 329 Time synchronisation interface Ethernet electrical (EN 100) for IEC 61850 and DIGSI FOC connector type ST connector receiver/transmitter Connection for flush mounting housing Rear panel, mounting location „B“ Connection for surface mounting housing Not deliverable Optical Wavelength λ = 1350 nm Transmission rate 100 Mbit/s Laser class 1 according to EN 60825-1/-2 using glass fibre 50 μm/125 μm or using glass fibre 62,5 μm/125 μm Permissible path attenuation max. 5 dB, with glass fibre 62,5 μm/125 �

  • Siemens SIPROTEC 7SD610, Functions 2.18 Command Processing SIPROTEC, 7SD610, Manual C53000-G1176-C145-6, Release date 02.2011 266 2.18.3.2 Information List 2.18.4 Protocol 2.18.4.1 Information List ■ No. Information Type of In- formation Comments - >Door open SP >Cabinet door open - >CB wait SP >CB waiting for Spring charged - >Err Mot U SP >Error Motor Voltage - >ErrCntrlU SP >Error Control Voltage - >SF6-Loss SP >SF6-Loss - >Err Meter SP >Error Meter - >Tx Temp. SP >Transformer Temperature - >Tx Danger SP >Transformer Danger No. Information Type of In- formation Comments - SysIntErr. Int

  • Functions 2.2 Protection Data Interfaces and Protection Data Topology SIPROTEC, 7SD610, Manual C53000-G1176-C145-6, Release date 02.2011 50 2.2 Protection Data Interfaces and Protection Data Topology Devices protecting an object protected by current transformer sets, must exchange data of the protected object. This applies not only to the measured quantities relevant to the actual

  • Siemens SIPROTEC 7SD610, Mounting and Commissioning 3.1 Mounting and Connections SIPROTEC, 7SD610, Manual C53000-G1176-C145-6, Release date 02.2011 280 Input/Output Board C-I/O-11 Figure 3-6 C-I/O-11 input/output board with representation of jumper settings required for checking con- figuration settings Table 3-8 Jumper settings for Control Voltages of the binary inputs BI6 and BI7 on the input/output board C-I/O-11 1) Factory settings for devices with power supply voltages of DC 24 V to 125 V 2) Factory settings for devices with power supply

  • Siemens SIPROTEC 7SD610, Functions 2.3 Differential Protection SIPROTEC, 7SD610, Manual C53000-G1176-C145-6, Release date 02.2011 70 The charges of both ends of the protected object are added in the same way as done with the current phasors of the differential protection. Thus the total of the charges is available at both ends of the protected zone. Immediately after a fault has occurred in the protected zone, a charge difference emerges. For high fault cur- rents which can lead to saturation of current transformers, a decision is thus r

  • Siemens SIPROTEC 7SD610, Functions 2.17 Additional Functions SIPROTEC, 7SD610, Manual C53000-G1176-C145-6, Release date 02.2011 246 Figure 2-115 Operational measured values in the default display Default display 3 shows the measured power values and the measured values U L1-L2 and I L2 . Figure 2-116 Operational measured values in the default display Moreover, the device has several event buffers for operational indications, fault indications, switching statistics, etc., which are protected against loss of auxiliary supply by means of a backup battery. These indications can be displayed on the LCD at any time by selection using the keypad or transferred to a personal computer vi

  • Siemens SIPROTEC 7SD610, Functions 2.10 Automatic Reclosure Function (optional) SIPROTEC, 7SD610, Manual C53000-G1176-C145-6, Release date 02.2011 139 Figure 2-53 Connection example for 2 protection devices with 2 automatic reclosure functions BI Binary inputs M Signal output K Command * ) for all protection functions operating with AR.

  • Functions 2.15 Monitoring Functions SIPROTEC, 7SD610, Manual C53000-G1176-C145-6, Release date 02.2011 215 Broken wire monitoring The broken wire monitoring is enabled or disabled via the parameter 2931 BROKEN WIRE. The differential pro- tection function is only blocked with the setting ON. By means of the setting Alarm only, a broken wire can be signalled; the protection functions are not blocke

  • Siemens SIPROTEC 7SD610, Index SIPROTEC, 7SD610, Manual C53000-G1176-C145-6, Release date 02.2011 446 Overtemperature 198 Overvoltage protection 153 Compounding 156 Negative sequence system U 2 157, 165, 353 Optional single-phase voltage 353 Phase-earth 352 Phase-phase 154, 352 Phase-to-earth 164 Phase-to-phase 164 Positive sequence system U 1 164 Positive sequence systemU 1 155, 352 Zero sequence system 3U 0 353 Zero-sequence system 165 Zero-sequence system 3U 0 158 P Phase Angle Monitoring 210 Phase currents 84 Phase-segregated initiation of the circuit breaker failure protection 183 Pickup logic 111 Pickup Logic of the Entire Device 230 Polarity check 313 Polari

  • Siemens SIPROTEC 7SD610, Appendix A.7 Settings SIPROTEC, 7SD610, Manual C53000-G1176-C145-6, Release date 02.2011 393 3455 1.AR Tdead 3Flt Auto Reclose 0.01 .. 1800.00 sec; ∞ 0.50 sec Dead time after 3phase faults 3456 1.AR Tdead1Trip Auto Reclose 0.01 .. 1800.00 sec; ∞ 1.20 sec Dead time after 1pole trip 3457 1.AR Tdead3Trip Auto Reclose 0.01 .. 1800.00 sec; ∞ 0.50 sec Dead time after 3pole trip 3458 1.AR: Tdead EV. Auto Reclose 0.01 .. 1800.00 sec 1.20 sec Dead time after evolving fault 3459 1.AR: CB? CLOSE Auto Reclose YES NO NO CB ready interrogation before re- closing 3460 1.AR SynRequest Auto Reclose YES NO NO Request for

  • Siemens SIPROTEC 7SD610, Functions 2.9 Backup Time Overcurrent Protection SIPROTEC, 7SD610, Manual C53000-G1176-C145-6, Release date 02.2011 113 Table 2-4 Trip signals of the single phases 1) If tripping by the 3I0 measuring unit is performed simultaneous with or after tripping by a phase measuring unit and if single-pole tripping is effective, „O/C TRIP 1p.L1“, „O/C TRIP 1p.L2“ or „O/C TRIP 1p.L3“ is sig- naled. 2) If tripping is only performed by the 3I0 measuring unit but not by a phase measuring unit, „O/C TRIP L123“ is signaled. Internal indication Display Output indi

  • Siemens SIPROTEC 7SD610, Functions 2.12 Frequency Protection (optional) SIPROTEC, 7SD610, Manual C53000-G1176-C145-6, Release date 02.2011 175 2.12.2 Setting Notes General Frequency protection is only in effect and accessible if address 136 FREQUENCY Prot. is set to Enabled during configuration of protection functions. If the function is not required, Disabled is to be set. The frequency protection function features 4 frequency stages f1 to f4 each of which can function as overfre- quency stage or underfrequency stage. Each stage can be set active or inactive. This is set in addresses: • 3601 O/U FREQ. f1 for frequency stage f1, • 3611 O/U FREQ. f2 f

  • Siemens SIPROTEC 7SD610, Functions 2.6 Direct Local Trip SIPROTEC, 7SD610, Manual C53000-G1176-C145-6, Release date 02.2011 91 2.6.3 Settings 2.6.4 Information List Addr. Parameter Setting Options Default Setting Comments 2201 FCT Direct Trip ON OFF OFF Direct Transfer Trip (DTT) 2202 Trip Time DELAY 0.00 .. 30.00 sec; ∞ 0.01 sec Trip Time Delay No. Information Type of In- formation Comments 4403 >BLOCK DTT SP >BLOCK Direct Transfer Trip function 4412 >DTT Trip L1 SP >Direct Transfer Trip INPUT Phase L1 4413 >DTT Trip L2 SP >Direct Transfer Trip INPUT Phase L2 4414 >DTT Trip L3 SP >Direct Transfer Trip INPUT Phase L3 4417 >DTT Trip L123 SP >Direct Transfer Trip INPUT 3ph L123 4421

  • Siemens SIPROTEC 7SD610, Functions 2.9 Backup Time Overcurrent Protection SIPROTEC, 7SD610, Manual C53000-G1176-C145-6, Release date 02.2011 123 2.9.5 Information List No. Information Type of In- formation Comments 7104 >BLOCK O/C I>> SP >BLOCK Backup OverCurrent I>> 7105 >BLOCK O/C I> SP >BLOCK Backup OverCurrent I> 7106 >BLOCK O/C Ip SP >BLOCK Backup OverCurrent Ip 7107 >BLOCK O/C Ie>> SP >BLOCK Backup OverCurrent Ie>> 7108 >BLOCK O/C Ie> SP >BLOCK Backup OverCurrent Ie> 7109 >BLOCK O/C Iep SP >BLOCK Backup OverCurrent Iep 7110 >O/C InstTRIP SP >Backup OverCurrent Instantan

Related Products and Documents (Relays):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 NordicTrack T9ci Operation & user’s manual nordictrack/t9ci-TTQ.pdf 25 May 2023 40
2 GE JTS10SPSS Owner's manual ge/jts10spss-YVZ.pdf 22 Dec 2023 44 1.08 Mb
3 Hasbro Toad Double Bubble Instructions hasbro/toad-double-bubble-8JU.pdf 17 Nov 2023 1 0.15 Mb
4 CCTV CCM-1481 Operation & user’s manual cctv/ccm-1481-E5U.pdf 10 Sep 2023 8 0.14 Mb
5 Philips CD2301S/73 Operation & user’s manual philips/cd2301s-73-4X4.pdf 06 Aug 2022 35 0.62 Mb
6 Soleus Air GL-DEH SERIES Operating instructions manual soleus-air/gl-deh-series-1LM.pdf 31 May 2023 11 0.78 Mb

Similar Resources:

  • GE

    C30

    (488 pages)
    GEGrid SolutionsInstruction ManualProduct version: 7.6xGE publication code: 1601-0088-AF1 (GEK-130993)C30Controller System1601-0088-AF1IISO 9001GNEI LMIUTLTESIRGEEDRLISTED52TLIND.CONT. EQ.E83849 …
  • MITSUBISHI ELECTRIC ENGINEERING

    DG2BK1TB Series

    (2 pages)
    Drive Goods Relay Terminal Block with Brake Contact Output Model Name DG2BK1TB-□-□ User’s Manual Before Using the Product Thank you for purchasing these Drive Goods product. Before using the product, this document and our MEEFAN homepage obtain the User’s Manual of the publication, and please read the following items. ・ SAFETY PRECAUTIONS …
  • PickData

    TIR Two

    (4 pages)
    V01-050417 TIR Two TIR Two (Temperature Inputs Relays) is a digital signals and impulse centralizer. In only 4 DIN modules, the unit has 2 relay outputs, 2 voltage free digital inputs and 2 NTC/PTC inputs for temperature sensors. The device works with LoRaTM protocol for long range radio communications, with maximum communication’s ra …
  • Danfoss

    vlt series

    (56 pages)
    0 - 1IntroductionSafety Precautions 0 - 2Required Tools 0 - 3Section OneDescription of Operation 1 - 1Sequence of Operation 1 - 4Section TwoFault Indicators and Messages 2 - 1Troubleshooting Tips 2 - 5Troubleshooting Flowchart 2 - 6Symptom/Cause Chart 2 - 9Section ThreeStatic Test Procedures 3 - 1Dynamic Test Procedures 3 - 6Section FourComponent Replacement …
  • ABB

    Relion REB500

    (24 pages)
    RELION® REB500Distributed busbar protection REB500Version 8.3 IECCommissioning manual� …
  • AJAX Systems

    Relay

    (11 pages)
    Relay User ManualUpdated January 27, 2021Relay is a wireless, low-voltage relay featuring potential-free (dry) contacts. UseRelay to remotely switch on/off appliances powered by a 7–24 V DC source. Relaycan operate both in pulse and bistable mode. The device communicates with a hubvia radio protocol. In the line of sight, the communication distance is up …

Comments, Questions and Opinions: