  • Toshiba 4200 FA CT, TOSHIBA IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during the installation, maintenance, and operation of the UPS and its batteries to assure safe and proper operation 1. Turn off, lockout, and tagout all power sources before connecting the power wiring to the equipment or when performing maintenance. 2. Hardwire type UPS units are not equipped with an over-current protection device, nor do they have an output disconnect for the ac output. Therefore, a user-installed c

  • Toshiba 4200 FA CT, TOSHIBA 6.16 Maintenance Bypass Procedure To safely set the unit in Maintenance Bypass, the UPS is first electrically switched to bypass mode, and then mechanically switched to bypass mode. This prevents the UPS from being placed in parallel with commercial power. Follow the instructions below when switching the UPS to and from Maintenance Bypass Mode. WARNING Failure to adhere to the following instructions could result in damage to your equipment and/or you risk removal of power to any equipment attached to the UPS. 6.16.1 Switch from UPS to Maintenance Bypass 1) Turn t

  • Toshiba 4200 FA CT, TOSHIBA The following precautions should be observed when working with batteries. 1) Verify that the “UPS” is off and that the Input Circuit Breaker is in the off position. 2) Remove watches, rings, jewelry, or other metal objects. 3) Use tools with insulated handles to prevent accidental shorts. 4) Wear rubber gloves and boots. 5) Do not lay tools or metal parts on top of batteries. 6) Determine if the battery is grounded. If grounded, remove source of the ground. Contact with any part of a grounded battery can result in an electrical shock. Electrical shock will be

  • Toshiba 4200 FA CT, TOSHIBA 6.19 Menu Data Screens 6.19.1 Settings for Calendar and Clock Press the MENU key to access the menu data screens and press the 'down' arrow key to scroll to the present date and time adjustment screen: CALENDER / CLOCK DATE (DAY) TIME >*F1: DATA SET MODE >Δ/∇ PRV/NEXT SCREEN Press the F1 key to display the following active adjustment screen: CALENDER / CLOCK DATE (DAY) TIME > Δ/∇ : UP/DOWN >ENTER:NEXT DATA Press the "up/down" arrows

  • Toshiba 4200 FA CT, TOSHIBA 1.0 Product Description 1.1 Theory of Operation An Uninterruptible Power Supply (UPS) is a system that is installed between the commercial power and the critical load. The UPS provides steady AC output power during commercial power fluctuations and interruptions. During “Normal Operation” the UPS utilizes commercial AC power and removes high voltage spikes and transients caused by switching and faults on the utility. The result of this process is maximum power conditioning and regulation. If the AC power supplied to the UPS drops below a specified voltage level, the unit's batteries automatically begin supplying power instead of receiving it. This in

  • Toshiba 4200 FA CT, TOSHIBA 4.3.2 Power Connection Cable Routing and Conduit Placement 50 kVA The following illustrates the proper cable routing that should be followed during the power connection process for the 50kVA. Bottom Conduit Entry Removable cover for conduit access 22 4200FA CT/XT User’s Manual

  • TOSHIBA 6.2 Bypass Mode If the UPS unit is severely overloaded or develops an internal fault, power flow is automatically switched from the main circuit to the Bypass circuit. Power flow through the bypass is shown in the following illustration. This changeover occurs automatically in less than 4 milliseconds in phase (Make-Before-Break). If the power flow is transferre

  • TOSHIBA DANGER Turn off and lock out all power sources. Wait at least five (5) minutes for powe r to dissipate then check voltage before servicing. Capacitors stay charged after power has been shut off. Accidental contact with live parts can cause personal injury and death. RISK OF ELECTRIC SHOCK 39561 DANGER Hazardous voltages are used in the operation o

  • Toshiba 4200 FA CT, TOSHIBA The maximum ambient temperature in which the Uninterruptible Power System (UPS) should be operated is 104 °F (40 °C) without batteries, and 89 °F (32 °C) if the battery cabinet is subject to the same ambient temperature as the UPS. The nominal battery voltage for all internal battery models is 288 VDC. The nominal battery voltage for all external battery models is 288 VDC. An Authorized TOSHIBA Representative who is knowledgeable of batteries and the required precautions should perform service on the batteries. Keep unauthorized perso

  • Toshiba 4200 FA CT, TOSHIBA 5.4 4200FA 30 kVA w/Internal Transformer Model Number T42#3*300#AMXN Input # =(B: 208; H: 220; C: 240; N: 380–415 Δ-wye; P: 380–415 wye; D: 480; M: 600) VAC Output *=(F: 208; H: 220 wye; J: 240; P: 380–415 wye; K: 480 wye: M:600) VAC Rated Output Capacity 30 kVA External Dimensions W x D x H (cm) 20.0” x 36.3” x 59.7” (50.8 cm x 92.2 cm x 151.6 cm) Rated Voltage 208; 220; 240; 380; 400; 415; 480; 600 VAC (Determined by Input Transformer internal to the unit) Voltage Variation +10% to -30%; (-15% to -30%****) Rated Frequency 50/6

  • Toshiba 4200 FA CT, TOSHIBA When the battery test is completed, the previous operation will be resumed and the main system MONI screen will be displayed. If the battery test detects a low DC battery voltage, then the message screen will display: - UPS ON-LINE - OUTPUT VOLTAGE=208 V CURRENT=38/55/48% * LOW BATTERY * If the battery test passes then the following screen message will be displayed: - UPS ON-LINE - OUTPUT VOLTAGE=208 V CURRENT=38/55/48% DATE (DAY) TIME If the inverter is not operating when the BATT TEST key is press then the function

  • Toshiba 4200 FA CT, TOSHIBA IMPORTANT NOTICE The Instructions contained in this manual are not intended to cover all of the details or variations in equipment or to provide for every possible contingency to be met in connection with installation, operation, or maintenance. Should further information be required or should particular problems arise which are not covered sufficiently the matter should be referred to the local TOSHIBA sales office. The contents of this instruction manual shall not become a part of or modify any prior or exi

  • Toshiba 4200 FA CT, TOSHIBA DISPLAY DURATION SET <3 MIN> 30 MIN >Δ/∇: CHANGE DATA >ENTER:ACCEPT CHANGE Press the 'up' or 'down' arrow key to move the marker between the two available idle mode times. Press the ENTER key to save the change or press the MENU key to exit to the main menu and discard the change. Note: If any of the following conditions occur, the LCD-Idle Mode will be inhibited and the LCD will remain on continuously: 1) The UPS has rece

  • Toshiba 4200 FA CT, TOSHIBA 5.3 4200FA 30 kVA @ 208 VAC Input/ 208 VAC Output w/Internal Batteries Model Number T42F3F300XAMBN T42F3F300##MBN Rated Output Capacity 30 kVA External Dimensions W x D x H (cm) 20.0” x 36.3” x 59.7” (50.8 cm x 92.2 cm x 151.6 cm) Rated Voltage 208 VAC Voltage Variation +10% to -30%; (-15% to -30% ****) Rated Frequency 50 / 60 Hz Input Cables required 3 phase ; 4 Wire + GND Dual Input Option Cables required 3 phase ; 4 Wire + GND * Power Factor Greater than 0.98 when in inverter mode Required Input kVA 28.0 kVA Walk-in Function From 20% to 100% over 5 seconds Inrush Current L

  • Toshiba 4200 FA CT, TOSHIBA 4.5 Communication Interface 4.5.1 Remote Contact This interface is a standard feature and is available as dry switch contacts through a DB9 male connector located on the front of the UPS. The following schematic shows the contact state and pin assignment for each signal and the associated DB9 connector pin- out. 5 System Common 6 Bypass Active Fault Signal Detect 1 2 8 UPS On-line 7 Battery Voltage Low Battery Discharge 9 4 DB9 Male Connector Outline (facing conn

  • TOSHIBA 4.2 Control Circuit and External Battery Interface Connections 15/25/30 kVA The following illustrates the wiring connections of the Control Circuits, and Battery Interface Circuits. Battery Connection (+) Positive (3) Battery Shunt Trip (4) Battery Shunt Trip (5) Battery Aux. (1) Low Battery (2)

  • Toshiba 4200 FA CT, TOSHIBA 6.19.8 Reset to Default Settings Press the MENU key to access the menu data screens and press the 'down' arrow key to scroll to the original factory 'default settings' adjustment screen display: MENU DATA RESET DATA INITIALIZATION >F1: TO ACCESS RESET >Δ/∇:PRV/NEXT SCREEN Press the F1 key to display the following active adjustment screen: MENU DATA RESET DATA INITIALIZATION > MENU: NO DATA RESET >ENTER: ACCEPT CHANGE When the ENTER key is pressed the following factory defaults are reset: 1) Resets the voltage

  • TOSHIBA 9.3 Shipping Dimensions and Weights All 15, 25 & 30 kVA models Shipping Dimensions, Standard Inches (cm) Shipping Dimensions, with crate Inches (cm) Width 42.8 (109) 43.5 (111) Depth 49.0 (125) 49.8 (127) Height 64.6 (164) 69.6 (177) Height with packing material 67.6 (172) 69.6 (177) All 50 kVA models Shipping Di

  • Toshiba 4200 FA CT, TOSHIBA 4.5.2 RS-232C The RS-232C serial communication interface is available through a DB9 female connector located on the inside of the UPS. This interface allows control of the UPS from a computer network running TOSHIBA RemotEyeII™ software. The computer and the UPS are connected through a serial RS-232C communication port. The available data from the UPS, via the RS-232C communication link, is shown below: Input Voltage Output Voltage Input Frequency Output Frequency Battery Voltage Output Current Operating C

  • Toshiba 4200 FA CT, TOSHIBA 4.4 Control Circuit and External Interface Connections 50 kVA The following illustrates the wiring connections of the Control Circuits, and Battery Interface Circuits for the 50kVA. (3) Battery Shunt Trip (4) Battery Shunt Trip (5) Battery Aux. ( 6 ) Batter y Aux. (1) Low Battery (2) Battery Discharge (3) Fault (4) Not Used (5) Inverter Supply (6) Inverter Supply (7) P24A3 (8) Remote Run (9) P24A3 (10) Remote Stop (11) Bypass (12) COMMON (13) EPO (14) EPO (15) – (18) Not Used 4.4.1 Recommended Wire Size and Torqu

  • Toshiba 4200 FA CT, TOSHIBA 4.1.3 Recommended Wire Size and Torque Requirements Minimum Wire Size and Torque Requirements UPS Input and Output Terminals 15/25/30 kVA (USE MINIMUM 75 °C INSULATED COPPER WIRING) Phase: (A) (B) (C) Input: (H1) (H2) (H3) 15 kVA 25 kVA 30 kVA AWG* Torque AWG* Torque AWG* Torque 208 V 8 51 in-lbs. 4 51 in-lbs. 2 87 in-lbs. 220 V 8 51 in-lbs. 4 51 in-lbs. 2 87 in-lbs. 240 V 8 51 in-lbs. 4 51 in-lbs. 2 87 in-lbs. 380 V 10 35 in-lbs. 8 51 in-lbs. 6 51 in-lbs. 400 V 10 35 in-lbs. 8 51 in-lbs. 6 51 in-lbs. 415 V 10 35 in-lbs. 8 51 in-l

  • Toshiba 4200 FA CT, TOSHIBA 6.17 Keypad Overview The following illustrates the 12-key data entry pad with each key functionally labeled. MONI BATT F1 IN OUT BATT TEST BUZZ STOP MENU ENTER RESET MONI Monitor – Press to display system-monitoring screens. BATT Battery – Press to display UPS battery conditions. F1 Function – Press to change settings of various menus. IN Input – Press to display UPS input conditions. OUT Output – Press to display UPS output conditions. BATT TEST Battery Test – Press to execute On-Line Battery test. BUZZ STOP Buzzer Stop – Press to stop the audible alert buzzer. MENU Menu – Press to display the main use

  • Toshiba 4200 FA CT, TOSHIBA 6.18 Key Functions 6.18.1 MONI After the UPS has been successfully started, the system will be in the normal 'AC Input Mode' of operation. The LCD screen will automatically display the main MONI (monitor) function. If the MONI key is pressed at this time the screen output will not change. The MONI function automatically monitors the entire UPS system. The LCD screen will automatically switch "off" after a period of keypad inactivity and switch "on" if any key is pressed. It will switch "on" automatically dur

  • Toshiba 4200 FA CT, TOSHIBA 6.5 Battery Backup Time and Discharge Process The UPS system, when used in conjunction with a TOSHIBA designed Battery System, is designed to provide several minutes of back-up time (Refer to the Battery System Manual for back-up times). These times are valid when the unit is operating under full load. When these models are operating at half load, the batteries can provide approximately 2 times the specified value. The exact length of these times will depend on the UPS model used, condition of the batteries, amount and type of

  • TOSHIBA 5.2 4200FA 15/25 kVA w/Internal Transformer Model Number C42#3*150#AMXN C42#3*250#AMXN Input # =(B: 208; H: 220; C: 240; N: 380–415 Δ-wye; P: 380–415 wye; D: 480; M: 600) VAC Output *=(F: 208; H: 220 wye; J: 240; P: 380–415 wye; K: 480 wye: M:600) VAC Rated Output Capacity 15 kVA 25 kVA External Dimensions W x D x

Related Products and Documents (UPS):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 HTC HTC One S Operation & user’s manual htc/htc-one-s-CPO.pdf 16 Jun 2023 80
2 Yamaha mLAN Driver Owner's manual yamaha/mlan-driver-433.pdf 07 Aug 2023 43 0.9 Mb
3 Rosewill NEON M60 Operation & user’s manual rosewill/neon-m60-B32.pdf 07 Jan 2024 12
4 Enerzone Solution 1.6 AGENCY PHASE II CERTIFIED WOOD Operation & user’s manual enerzone/solution-16-agency-phase-ii-certified-wood-I11.pdf 24 Jul 2022 45
5 Sony SU-46HX1 Specifications sony/su-46hx1-H4O.pdf 07 Oct 2023 1 0.15 Mb
6 RCA AH765R Manual  rca/ah765r-E76.pdf 10 Jul 2023 1 0.1 Mb

Similar Resources:

  • Gamatronic

    Power+

    (111 pages)
    Har Hotzvim Industrial Park, 14 Hartom St., PO Box 45029, Jerusalem 91450, Israel Tel: +972-2-588-8222 Fax: +972-2-582-8875 Email: [email protected] Website: www.gamatronic.com 2MUM-PP/18 POWER+ MMOODDUULLAARR UUPPSS SSYYSSTTEEMM RRMM 5500 KKVVAA NNOORRTTHH AAMMEERRIICCAANN SSTTAANNDDAARRDD UUsseerr GGuuiiddee Release 1. …
  • Eaton

    Pulsar EX RT Series

    (2 pages)
    1EATON Product CatalogueEaton EX RT7/11 kVA single phase input / single phase output5/7/11 kVA three phase input / single phase outputDouble conversion (on-line)High performance UPS for single phase applications.Maximum availability• Hot swappable UPS and battery modules• Internal bypass and maintenance bypass included as standard• The UPS can …
  • Tripp Lite

    OmniSmart, SmartPro 120V Input/Output

    (15 pages)
    Owner’s Manual1111 W. 35th Street Chicago, IL 60609 USACustomer Support: (773) 869-1234 • www.tripplite.comImportant Safety Instructions2Quick Installation3Basic Operation4Storage & Service7Specifications8SMART750USB120V Input, Line-Interactive UPS SystemCopyright ©2007 Tripp Lite. All rights reserved. Español9Français19UL1778 …
  • Omron

    S8T-DCBU-01

    (20 pages)
    DC Backup Block for S8TS S8T-DCBU-01 L-39PowerSuppliesDC Backup Block for S8TSS8T-DCBU-01DC Backup Block for S8TS for Preventing 24 VDC Outages due to Instantaneous Power Failures• Supplies 24 VDC for a fixed period of time even during AC input outages to considerably improve system reliability.• Block Power Supply Basic Block is connected by the Bus Lin …
  • Cuppon

    SM1200

    (3 pages)
    WARRANTY CONDITIONS 1. 2 Year Warranty. The warranty period begins on the date of delivery of the product. 2. All parts of the product are under the warranty of our company. 3. In case the product fails with …
  • PowerWalker

    VI 650SE LCD

    (53 pages)
    Line Interactive UPS Quick Start Guid …

Comments, Questions and Opinions: