  • Mega MEg101.4, MEgA – Měřící Energetické Aparáty, a.s.MEgA – Měřící Energetické Aparáty, a.s. 664 31 Česká 390664 31 Česká 390 Czech RepublicCzech Republic Uninterruptible power supply Supply MEg101.4

  • Mega MEg101.4, Uninterruptible power supply Supply MEg101.4 3 Uninterruptible power supply MEg101.4 1/ CHARACTERISTICS e uninterruptible power supply MEg101.4 is designed for feeding the measuring and communication devices with 12 V nominal supply voltage. Its core is a High-frequen- cy voltage converter that converts the supply voltage with high eciency to the output uninterruptible DC voltage. When the supply voltage is interrupted, the power supply delivers the output DC voltage from the internal supercapacitor for 3 sec at least or if an external a 12 V lead-acid accumulator is connected, it will extend duration of power

  • Mega MEg101.4, Měřící Energetické Aparáty 4 2/ TECHNICAL DATA Power supply MEg101.4 input Supply voltage: DC AC, f = 50 Hz Rated voltage: 220 V DC 230 V AC Minimum voltage: 150 V DC 150 V AC Maximum voltage: 300 V DC 300 V AC Rated current: 180 mA DC 180 mA AC Maximum current: 250 mA DC 250 mA AC Input power: 20 W / 45 VA Insulation voltage: 5.4 kV AC Overvoltage category: CAT IV / 300 V AC Fuse FU1: FSK001 / 1 A-T Accumulator Type, rated voltage, capacity: lead-acid, gel type, 12 V, 1.2 Ah to 24 Ah Fuse FU2: FSK001 /

  • Mega MEg101.4, Uninterruptible power supply Supply MEg101.4 5 Design data Length × width × height: 108 × 90 × 63 mm Weight: 0.4 kg Installation: DIN rail TS 35 Terminal block, max. wire cross-section: 4 mm 2 Operating conditions Rated operating temperature: 22 °C Operating temperature range: -20 °C to +55 °C Operation: interior, with cover panel of terminals outdoor, in waterproof case Protection rating: IP00 Relative humidity: 20 % to 90 % Altitude: up to 2 000 m Operating position: vertical with ventilation openings on upper side, installation on DIN rail Safety: EN 61010-1:2010 EMC: EN 6132

  • Mega MEg101.4, Měřící Energetické Aparáty 6 3/ EXPLANATION OF SYMBOLS IN USER MANUAL FOR POWER SUPPLY MEg101.4 Danger, electric shock risk Note in documentation / Danger, risk of danger Ground, grounding terminal for RF grounding IP kód Degree of protection provided by enclosure e product is intended for recycling and collection spots Declaration of Conformity – European Community 4/ CONSTRUCTION e uninterruptible power Supply MEg101.4 is built in a plastic case made of self-extin- guishing polycarbonate. e power supply is installed on the DIN rail TS

  • Mega MEg101.4, Uninterruptible power supply Supply MEg101.4 7 Tab. 1: Power supply MEg101.4 terminals Terminal number Terminal denotation Terminal description 1 OUTPUT STOP Uninterruptible output voltage blocking 2 OUTPUT GND Output ground of power supply MEg101.4 3 OUTPUT +12 V Uninterruptible output voltage +12 V DC 14 POWER L POWER + AC phase conductor or DC supply voltage positive pole 16 POWER N POWER – AC neutral conductor or DC supply voltage negative pole 18 POWER RF grounding 35 AKU + Positive pole of the 12 V lead-acid accumulator 36 AKU – Negative pole of the 12 V lead-acid

  • Mega MEg101.4, Měřící Energetické Aparáty 8 Obr. 2: MEg101.4 rating label example MEg101.4 Made in Czech Republic Supply P ower: U =230V , (150-300) V , f =50Hz n O utput: U = 12V , (10-14)V n max U =220V , (150-300) V n I =180mA , I =250mA n max I =1,5 A (term.2-3 and 36-35) total I =0,2 A (term.36-35) n 5/ SAFETY INFORMATION Maximum attention must be paid to this information Warn

  • Uninterruptible power supply Supply MEg101.4 9 6/ INSTALLATION AND PUTTING IN OPERATION If the uninterruptible power supply MEg101.4 is used in ways other than origi- nally intended, the protection provided by the power supply may be impaired. e uninterruptible power supply MEg101.4 is a Class A product designed for industrial environments. It may cause rad

  • Mega MEg101.4, Měřící Energetické Aparáty 10 Fig. 3: Example of installation source unit in vertical position to box with DIN rail e power supply terminal (18) for RF grounding must be connected to the grounding system in the power supply installation site. Based on the type of power supply, AC or DC supply voltage is brought to terminals (14) and (16). e power supply MEg101.4 can be fed by AC voltage ranging from 150 V AC to 300 V AC . e power supply MEg101.4 can be fed by DC voltage ranging from 150 V DC to 300 V DC . When the uninterruptible power supply MEg101.4 is used for feeding external devices, the uninterrupt

  • Mega MEg101.4, Uninterruptible power supply Supply MEg101.4 11 uninterruptible power supply. e termination of uninterruptible power supply is indica- ted by the LED indicator RUN turned o. Renewal of the uninterruptible power supply is started up also by short-term renewal of the input supply voltage. Fig. 4: Power supply MEg101.4 wiring Poz. Skl. číslo Popis Ks Poznámka Měř.: Datum: Konstrukce: Schválil: Datum posl. revize: Číslo výkresu: Skl. číslo: Název: MEgA - Měřící Energetické Aparáty, a.s. 1 1:1 Kreslil: List: Zdeněk Kružík Lead-acid Accu 12V, max.24Ah DC +12V +/L -/N 150V to 300

  • Mega MEg101.4, Měřící Energetické Aparáty 12 7/ MAINTENANCE REQUIREMENTS e repairs of the power supply MEg101.4 during the warranty period may only be carried out by the manufacturer's skilled and trained personnel or by the manu- facturer's service organizations. e contact to the manufacturer's service is indica- ted on the website www.e-mega.cz. e power supply MEg101.4 unit may not be exposed to chemicals. e power supply MEg101.4 may be transported in its original container only. e power supply MEg101.4 has no requirements for forced cooling. When polluted, the power supply unit is carefully cleaned with a da

  • Mega MEg101.4, Uninterruptible power supply Supply MEg101.4 13 Tab. 2: Informative periods of uninterruptible power supply without connected external accumulator with voltage drop to 10 V P [W] 10 15 t [sec] 8 4 8/ DISPOSAL When the power supply MEg101.4 service life is over, have the unit recycled in waste disposal sites according to rules for electronic waste disposal. e power supply set may include the accumulator as well. 9/ CONTENTS OF THE SET Basic set – Uninterruptible power supply MEg101.4 – 1 pc fuse FU1 type FSK 001 / 1 A-T – 1 pc fuse FU2 type FSK 001 / 2,5 A-T – 1 pc fuse FU3 type FSK 001 / 0,16 A-T – CD with user description Optional parts of the set – DIN rail TS 35 wi

  • Měřící Energetické Aparáty 14 10/ WARRANTY It is not permitted to open the power supply MEg101.4 during warranty period. e power supply MEg101.4 design is covered by a 24-month warranty from the date of purchase, however, 30 months after removal from the manufacturer storage at longest. Defects originating during this period as a demonstrable result of defective design,

Related Products and Documents (UPS):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 MTX Road Thunder RT15-44 Specifications mtx/road-thunder-rt15-44-9RW.pdf 14 Oct 2022 4
2 Kenwood KDC-355U Instruction manual kenwood/kdc-355u-41U.pdf 18 Sep 2023 44
3 RM NB320 Operation & user’s manual rm/nb320-73C.pdf 16 Oct 2022 268
4 Yuxin YWH100 Operation & user’s manual yuxin/ywh100-13M.pdf 27 Nov 2023 43
5 SEVERIN KA 4752 Dimensions severin/ka-4752-FWU.pdf 23 Sep 2022 1 0.78 Mb
6 Hussmann M4X-GEP Technical data sheet hussmann/m4x-gep-3YB.pdf 13 Feb 2024 8

Similar Resources:

  • Riello

    5KVA

    (164 pages)
    Uninterruptible Power Supply ON LINE MULTISTANDARD 5000 VA – 6000 VA MM 6500 VA – 8000 VA – 10000 VA MM/TM Manuale d’installazione ed uso Installation and use manual Installations und Bedienungsanleitung Manuel d’installation et d’utilisation Manual de instalación y uso Riello Power Dialog UPS available from EcoPowerSuppliesFor more …
  • Riello UPS

    MASTER HP-UL Series

    (83 pages)
    Pag. 1 a 83 0MLMHTK65RUENUB UUNNIINNTTEERRRRUUPPTTIIBBLLEE PPOOWWEERR SSUUPPPPLLYY 65 to 125 kVA Three-Phase Output USER MANUAL MASTER HP-UL …
  • socomec

    ITYS

    (40 pages)
    ITYS1-10 kVA安装及操作手册 CNInstallations- und bedienungsanleitung DEManual de instalación y uso ES Manuel d’installation et d’utilisation FR Installation and operating manual GB Manuale di installazione e uso IT Installatie– en bedieningshandleiding NLDokumentacja Techniczno-Ruchowa PLManual de instalação e funcionamento PTManual de instala …
  • IBM

    1000 VA LCD

    (20 pages)
    IBM United States Hardware Announcement110-210, dated September 28, 2010IBM United States Hardware Announcement 110-210 IBM is a registered trademark of International Business Machines Corporation1IBM 1000VA and 1500VA LCD Tower UPS optionsavailable for IBM System x serversTable of contents1 Overview 5 Publications 2 Key prerequisites 6 Technical informati …
  • Energenie

    EG-AVR-0501

    (10 pages)
    USER MANUALHANDBUCHHANDLEIDINGMANUEL DESCRIPTIFРУКОВОДСТВО ПОЛЬЗОВАТЕЛЯКЕРІВНИЦТВО КОРИСТУВАЧАEG-AVR-0501 AUTOMATIC ACVOLTAGE REGULATOR ANDSTABILIZER, LED, 220 V AC, 500 VA …
  • Integra

    OPTIMA RT9 6KVA

    (42 pages)
    ENGLISH OPTIMA RT9 6KVA / 10KVA USER MANUAL DOUBLE CONVERSION UPS RACK / TOWER UPS  Technical information on this manual is property of INTEGRA . This manual Information cannot be copied or distributed totally or partially without written approval of INTEGRA.  INTEGRA can introduce modifications in their p …

Comments, Questions and Opinions: