EMS FIRECELL Maintenance Manual

EMS FIRECELL Manual Online:

3.5, 1176 votes
EMS FIRECELL User Manual
EMS FIRECELL User Guide
EMS FIRECELL Online Manual

Text of EMS FIRECELL User Guide:

  • EMS FIRECELL, Contents Overview 3 Pre-testing Guidelines 4 Daily Maintenance 4 Weekly Maintenance 5 Six Monthly Maintenance 6 Annually Maintenance 7 Four-Five Yearly Maintenance 8 Battery Information 9 Fire Control Panel / PSU Batteries 9 Page 2 of 10

  • EMS FIRECELL, Overview It is important that re alarm systems are regularly checked to ensure their continued correct operation. The maintenance of re alarm systems should be in accordance with applicable local installation codes. This maintenance guide has been written in conjunction with British Standard BS5839: Part 1. Important Note: other local installation codes may vary. The owner or other person having control of the premises should appoint a responsible person to supervise the system. The person should be given sucient authority to ensure the carrying out of any necessary work to maintain the syste

  • EMS FIRECELL, Pre-testing Guidelines It is important to ensure that operation during testing does not result in a false re alarm. If the re alarm system is connected to an automatic dialling unit, then transmission should be prevented (for instance by disconnection) before the routine test is carried out, since under normal conditions test calls are not permitted. In certain equipment using automatic dialling, it is possible to prevent transmission of signals by lifting a telephone receiver. Use of this function to inhibit trans

  • EMS FIRECELL, Page 5 of 10 Weekly Maintenance These checks would normally be carried out by a responsible member of the building sta. They should also be carried out by the service engineer after all routine maintenance checks. Note: When reference is made to the controller, the actions should be carried out / checked on all repeater units tted on the system. The re alarm system testing should be in accordance with applicable local installation codes. The following checks should be made:- a) If necessary, clean the front panel of the controller with a suitable cleansing agent. i.e. anti sta

  • EMS FIRECELL, Page 6 of 10 Six Monthly Maintenance Note: When reference is made to ancillary equipment, the actions should be carried out / checked on all Radio Cluster Communicator units tted on the system and also the Radio Hub were applicable. The following checks should be made:- a) Perform the weekly checks. b) Check the entries in the log book and carry out any necessary action. c) Test all call points and 50% of automatic devices and conrm correct operation as detailed in weekly tests point d) Check device signal strength readings against the recorded commissioning levels as per FireCell minimu

  • EMS FIRECELL, Page 7 of 10 Yearly Maintenance Note: When reference is made to ancillary equipment, the actions should be carried out / checked on all Radio Cluster Communicator units tted on the system and also the Radio Hub were applicable. The following checks should be made:- a) Carry out all six monthly checks. b) Visually check the inside and outside of the controller / repeater panel for damage. c) Check for damage to, and paint on, all detection devices. d) Check for damage and accumulations of dirt on smoke detectors. DO NOT CLEAN; these units MUST be exchanged and returned to the factory for service. An

  • Page 8 of 10 Four-Five Yearly Maintenance The following checks should be made:- a) Carry out all annual checks. b) Inform the responsible person that “x” number of batteries require to be replaced. c) Replacement batteries are required in the following equipment; i) All Radio Type Device Variants ii) Radio Cluster Communicators d) The Battery In

  • EMS FIRECELL, Page 9 of 10 Battery Information FireCell Equipment Type FireCell Control Panel/PSU RCC Callpoint Detector Combined Sounder & Detector Sounder / Sounder-Strobe or Visual Indicator Input/Output Unit Typical Battery Life Up to 5 years* Up to 5 years*‡ Up to 5 years* Up to 5 years* Up to 5 years* Up to 5 years* Up to 5 years* Batteries Required As per system design† 1x 6V 4Ah 6 x AA Alkaline cells 6 x AA Alkaline cells 3 x AA Alkaline cells 3 x C Alkaline cells 3 x AA Alkaline cells 3 x C Alkaline cells 6 x AA Alkaline cells * Typical 5 year battery life, based on normal usage † See th

  • EMS FIRECELL, Page 10 of 10 www.emsgroup.co.uk Third Party Accredited ISO 9001 ISO 13485 ISO 14001 The information contained within this literature is correct at time of publishing. The EMS Security Group Ltd reserves the right to change any information regarding products as part of its continual development enhancing new technology and reliability. The EMS Group advises that any product literature issue numbers are checked with its head oce prior to any formal specication being written.

Related Products and Documents (Fire Alarms):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 Hotsy 558 Operating instructions and parts manual hotsy/558-E8M.pdf 20 Mar 2024 17
2 Axiom SW218XA Operation & user’s manual axiom/sw218xa-M8C.pdf 17 Dec 2023 8
3 GME FG-3005 Operation & user’s manual gme/fg-3005-Q94.pdf 06 Mar 2024 10
4 CYP CLUX-4M Operation manual cyp/clux-4m-DTT.pdf 04 Sep 2022 8
5 Hallicrafters SR-150 Operating and service instructions hallicrafters/sr-150-KAM.pdf 25 Mar 2023 43
6 Gigabyte GA-6VTXE-A Operation & user’s manual gigabyte/ga-6vtxe-a-92A.pdf 10 Mar 2023 64 1.17 Mb

Similar Resources:

  • Ziton

    ZP700 Series

    (4 pages)
    ZP700 Series Addressable Detector Installation Sheet 1 2 3 4 EN: Installation Sheet Description ZP700 Series Addressable Detector models are shown in Table 1. Table 1: Models Number Description ZP720-3P Addressable Thermal Sensor, Polar White ZP730-2P ZP730-2B ZP730-2S30 Addressable Optical Smoke Sensor, Polar White Addressable Optical Smoke Senso …
  • bolid

    IPR 513-3M

    (2 pages)
    1 RESETTABLE MANUAL CALL POINT IPR 513-3M INSTRUCTION MANUAL 1 TECHNICAL DATA 1.1 General IPR 513-3M Resettable Manual Call Point (hereinafter referred to as the call point or the IPR 513-3M) is designed to be used in fire alarm systems and fixed fire-fighting systems to manually release fire alarms or activate the system respectively. The IPR 513-3M is t …
  • Bosch

    WFMC220BUC

    (96 pages)
    enfresOperating, Care and Installation Instructi"o:n','_........................_' ,,,_Seche-hnge: Nohce d'uhlsation, de maint_'5'an,_'_ et d'lnstallatio_Secador; Operacion, culdado y instrucciones,,,,,,pa_a la instalaci6_};,! …
  • Wheelock

    ET-1010

    (4 pages)
    P82055 S Sheet 1 of 4 273 Branchport Avenue Long Branch, NJ 07740 (800) 631-2148 www.wheelockinc.com Thank you for using our products. INSTALLATION INSTRUCTIONS ET-1010 VANDAL RESISTANT SPEAKER Use this product according to this instruction manual. Please keep this instruction manual for future reference. GENERAL: Wheelock’s Series ET-101 …
  • MEDC

    SM87BG

    (28 pages)
    © MEDC 2015 07/15      Please note that every care has been taken to ensure the accuracy of our technical manual. We do not, how-ever, accept responsibility for damage, loss or expense result-ing from any error or omission. We reserve the right to make alterations in line with techn …
  • Ei Electronics

    Ei 204EN

    (32 pages)
    Model Ei 204ENModel Ei 205ENModel Ei 205ENAModel Ei 205CEN- STANDARD- WITH MEMORY- WITH MEMORY &SEALED IN BATTERIES- WITH MEMORY &INTERCONNECTRead and retain carefully for as long as the product is being used. It contains vital informationon the operation and installation. The leaflet should be regarded as part of the product.If you are just installi …

Comments, Questions and Opinions: