  • Siemens MICROMASTER 440, Issue 10/06 6 Commissioning MICROMASTER 440 Operating Instructions (Compact) 69 6.4.19 Data sets For many applications it is beneficial to have the possibility to change several parameter settings simultaneous during operation or in the state ready to run with an external signal. By indexing it is possible to set a parameter to several values which can be activated by data set change-over. There are the following data sets: ¾ CDS Command Data Set ¾ DDS Drive Data Set Command data set (CDS) P0810 =... Command data set CDS bit 0 (local / remote) Selects the command source in which bit 0 should be read-out to select a command data set (CDS). t0 1 2

  • 4 Communications Issue 10/06 MICROMASTER 440 24 Operating Instructions (Compact) 4 Communications 4.1 Establishing communications MICROMASTER 440 ⇔ STARTER The following optional components are additionally required in order to establish communications between STARTER and MICROMASTER 440: ¾ PC <-> frequency inverter connecting set ¾ BOP if the USS standard values (

  • Siemens MICROMASTER 440, 6 Commissioning Issue 10/06 MICROMASTER 440 44 Operating Instructions (Compact) 6.4.12 Reference/limit frequencies Min. frequency (entered in Hz) Sets minimum motor frequency [Hz] at which motor will run irrespective of frequency setpoint. If the setpoint falls below the value of p1080, then the output frequency is set to p1080 taking into account the sign. Max. frequency (entered in Hz) Sets maximum motor frequency [Hz] at which motor will run irrespective of the frequency setpoint. If the setpoint exceeds the value p1082, then the output frequency is limited. The value set here is valid for both clockwis

  • Siemens MICROMASTER 440, 6 Commissioning Issue 10/06 MICROMASTER 440 52 Operating Instructions (Compact) Control word of motor model This parameter controls the operation of the sensorless vector control (SLVC) at very low frequencies. This therefore includes the following conditions: Bit00 Start SLVC open loop 0 NO 1 YES (Operation directly after an ON command) Bit01 Zero crossing SLVC open loop 0 NO 1 YES (zero crossing) f t p1755 Closed loop Open loop Start f t Closed loop Open loop Zero crossing p1755 p1755 For most applications the

  • Siemens MICROMASTER 440, 6 Commissioning Issue 10/06 MICROMASTER 440 30 Operating Instructions (Compact) BOP USS BOP link USS COM link P0700 = 2 Terminals CB COM link Sequence control Setpoint channel Motor control P1000 =... Selection of frequency setpoint * (enters the frequency setpoint source) 1 MOP setpoint 2 Analog setpoint 3 Fixed frequency 4 USS on BOP link 5 USS on COM link (control terminals 29 and 30) 6 CB on COM link (CB = communications module) 7 Analog setpoint 2 10 No main setpoint + MOP setpoint 11 MOP setpoint + MOP setpoint 12 Analog setpoint + MOP setpoint ... 76 CB on COM link + Analog s

  • Siemens MICROMASTER 440, Issue 10/06 6 Commissioning MICROMASTER 440 Operating Instructions (Compact) 61 6.4.18.8 Load torque monitoring This function monitors the transmission of force between a motor and driven load within a defined frequency range. Typical applications include, for example, detecting when a transmission belt breaks or detecting when a conveyor belt is in an overload condition. For the load torque monitoring, the actual frequency/torque actual value is compared to a programmed frequency/torque characteristic (refer to P2182 – P2190). Depending on P2181, the system monitors whether the permissible torque curve

  • Siemens MICROMASTER 440, 6 Commissioning Issue 10/06 MICROMASTER 440 74 Operating Instructions (Compact) r1079 CO: Selected frequency setpoint Displays the selected frequency setpoint. The following frequency setpoints are displayed: • r1078 total setpoint (HSW + ZUSW) • P1058 JOG frequency, clockwise • P1059 JOG frequency, counter-clockwise. Motor control RFG Skip frequency Inhibit neg. freq. setpoint Reverse Setpoint source r1079 r0020 r1170 P1110 P1091 P1080 P1082 P1120 P1135 . . . IfI r1078 JOG r1114 r1119 r1114 CO: Freq. setpoint after dir. ctrl. Displays the setpoint (reference) frequency in Hz after the function bloc

  • Siemens MICROMASTER 440, 6 Commissioning Issue 10/06 MICROMASTER 440 60 Operating Instructions (Compact) 6.4.18.6 Dynamic braking The following settings should always be made: ¾ The Vdc_max controller de-activated P1240 = 0 (def.: P1240 = 1) ¾ The compound brake de-activated P1236 = 0 (def.: P1236 = 0) ¾ Resistor brake activated P1237 > 0 (def.: P1237 = 0) Dynamic braking Dynamic braking is activated using parameter P1237 – the nominal (rated) duty cycle as well as the switch-in duration of the braking resistor are also defined. 0 Inhibited 1 Load duty cycle 5

  • Siemens MICROMASTER 440, Issue 10/06 6 Commissioning MICROMASTER 440 Operating Instructions (Compact) 73 r0054 CO/BO: Control word 1 Displays the first control word (STW) of the frequency inverter and can be used to display the active commands. Bit00 ON/OFF1 0 NO 1 YES Bit01 OFF2: Electrical stop 0 YES 1 NO Bit02 OFF3: Fast stop 0 YES 1 NO Bit03 Pulse enable

  • 6 Commissioning Issue 10/06 MICROMASTER 440 68 Operating Instructions (Compact) FFB Input parameters Output parameters Setting parameters AND1 P2810[2] BI: AND 1 r2811 BO: AND 1 – AND2 P2812[2] BI: AND 2 r2813 BO: AND 2 – AND3 P2814[2] BI: AND 3 r2815 BO: AND 3 – OR1 P2816[2] BI: OR 1 r2817 BO: OR 1 – OR2 P2818[2]

  • Siemens MICROMASTER 440, Issue 10/06 6 Commissioning MICROMASTER 440 Operating Instructions (Compact) 51 6.4.17.1 Sensorless vector control (SLVC) Control mode 20 Closed-loop Vector control – speed without encoder SLVC can provide excellent performance for the following types of application: • Applications which require high torque performance • Applications which require fast respond to shock loading • Applications which require torque holding while passing through 0 Hz • Applications which require very accurate speed holding • Applications which require motor pull out protection Filter time for act. freq (SLVC) Sets time constant of PT1 f

  • Siemens MICROMASTER 440, 6 Commissioning Issue 10/06 MICROMASTER 440 34 Operating Instructions (Compact) 6.4 Commissioning the application An application is commissioned to adapt/optimize the frequency inverter - motor combination to the particular application. The frequency inverter offers numerous functions - but not all of these are required for the particular application. These functions can be skipped when commissioning the application. A large proportion of the possible functions are described here; refer to the parameter list for additional functions.

  • Siemens MICROMASTER 440, Issue 10/06 6 Commissioning MICROMASTER 440 Operating Instructions (Compact) 65 PID cancer control Closed-loop dancer roll control is selected with P2251 = P2200 = 1. Important parameters and the structure are shown in the following diagrams. MOP ADC PID SUM PID FF USS BOP link USS COM link CB COM link ADC2 P2254 P2253 PID RFG PID PT1 − ∆ PID P2200 P2264 PID PT1 PID SCL & P2251 = 1 Output PID 0 1 Motor control P2257 P2258 P2261 P2271 P2269 P2270 P2265 P2280 P2285 0 SUM P1070 P1075 AFM P1120 P1121 RFG Parameter Parameter text Setting Meaning CI: PID setpointP2253 1024 Fixed setpoint

  • Siemens MICROMASTER 440, 6 Commissioning Issue 10/06 MICROMASTER 440 66 Operating Instructions (Compact) 6.4.18.10 Positioning down ramp Technological application Selects technological application. Sets control mode (P1300). 0 Constant torque 1 Pumps and fans 3 Simple Positioning Gearbox ratio input Defines the ratio between number of motor shaft revolutions to equal one revolution of the gearbox output shaft. n n Motor Load Load Ü Ü = P2482 P2481 = Motor revolutions Load revolutions Motor Gear Gearbox ratio output Defines the ratio between number of motor shaft revolutions to equal one revolution of the gearbox output shaft. No. of shaf

  • Siemens MICROMASTER 440, 2 Electrical Installation Issue 10/06 MICROMASTER 440 22 Operating Instructions (Compact) 2.4 Block diagram PE 1/3 AC 200 - 240 V 3 AC 380 - 480 V 3 AC 500 - 600 V SI PE L/L1, N/L2 L/L1, N/L2,L3 L1, L2, L3 = 3 ~ PE U,V,W M 12 ADC 1 ADC 2 12 60 Hz 50 Hz A/D A/D +10 V 0 V 0 - 20 mA max. 500 Ω NPN PNP CPU RS485 D/A D/A DCNA DCPA B+/DC+ B- DC- ~ = ADC1+ ADC1- ADC2+ ADC2- DIN1 DIN2 DIN3 DIN4 DIN5 DIN6 PTCA PTCB DAC1+ DAC1- DAC2+ DAC2- P+ N- COM NC NO COM NC NO COM NO 1 2 3 4 10 11 5 6 7 8 16 17 9 28 14 15 12 13 26 27 29 30 20 18 19 25 23 24 22 21 0 - 20 mA max. 500 Ω ≥ 4.7 kΩ Output 0 V max. 100 mA (isolated) or M

  • Siemens MICROMASTER 440, Issue 10/06 2 Electrical Installation MICROMASTER 440 Operating Instructions (Compact) 19 Shield connection Mains cable PE Hoisting eyes Mains cable Phase U1/L1, V1/L2, W1/L3 Top adjustment rail Bottom adjustment rail Status Display Panel Shield connection control leads Transformer adaption Motor cable Phase U2, V2, W2 Motor cable PE Shield connection Fan screws Bottom retaining screw Elektronic box Top retaining screw Connection to Y-Capacitor Fan fuses Cable opening for mains conection U1/L1, V1/L2, W1/L3 Fan C

  • Siemens MICROMASTER 440, Issue 10/06 6 Commissioning MICROMASTER 440 Operating Instructions (Compact) 75 6.5 Series commissioning An existing parameter set can be transferred to a MICROMASTER 440 frequency inverter using STARTER or DriveMonitor (refer to Section 4.1 "Establishing communications MICROMASTER 440 ⇔ STARTER"). Typical applications for series commissioning include: 1. If several drives are to be commissioned that have the same configuration and same functions. A quick / application commissioning (first commissioning) must be carried-out for the first drive. Its paramete

  • Siemens MICROMASTER 440, Issue 10/06 2 Electrical Installation MICROMASTER 440 Operating Instructions (Compact) 11 Input voltage range 3 AC 380 V – 480 V, ± 10 % (Unfiltered) Order No. 6SE6440- 2UD38-8FA1 2UD41-1FA1 2UD41-3GA1 2UD41-6GA1 2UD42-0GA1 Frame Size FX GX [kW] 90 110 132 160 200 Output Rating(CT) [hp] 125 150 200 250 300 Output Power [kVA] 145,4 180 214,8 263,2 339,4 CT-Input Current 1) [A] 169 200 245 297 354 CT-Output Current [A] 178 205 250 302 370 VT-Input Current 1) [A] 200 245 297 354 442 VT-Output Current [A] 205 250 302 370 477 [A] 250 315 400 450 560 Recommended Fuse 3NE 1227-0 1230-0 1332-0 1333-0 1435-0 Pipe cabl

  • Siemens MICROMASTER 440, 6 Commissioning Issue 10/06 MICROMASTER 440 72 Operating Instructions (Compact) 6.4.20 Diagnostic parameters r0021 CO: Act. filtered frequency Displays actual inverter output frequency (r0021) excluding slip compensation, resonance damping and frequency limitation. r0022 Act. filtered rotor speed Displays calculated rotor speed based on inverter output frequency [Hz] x 120 / number of poles. r0313 60 [Hz] r0021 [1/min] r0022 ⋅= r0032 CO: Act. filtered power

  • Siemens MICROMASTER 440, 6 Commissioning Issue 10/06 MICROMASTER 440 48 Operating Instructions (Compact) 6.4.16 V/f control P1300 =... Control mode The control type is selected using this parameter. For the "V/f characteristic" control type, the ratio between the frequency inverter output voltage and the frequency inverter output frequency is defined. 0 V/f with linear 1 V/f with FCC 2 V/f with parabolic characteristic 3 V/f with programmable characteristic (→ P1320 – P1325) P1310 =...

  • Siemens MICROMASTER 440, Warnings, Cautions and Notes Issue 10/06 MICROMASTER 440 2 Operating Instructions (Compact) Warnings, Cautions and Notes The following Warnings, Cautions and Notes are provided for your safety and as a means of preventing damage to the product or components in the machines connected. Specific Warnings, Cautions and Notes that apply to particular activities are listed at the beginning of the relevant chapters and are repeated or supplemented at critical points throughout these sections. Please read the information ca

  • 6 Commissioning Issue 10/06 MICROMASTER 440 42 Operating Instructions (Compact) 6.4.10 JOG JOG frequency right Frequency in Hz when the motor is rotating clockwise in the jog mode. JOG frequency left Frequency in Hz when the motor is rotating counter-clockwise in the jog mode. JOG ramp-up time Ramp-up time in s from 0 to the maximum frequency (p1082). JOG ramp- up is

  • Siemens MICROMASTER 440, Siemens AG Bereich Automation and Drives (A&D) Geschäftsgebiet Standard Drives (SD) Postfach 3269, D-91050 Erlangen Bundesrepublik Deutschland © Siemens AG, 2005, 2006 subject to change without prior notice Siemens Aktiengesellschaft Issue 10/06 Information about MICROMASTER 440 is also available from: Regional Contacts Please get in touch with your contact for Technical Support in your Region for questions about services, prices and conditions of Technical Support. Central Technical Support The competent consulting service for technical issues with a broad range of requirements-based services

  • 6 Commissioning Issue 10/06 MICROMASTER 440 64 Operating Instructions (Compact) Controller structures These structures are selected using parameters P2200 and P2251. P2200 = 0:0 2) P2251 = 0 1 P2200 = 1:0 2) P2251 = 0 2 P2200 = 0:0 1) P2251 = 1 3 P2200 = 1:0 1) P2251 = 1 4 − − − ON: active OFF1/3: active ON: - OFF1/3: - ON:

  • Issue 10/06 6 Commissioning MICROMASTER 440 Operating Instructions (Compact) 67 6.4.18.11 Free function blocks (FFB) P2800 =... Enable FFBs Parameter P2800 is used to activate all free function blocks (generally, P2800 is set to 1). Possible settings: 0 Inhibited 1 Enabled P2801 =... Activate FFBs Parameter P2801 is used to individually enable (act

  • Siemens MICROMASTER 440, 6 Commissioning Issue 10/06 MICROMASTER 440 32 Operating Instructions (Compact) 6.2 Motor data identification Factory setting Ambient motor temperature (entered in °C) The motor ambient temperature is entered at the instant that motor data is being determined (factory setting: 20 °C). yes no The difference between the motor temperature and the motor ambient temperature P0625 must lie in the tolerance range of approx. ± 5 °C. If this is not the case, then the motor data identification routine can only be carried-out after the motor has cooled down. Select motor data identification with P19

  • Siemens MICROMASTER 440, Issue 10/06 6 Commissioning MICROMASTER 440 Operating Instructions (Compact) 59 t P1234 OFF1/OFF3 ON t t ⏐f⏐ OFF ramp P1233 2 t OFF2 t t P0347 OFF2 OFF2 DC braking 0 1 DC braking active r0053 Bit00 P1234 =... DC braking start frequency (entered in Hz) Sets the start frequency for the DC brake. 6.4.18.5 Compound braking P1236 =... Compound braking current (entered in %) Defines DC level superimposed on AC waveform after exceeding DC-link voltage threshold of compound braking. The value is entered in [%] relative to rated motor current (P030

  • Siemens MICROMASTER 440, Issue 10/06 2 Electrical Installation MICROMASTER 440 Operating Instructions (Compact) 9 Input voltage range 3 AC 380 V – 480 V. ± 10 % (with built in Class A Filter) Order No. 6SE6440- 2AD22- 2BA1 2AD23- 0BA1 2AD24- 0BA1 2AD25- 5CA1 2AD27- 5CA1 2AD31- 1CA1 2AD31- 5DA1 Frame Size B C D [kW] 2,2 3,0 4,0 5,5 7,5 11,0 15,0 Output Rating(CT) [hp] 3,0 4,0 5,0 7,5 10,0 15,0 20,0 Output Power [kVA] 4,5 5,9 7,8 10,1 14,0 19,8 24,4 CT-Input Current 1) [A] 7,5 10,0 12,8 15,6 22,0 23,1 33,8 CT-Output Current [A] 5,9 7,7 10,2 13,2 18,4 26,0 32,0 VT-Input Current 1) [A] – – – 17,3 23,1 33,8 37,0 VT-Output Current

  • Issue 10/06 6 Commissioning MICROMASTER 440 Operating Instructions (Compact) 57 BI: Fct digital output 1 Defines the source for digital output 1. NOTE The brake relay can also be controlled from another digital output (if this is available) or using a distributed I/O module. Analog to DOUT 1, it should be guaranteed that the I/Os are controlled by the status bit “MHB active

Related Products and Documents (Inverter):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 Yamaha CRW-F1DX Owner's manual yamaha/crw-f1dx-17D.pdf 19 Jan 2024 74 2.16 Mb
2 Philips 32PT740H37A Directions for use manual philips/32pt740h37a-68G.pdf 16 Aug 2022 56
3 Campbell Hausfeld FP2030 Operating instructions manual campbell-hausfeld/fp2030-XJ3.pdf 18 Nov 2023 12
4 HoMedics BPW-410WGN Instruction manual homedics/bpw-410wgn-LB3.pdf 26 Dec 2022 36
5 Siemens FI18NP Series Operating instructions manual siemens/fi18np-series-23H.pdf 27 Jun 2023 24 3.18 Mb
6 Cucina Pro 300 Manual  cucina-pro/300-H49.pdf 06 May 2023 5

Similar Resources:

  • UNIRAC

    SolarMount

    (6 pages)
    © 2005 by UniRac, Inc. All rights reserved.Pub 050304-1iiMarch 2005 UniRac welcomes input concerning the accuracy and user friendliness of this publication. Please write to [email protected]. Des. Patent No. D496,248S. Other patents pending.This manual details the procedure for fl ush mounting SolarMount to a pitched roof. If your installation in …
  • Nupower

    EVOLUTION NPEGG780

    (156 pages)
    NPEGG780IGeneratore di corrente ..............12GBGasoline generator ........................19FGénérateur de courant ..............26DStromerzeuger ....................................33EGenerador de corriente ............40PGerador de corrente .....................47NLStroomgenerator ..............................54DKStrømgenerator ..................... …
  • Westinghouse

    iGen4500

    (87 pages)
    SAFETY USER MANUALDO NOT RETURN THIS PRODUCT TO THE STORE If you have questions or need assistance, please call customer service at 855-944-3571.iGen4500 Digital Inverter Generator Gasoline: 3700 Running Watts | 4500 Peak Watts …
  • Siemens

    SINAMICS V20 Inverter

    (404 pages)
    ___________________ ___________________ ___________________ ___________________ ___________________ ___________________ ___________ ___________________ ___________________ ___________________ ___________________ ___________________ ___________________ SINAMICS SINAMICS V20 Inverter Operating Instructions 11/2016 A5E34559884-006 Preface Fundamental …
  • Nice

    Solemyo SYKCE

    (44 pages)
    SolemyoEN - Installation and use instructions and warningsIT - Istruzioni ed avvertenze per l’installazione e l’usoFR - Instructions et avertissements pour l’installation et l’utilisationES - Instrucciones y advertencias para la instalación y el usoDE - Anweisungen und Hinweise für die Installation und die BedienungPL - Instrukcje instalacji i uży …
  • Old World Industries

    PKC0AW

    (10 pages)
    Inversor de Energía de 3000 VatiosModelo: PKC0AWManual del Propietario e Información de GarantíaLea completamente estas instrucciones antes de usar este producto.Conserve este Manual del Propietario para referencia futura.P/N XXXXX, 1/0913000 Watt Power InverterModel No.: PKC0AWOwner’s Manual and Warranty InformationRead these instructions completely b …

Comments, Questions and Opinions: