Text of Sanyo SANUPS E11A202U User Guide:

  • Sanyo SANUPS E11A202U, − 19 − 9. Operating Procedures 9.1 UPS Startup (Normal Operation) Check that the INPUT indicator has changed from blinking to lit, and then proceed to step ② . ・ The green LOADLEVEL 25 to 100% indicator and the red LOADLEVEL O.L indicator light according to the load connected to the UPS. ・ The green ECONOMY indicator lights when the UPS operating mode is Economy Mode. ・ The green DOUBLE CONVERSION indicator when the UPS operating

  • Sanyo SANUPS E11A202U, − 15 − 6.6 Mounting a Rack Mount Type UPS CAUTION ! ・ Be careful to avoid straining your lower back when moving and installing the UPS. ・ The UPS weighs about 29 kg (63.93 lbs). Always get at least one other person to help you install it. Bodily injury can result if the UPS falls. ・ The UPS can fall when it is moved or installed, resulting in bodily injury or damage to the UPS. Hold the bottom side of the UPS firmly with both hands when installing it. ・ For safety, use L-type rails (support rails) when mounting the UPS in a rack. (Contact the manufacturer of your rack for more inform

  • Sanyo SANUPS E11A202U, − 33 − Condition Countermeasure No recovery from utility power source failure. Utility power source failure occurs frequently. ・ Check whether MAIN MCCB on the back panel of the UPS is in the “ON” position. (If MAIN MCCB is set to the “OFF” position during normal operation, the same operation as for a utility power source failure will be triggered.) See §9.1 “UPS Startup (Normal Operation)”. ・ Verify that input voltage and input frequency are within the rated limits. See §15.3 “Specifications”. UPS is operated in the “Double Conversion” mode though set UPS in the Economy” mode. ・ UPS automa

  • − 23 − 10. User Settings 10.1 Setup Menu Item List You can configure the UPS by setting the menu items in the following list. Configure it according to your environment and requirements. The controls and indicators on the control panel are used to set items in the Setup menu. For details, see §10.2 “Setup Menu Operations”. Whenever you change a menu item setti

  • Sanyo SANUPS E11A202U, − 36 − 15. Functional Description 15.1 Basic Operation (1) Normal Operation In normal operation, the UPS switches automatically * between the three modes (a) to (c) depending on the state of the power. * The UPS does not switch automatically when item ① “UPS operation mode” in § 10.1 “Setup Menu Item List” is set to “Double Conversion”. However,The UPS switch automatically according to the state of the input power and the load condition when item ① "UPS operation mode" i

  • Sanyo SANUPS E11A202U, − 6 − 2. For Proper Operation 2.1 Input Power Requirements (1) Please use UPS as a commercial power supply in the region and the output voltage of UPS are matched referring to the table below. MODEL AC input voltage AC input frequency NOTE E11A202U001 120V (+15%,-20%) 50 or 60Hz ( ± 5%) ※ E11A202U001J 100,110,115,120V (+15%,-20%) 50 or 60Hz ( ± 5%) ※ ※ The frequency variation range is set to ± 3% when the UPS is shipped from the factory. If the frequency variation range of input power supply is ± 5%, select ± 5% as described in item ③ “Frequency sync ra

  • Sanyo SANUPS E11A202U, − 44 − LED blinking for setting up menu For the following two Menu Item, • “Restart time (battery charge rate)” in the E11A Instruction Manual §10.1 “Setup Menu Item List No. ⑦ ”. • “Low battery voltage signal timing” in the E11A Instruction Manual §10.1 “Setup Menu Item List No. ⑫ ”. when confirming two items using control panel of UPS, the positions of the LED blinking for setting up menu might be different from description in the E11A Instruction Manual. Refer to §10.2 “Setup Menu Operations” in the Instruction Manual of E

  • Sanyo SANUPS E11A202U, − 14 − 6.5 Attaching the Stand CAUTION ! ・ Unless the UPS is secured solidly in place, it can shift or fall during seismic events (earthquakes) or when it is subjected to shock or vibration, possibly causing bodily injury. ・ Be careful not to get your hands caught when installing the stand. Proceed as follows to attach the supplied stand. ① Prepare two supplied stand. ② Place the UPS in the stand. Always place with the left side of the UPS on the bottom, and the control panel on t

  • Sanyo SANUPS E11A202U, − 21 − 9.3 Outage Simulation Test You should perform a test of whether the UPS operates properly during a power outage. Proper operation is as described below. Note Perform this test before powering the connected load devices on. Note If your utility power breaker panel is too far away to access conveniently, you can also perform the test by setting MAIN MCCB to the “OFF” and “ON” positions. Because the UPS continues inverter operation, there is a small amount of voltage (u

  • Sanyo SANUPS E11A202U, − 27 − 11.4 Battery Maintenance CAUTION ! ・ Internal maintenance and inspection should be performed only by technically qualified personnel. Electric shock, injury, burning, smoke or file could otherwise result. ・ Batteries should be replaced periodically. Batteries used after their service life has passed may cause a fire. ・ Never use organic chemicals such as gasoline, thinner, benzene or detergent to clean batteries. These can cause the casing to crack and leak, resulting in fire or current leakage. (1) Battery backup time confirmation Refer to §11.5 “Battery Test”, and

  • Sanyo SANUPS E11A202U, − 42 − Appendix. Usage notes for SANUPS SOFTWARE STANDALONE When using supplied “SANUPS SOFTWARE STANDALONE”, please note the following instructions. “Charge” on the main screen of “SANUPS SOFTWARE STANDALONE” For the charge rate (as a %) of the battery displayed on the main screen of “SANUPS SOFTWARE STANDALONE”, please note the followings. Refer to §6.1 “Main Screen” in the User Guide of SANUPS SOFTWARE STANDALONE for details. 1. Proceed as follows to charge the batteries of the UPS for 12 hours or more at initial startup of the UPS. ( Use the internal batter

  • Sanyo SANUPS E11A202U, − 41 − (*5): The above table lists standard specifications. Some specifications are different for units with long backup times. For details, refer to the external battery specification instruction manual. (*6): When Input plug is NEMA 5-20P type (MODEL:E11A202U001), output voltage is 120V only. If you intend to use this UPS with the wide range voltage(100/110/115/120V), use this UPS with NEMA L5- 30P type input plug..(MODEL: E11A202U001J) (These are requirements of UL.) 16. Warranty Warranty for Use Overseas (North America) 3 Years 1. This product is warranted against electrical failure due defects in m

  • Sanyo SANUPS E11A202U, − 10 − 5.2 Control Panel and Indicators Functions No. Label Status display Lit Not lit Slow blink Fast blink LED0 INPUT Input power status Normal input - Input error - LED1 OUTPUT UPS output power status Inverter operation OFF Bypass operation - LED2 ECONOMY Operation mode Economy mode operation (*1) OFF (*3) - - LED3 DOUBLE CONVERSION Operation mode Double conversion mode operation (*2) OFF (*3) -

  • Sanyo SANUPS E11A202U, Introduction Thank you for choosing the SANUPS (E11A202U). SAVE THESE INSTRUCTIONS This manual contains important instructions for E11A202U that should be followed during installation and maintenance of the UPS and batteries.To use the UPS correctly and safely, read this manual before using the UPS. After reading, please keep it handy for convenient reference. This UPS is intended for installation in a temperature-controlled indoor environment free of conductive contaminants. ・ Operating temperature: 0 to 4

  • Sanyo SANUPS E11A202U, − 39 − 15.3 Protective Function Table The following table shows functions and operations which activate to protect the UPS. The ○ mark indicates lit LEDs and buzzer alarms. Operation panel (front panel) indicators Alarms Item INPUT Green OUTPUT Green INV.ON STAND BY Green ALARM Red O.L Red BATT. LOW Red Buzzer pattern (*1) Protective functions (UPS operations) Notes Preparation ○ (*2) (*2) - - - - Rectifier, charger, operation Power up Normal �

  • − 25 − Two beeps sound from the buzzer. The setting is saved and the UPS returns to normal operation. 10.2 Setup Menu Operations Set all menu items with the following procedure. This example shows how to set the “UPS operation mode” item to “Economy”. ① With MAIN MCCB on the back panel set to “ON”, check that the green INV.ON/S

  • Sanyo SANUPS E11A202U, − 9 − 5. External Dimensions and Part Names 5.1 Front and Back Panels Depth: 565 mm (22.24 inch) Weight: 29 kg (63.93 lbs) No. Name Label Function ① Control panel and indicators - Control panel for control operations, UPS status display, and function settings ② Forced bypass switch Forced Bypass Switch to bypass UPS during maintenance ③ Battery connector - Battery connector ④ Card interface CARD I

  • Sanyo SANUPS E11A202U, − 26 − 11. Maintenance and Inspection 11.1 Daily Inspection Check the control panel LED indicators to confirm that no error is indicated. Remove any dust or dirt adhering to the intake and exhaust vents and fan. No other special inspection or maintenance is required. 11.2 Periodic Inspection Inspect the following items once every 6 months. CAUTION ! ・ Internal maintenance and inspection should be performed only by technically qualified personnel. Electric shock, injury, burning, fuming or fire could

  • Sanyo SANUPS E11A202U, − 13 − 6.4 Preparation Before Installation CAUTION ! ・ Wear insulated gloves and take other precautions when connecting the batteries. Otherwise electric shock can result. ・ There is a constant voltage (max. approx. 48V: approx. 12V × 4) at the battery terminals. Do not touch them with your hands or short circuit them. Bodily injury can result. ・ The battery connector cannot be inserted in the wrong orientation. If it does not go in, do not try to force it. Doing so can damage th

  • − 7 − (3) Power supply environment If the UPS is used in an environment subject to long and frequent power outages (more than once a week), the batteries may not receive sufficient charge, which could result in foreshortened battery life and premature battery failure. (4) If the UPS is not operated for a long period, the batteries may require

  • − 11 − 5.3 External Interfaces UPS back panel No. Name Function ① PC I/F (PC interface) (RS-232C) Allows you to control the UPS from a computer (PC or workstation) by using the supplied power management software. Install the power management software (*2) on the computer, and connect the computer to the UPS with the supplied netwo

  • Sanyo SANUPS E11A202U, − 17 − ③ Connect the input power plugs of the load devices to the output terminals. MODEL Output terminal capacity Note E11A202U001 125V 20A receptacle × 4pcs. (NEMA 5-20R) The total output from all output receptacles must not exceed 2.0kVA ( 1.4kW ) If you must make a single-wire grounded connection, always connect the ground phase to the V terminal (phase) side. E11A202U001J 125V 30A receptacle × 1pcs. (NEMA L5-30R) The total output from all output receptacles must not exceed 2.0kVA �

Related Products and Documents (UPS):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 IBP BA701CA Instruction manual ibp/ba701ca-Q73.pdf 11 Jul 2023 30
2 Boss Audio Systems CAP4C Operation & user’s manual boss-audio-systems/cap4c-7RT.pdf 30 Jun 2023 7 1.17 Mb
3 Conversor Listenor Operation & user’s manual conversor/listenor-TN3.pdf 14 Mar 2023 4
4 Crypto NovaPad Q10101 Operation & user’s manual crypto/novapad-q10101-A58.pdf 10 Jan 2024 30
5 EAW JFX200 Specifications eaw/jfx200-4W3.pdf 09 Jan 2023 2 0.34 Mb
6 Aiwa XP-V510 Service manual aiwa/xp-v510-RRE.pdf 27 Oct 2023 29

Similar Resources:

  • Cyber Power

    BP36V60ART2U

    (14 pages)
    User’s Manual EXTENDED BATTERY MODULE (EBM) BP36V60ART2U BP72V60ART2U Cyber Power Systems (USA), Inc. 4241 12th Avenue East Suite 400 Shakopee, MN 55379 Phone: 877-297-6937 Fax: 952-403-0009 http://www.cyberpowersystems.com K01-0000515-03 …
  • Vertiv

    Liebert NXL

    (4 pages)
    1Liebert® Battery Interface Box™Product Specification/Installation Sheet—Liebert NXL™, Liebert NX™ 225-600 and Liebert EXL™SAVE THESE INSTRUCTIONSThis manual contains important instructions that should be followed during installation of your Liebert Battery Interface Box. The Liebert Battery Interface Box can be used with the Liebert NXL, Liebert …
  • CyberPower

    Value600E

    (2 pages)
    Value600/800/1000E Value600/800/1000EI User’s Manual K01-C000023-02 IMPORTANT SAFETY INSTRUCTIONS (SAVE THESE INSTRUCTIONS) This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or …
  • Omron

    BU2002RWL

    (78 pages)
    • This manual provides important safety-related information. Thoroughly read and understand this manual before installing and using the product. • Keep this manual in a convenient location so that you can refer to it whenever necessary.• The contents of this manual are subject to change without notice.中文使用说明书请参照“10. Notes of Ch …
  • Forza

    HT-752LCD-C

    (5 pages)
    HT-1002LCD-CThis unit is shipped from the factory with its internal battery fully charged; however, some charge may be lost during shipping. Therefore, it is recommended to recharge the battery prior to initial use. Simply plug the unit into an appropriate AC outlet, and allow it to charge to maximum capacity for 6 hours.Important safety instructions SAFE H …
  • Soyntec

    SEKURY C 800VA

    (12 pages)
    1 User Manual SEKURY™ C 800VA 1. Introduction SEKURY™ C includes a software which can remote and control UPS through LAN, get warning notifications through broadcast and mobile phone, multi-shutdown PCs and schedule UPS self-test. This unique software provides complete power protection for computer system while power failu …

Comments, Questions and Opinions: