  • Eaton Powerware 9130, Specifications Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 69 Rear Panels This section shows each model's rear panel. Receptacles in Load Segment 1 are shaded. Table 13 on page 53 lists the rackmount models. Table 14 on page 54 lists the tower models. Input and output components for each model are listed in Table 18 through Table 24 (pages 57 through 61). For a description of communication features, see Figure 18 on page 38. RS-232 Port REPO Port Relay Port USB Port Communication Bay (6) 5-15R Output Receptables 5

  • Eaton Powerware 9130, Specifications Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 54 PW9130L3000R-XL2US 3000 VA / 2700W Figure 39 on page 72 PW9130G1000R-XL2U 1000 VA / 900W Figure 29 on page 69 PW9130G2000R-XL2U 2000 VA / 1800W Figure 36 on page 71 PW9130G2500R-XL2U 2500 VA / 2250W Figure 40 on page 73 PW9130G3000R-XL2U 3000 VA / 2700W Figure 40 on page 73 PW9130i1000R-XL2U 1000 VA / 900W Figure 30 on page 69 PW9130i1000R-XL2US 1000 VA / 900W Figure 30 on page 69 PW9130i1500R-XL2U 1500 VA / 1350W Figure 34 on page 71 PW9130i1500R-XL2US 1500 VA / 1350W Figure 34 on page 71 PW9130i2000R-XL2U 2000 VA / 1800W F

  • L5-30P Input Cord RS-232 Port USB Port Communication Bay REPO Port Relay Port (4) 5-20T Output Receptables (1) L5-20R Output Receptable EBM Connection (2) 20A AC Breakers Specifications Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 76 Figure 47. Model PW9130L3000T-XL RS-232 Port USB Port Communication Bay REPO Port Relay Port IEC C14-10A Input Con

  • Operation Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 37 To pass the battery test, the battery voltage must remain above the threshold value during discharge. Configuring Automatic Restart The UPS automatically restarts if utility returns after the output was shut off due to exhausted batteries, a shutdown input signal, or

  • Eaton Powerware 9130, Installation Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 18 3. If you are installing EBMs, see the following section, “Connecting the EBM(s),” before continuing with the UPS installation. 4. Replace the UPS right front cover. To replace the cover, verify that the ribbon cable is p rotected and (if EBMs are installed) the EBM cable is routed through the knockout on the bottom of the cover. Slide the cover to the left until it aligns with the left front cover. Reinstall the two screws on the right side of the right front cover. 5. If you are installing power management software, connect your computer to one of the

  • Eaton Powerware 9130, Installation Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 20 6. Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for each cable. sledoM AV 0003–0002sledoM AV 0051 ot pU Figure 13. Typical EBM Installation 7. Replace the EBM front cover. To replace the cover, verify that the EBM cables are ro uted through the EBM cover knockouts, then slide the cover from the left to the right until it connects with the cover hook near the left side of the EBM cabinet. Reinstall the two screws on the right side of the front cover. For reference, see Figure 12 on page 19. Repeat fo

  • Eaton Powerware 9130, Troubleshooting Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 85 Silencing the Alarm Press any button on the front panel display to silence the alarm. Check the alarm condition and perform the applicable action to resolve the condition. If the alarm status changes, the alarm beeps again, overriding the previous alarm silencing. Service and Support If you have any questions or problems with the UPS, call your Local Distributor or the Help Desk at one of the following telephone numbers and ask for a UPS technica

  • Installation Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 17 ! IMPORTANT A ribbon cable connects the LCD control panel to the UPS. Do not pull on the cable or disconnect it. NOTE Leave ribbon cable connected. Figure 9. Removing the UPS Right Front Cover CAUTION A small amount of arcing may occur when connecting the internal batteries.

  • Eaton Powerware 9130, Communication Bay USB Port RS-232 Port REPO Port Relay Port IEC C14-10A Input Connector (6) IEC 320-10A Output Receptables Specifications Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 78 Figure 51. Model PW9130i700T RS-232 Port USB Port Communication Bay REPO Port Relay Port IEC C14-10A Input Connector (6) IEC 320-10A Output Receptables EBM C onnection Figure 52. Model PW9130i1500T-XL

  • Eaton Powerware 9130, Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 44 Chapter 6 Maintenance This section explains how to: l Care for the UPS and batteries l Replace the UPS internal batteries and Extended Battery Modules (EBMs) l Test new batteries l Recycle used batteries or UPS l Update the UPS firmware UPS and Battery Care For the best preventive maintenance, keep the area around the UPS clean and dust-free. If the atmosphere is very dusty, clean the outside of the system with a vacuum cleaner. For full battery life, keep the UPS at an ambient tempera

  • Communication Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 41 See Figure 18 on page 38 for the REPO location. Figure 21 shows a schematic of the REPO connector contacts. – Polarity 2 + Polarity 1 REPO Figure 21. REPO Connector Contacts You can set the REPO polarity. See the “REPO Input Polarity” settin

  • Eaton Powerware 9130, Operation Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 36 Configuring Battery Settings Set the UPS for the number of EBMs installed, whether to run automatic battery tests, and automatic restart configuration. Configuring the UPS for EBMs To ensure maximum battery runtime, configure the UPS for the correct number of EBMs (see Table 4): 1. Press any button on the front panel display to activate the menu options, then select SETTINGS, USER SETTINGS, and NUMBER OF BATTERY STRINGS. 2. Use the or buttons to select the number of battery strings according to your UPS configuration: Table 4. Configuring the UPS for EBMs A

  • Eaton Powerware 9130, Safety Warnings Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 8 ATTENZIONE l Le batterie possono comportare un rischio di scossa elettrica o di ustione in seguito a un'elevata corrente di corto circuito. Osservare le dovute precauzioni. L'assistenza deve essere eseguita da personale qualificato esperto di batterie e delle necessarie precauzioni. Tenere il personale non autorizzato lontano dalle batterie. l Le batterie devono essere smaltite in modo corretto. Per i requisiti di smaltimento fare riferimento alle disposizioni locali. l Non gettare mai le batt

  • Eaton Powerware 9130, NOTE Leave ribbon cable connected. Maintenance Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 48 Figure 25. Removing the UPS Front Cover 2. Remove and retain the two screws holding the internal battery connector. Disconnect the internal battery connector. See Figure 26. Battery Cover Plate Internal Battery Connector Battery Tray Handle Figure 26. Replacing the UPS Internal Batteries 3. Remove and retain the two screws holding the battery cover plate. Grasp an edge of the battery cover plate and pull it forward gently. Remove and retain the battery cover plate. 4. Carefully pull the handle on the battery tray and slid

  • Eaton Powerware 9130, NOTE Verify that the replacement batteries have the same rating as the batteries being replaced Maintenance Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 49 5. Slide the new battery package into the cabinet. Push the battery package in firmly. 6. Replace the battery cover plate into the slots at left, threading the battery connector through the access slot. Reinstall the retained screws. CAUTION A small amount of arcing may occur when connecting the internal batteries. This is normal and will not harm personnel. Connect the cables quickly and firmly. 7. Reconnect the internal battery connector. Connect red to red, and black to black. P

  • Eaton Powerware 9130, NOTE Leave ribbon cable connected. Maintenance Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 46 Figure 23. Removing the UPS Right Front Cover 2. Disconnect the internal battery connector (see Figure 24). 3. Up to 1500 VA models only. If the EBM cable is not connected to an EBM, unclip the EBM cable and move it to the left out of the way (see Figure 24). sledoM AV 0003–0002sledoM AV 0051 ot pU Internal Battery yrettaB lanretnIrotcennoC Connector E

  • Eaton Powerware 9130, Specifications Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 59 PW9130G1000R-XL2UEU IEC C14-10A L6-20P to C14 coupler PW9130G2000R-XL2UEU IEC C14-10A L6-20P to C14 coupler PW9130G2500R-XL2UEU IEC C20-16A L6-20P to C20 coupler PW9130G3000R-XL2UEU IEC C20-16A L6-20P to C20 coupler PW9130G1000R-XL2UAU IEC C14-10A Aust. 10A to IEC 320-10A PW9130G1500R-XL2UAU IEC C14-10A Aust. 10A to IEC 320-10A PW9130G2000R-XL2UAU IEC C14-10A Aust. 10A to IEC 320-10A PW9130G3000R-XL2UAU IEC C20-16A Aust. 15A to IEC 320-16A Table 21. Electrical Input Connections (Tower Models) Model In

  • Eaton Powerware 9130, Operation Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 29 Overload Alarm Level [10%] [20%] [30%]...[100%] These values affect alarm level only, not UPS operation such as transfers or shutdown. 100% Generates the Output Overload alarm at the set level. Transfer to Bypass When Overload* [Immediate] [After Delay] If Immediate, transfer occurs at load >102%. If After Delay, transfer occurs according to Table 22 on page 59. Immediate Power Strategy [Normal] [High Efficiency] See “Setting Power Strategy”on page 33. Normal Automatic Sta

  • Eaton Powerware 9130, Bottom EBM Cable Knockout (underneath cover) Top EBM Cable Knockout EBM Cover Hook Installation Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 19 Figure 12. Removing the EBM Front Cover 3. For the bottom (or only) EBM, remove the EBM cable knockout on the top of the EBM front cover. See Figure 12 for the location of the top EBM cable knockout. 4. If you are installing more than one EBM, for each add itional EBM remove the EBM cable knockout on the top and bottom of the EBM front cover. See Figure 12 for the location of the EBM

  • Eaton Powerware 9130, Specifications Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 68 500/350 72 225 449 590 766 PW9130G2000T-XL / PW9130G2000T-XLEU / PW9130i2000T-XL (Estimated runtimes) 2000/1400 15 61 111 156 186 1500/1050 21 81 145 184 248 1000/700 34 129 198 293 431 500/350 72 225 449 590 840 PW9130L3000T-XL 3000/2100 9 35 66 95 132 2250/1575 13 53 100 139 183 1500/1050 22 86 153 221 267 750/525 69 168 298 395 545 PW9130G3000T-XL / PW9130G3000T-XLEU / PW9130i3000T-XL (Estimated runtimes) 3000/2100 9 36 68 101 137 2250/1575 12 49 90 134 165 1500/1050 20 79 143 180 240 750/525 46 161 267 434 547 NOTE

  • Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 12 Chapter 3 Installation This section explains: l Equipment inspection l Unpacking the cabinet l Checking the accessory kit l Cabinet installation (rackmount and tower) l Wiring installation l Initial startup Inspecting the Equipment If any equipment has been damaged during shipment, keep

  • Eaton Powerware 9130, Specifications Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 66 750/525 13 55 103 151 223 500/350 22 82 186 250 312 250/175 47 190 328 431 584 PW9130L1500R-XL2U / PW9130L1500R-XL2US 1500/1050 7 34 63 88 135 1125/788 11 44 84 129 210 750/525 18 79 148 207 267 375/263 38 167 278 475 540 PW9130i1500R-XL2U / PW9130i1500R-XL2US 1500/1050 7 32 61 98 128 1125/788 11 47 83 126 195 750/525 18 81 143 208 262 375/263 38 171 298 416 564 PW9130L2000R-XL2U / PW91

  • Eaton Powerware 9130, Communication Bay USB Port RS-232 Port REPO Port Relay Port 5-15P Input Cord (6) 5-15R Output Receptables Specifications Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 74 Figure 43. Model PW9130L700T-XL Communication Bay USB Port RS-232 Port 5-15P Input Cord REPO Port Relay Port (6) 5-15R Output Receptables EBM Connection Figure 44. Model PW9130L1500T-XL

  • Eaton Powerware 9130, Specifications Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 60 Nominal Outputs Low Voltage Models: 100/110/120/127V (voltage configurable or auto-sensing) 1000/1500/2000/3000 VA 0.9/1.35/1.8/ 2.7 kW High Voltage Models: 200/208/220/230/240V (voltage configurable or auto-sensing) 1000/1500/2000/3000 VA 0.9/1.35/1.8/ 2.7 kW Frequency 50 or 60 Hz, autosensing or configurable as a frequency converter Output Overload (Normal Mode) 100–102%: Activates Overload alarm. (Level 1) 102–129%: Load transfers to Bypass mode after 12 seconds. (Level 2

  • M6 16 Pan-Head Screws (6 places) Front of Rack M6 Cage Nuts (6 places) Tighten adjustment screws after rail attachment (3 places each rail). Position 4 Position 1 Installation Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 15 Figure 5. Securing the Rails 5. Repeat Steps 3 and 4 for the other rail assembly. 6. Tighten the th

  • Eaton Powerware 9130, Safety Warnings Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 9 ПРЕДУПРЕЖДЕНИЕ l В данном ИБП установлены собственные источники энергии (батареи). В ИБП может иметься напряжение даже в том случае, если он не подключен к сети переменного тока. l Для снижения опасности пожара или поражения электрическим током устанавливайте ИБП в закрытом помещении с контролируемыми температурой �

  • Eaton Powerware 9130, RS-232 Port USB Port Communication Bay REPO Port Relay Port IEC C14-10A Input Connector (4) 6-20R Output Receptables (1) L6-20 Output Receptable EBM Connection Specifications Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 77 Figure 49. Model PW9130G2000T-XL RS-232 Port USB Port Communication Bay REPO Port Relay Port IEC C20-16A Input Connector (1) L6-20 Output Receptable (1) L6-30 Output Receptable (2) 6-20R Output Receptables EBM Connection Figure 50. Model PW9130G3000T-XL

  • Eaton Powerware 9130, Maintenance Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 52 Testing New Batteries To test new batteries: 1. Plug the UPS into a power outlet for 48 hours to charge the batteries. 2. Press any button to activate the menu options. 3. Select CONTROL then START BATTERY TEST. The UPS starts a battery test if the batteries are fully charged, the UPS is in Normal mode with no active alarms, and the bypass voltage is acceptable. During the battery test, the UPS transfers to Battery mode and discharges the batteries for 25 seconds. The front panel displays “Battery test running” and th

  • Eaton Powerware 9130, Operation Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 31 Operating Modes The Eaton 9130 front panel indicates the UPS status through the UPS indicators (see Figure 17 on page 26). Normal Mode During Normal mode, the indicator illuminates solid and the UPS is powered from the utility. The UPS monitors and charges the batteries as needed and provides filtered power protection to your equipment. The UPS may at times silently implement a High Alert mode, usually when incoming util

Related Products and Documents (UPS):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 Toshiba PDVR-16100 Operation & user’s manual toshiba/pdvr-16100-ZAS.pdf 28 Feb 2023 83
2 Optoma EX330 Operation & user’s manual optoma/ex330-YX7.pdf 08 Dec 2023 50
3 Tvone 1T-FC-326 Instruction manual tvone/1t-fc-326-E4H.pdf 09 Sep 2023 9
4 Sanyo N-600AAK Specifications sanyo/n-600aak-4GX.pdf 14 Feb 2024 1 0.16 Mb
5 Oppo HA-2 Operation & user’s manual oppo/ha-2-FJ1.pdf 13 Feb 2023 18
6 Led Control LVP603S Operation & user’s manual led-control/lvp603s-R3I.pdf 04 Feb 2023 23

Similar Resources:

  • Tripp Lite

    SmartPro SMART750RM1U

    (5 pages)
    Tripp Lite1111 West 35th StreetChicago, IL 60609 USATelephone: +(773) 869 1234E-mail: [email protected] #: SMART750RM1USmartPro .75kVA Line Interactive Sine Wave UPS, SNMPWEBCARD option, 1U Rackmount, USB, Serial, EPO,120V Highlights750VA / 600W line interactive 1U rackmount UPS; Sine wave output 120V nominal output during brownouts to 83V and ov …
  • Tripp Lite

    BP12V81

    (32 pages)
    1IMPORTANT SAFETY INSTRUCTIONS• Use caution when lifting Battery Pack. Because of the Battery Pack’s considerable weight, atleast two people should assist in lifting and installing it. If rackmounting the Battery Pack, mountit in the lowest rack space possible.• Suggested mounting procedures are for common rack types and may not be appropriate for allr …
  • Faller

    191767/1

    (8 pages)
    Sa. Nr. 191 767 2SÄGEMÜHLESAWMILL MOULIN DE SCIERIE ZAAGMOLENArt. Nr. 191767/1Machen Sie sich bitte vor Beginn des Bastelns mit dem Bausatzinhalt und der Anleitung vertraut und prüfen Sie die Vollständigkeit. Im Reklamationsfall gilt die gesetzliche Gewährleistungspflicht. Sollte ein Teil fehlen, übersenden Sie bitte den Teilewunsch und den Kaufbeleg …
  • Para systems

    E750RT2U

    (16 pages)
    User's ManualEnterprise Plus LCDRT UPS SeriesPara Systems, Inc.1455 Lemay Dr.Carrollton, TX 75007Phone: 1-972-446-7363Fax: 1-972-446-9011Internet: minutemanups.comUPS Sizing: sizemyups.comPN - 34000434 R3 …
  • Dell

    UPS 2700R Series

    (112 pages)
    Dellt Online RackExternal Battery Modulefor use with 2700W UPS modelsGetting Started WithYour SystemDémarrer Avec Votre SystèmeErste Schritte Mit Ihrem SystemНачало работы c вашей системойInicio de su sistema系统使用 入门指南系統使用 入門指南사용자의 시스템 시작하기はじめに システムについてK80 …
  • HP

    4430

    (13 pages)
    One Blue Hill Plaza, 16th Floor, PO Box 1546 Pearl River, NY 10965 1-800-PC-AMERICA, 1-800-722-6374 (Voice) 845-920-0800 (Fax) 845-920-0880 HP 4430 2D Imaging Barcode Scanner This document contains barcodes for resetting the HP USB Barcode Scanner to factory defaults and for simulating a carriage return (pressing the Enter key). You can als …

Comments, Questions and Opinions: