  • Toshiba Satellite 4200, TOSHIBA 25 6.8 Light Emitting Diode (LED) Functions The following list describes the conditions necessary for each LED lamp to be "on". This green LED lamp is "on" when the UPS is not in an input over-voltage condition, input under-voltage condition, or power failure state. If there is an input power failure, this lamp is "off". If there is no power failure and the input voltage is in an over-voltage condition, the AC IN lamp will flicker on and off rapidly (0.4 sec "on" and 0.4 sec "off"). If there is no power failure and the input voltage is in an under-voltage condition, the AC

  • Toshiba Satellite 4200, TOSHIBA 6 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for 4200 Series 75/ And 100kVA that should be followed during the installation, operation, and maintenance of the UPS Systems. Refer to the Battery System Manual for details on operating and maintaining the battery units for each system. UPS System’s output is not equipped with an over-current protection device, nor an output disconnect for the AC output; therefore, a circuit breaker should be provided, by the user, between the UPS output an

  • Toshiba Satellite 4200, TOSHIBA 23 The recharge process usually consists of three periods. During the first period, the charging current is maintained at approximately 38.0 amperes. This current is the maximum value that can be used to charge the batteries (for minimal recharge time) while assuring safety and long battery life. In the second period, constant-voltage control starts and current gradually decreases as the batteries charge to their normal fully charged state. In the third period, a slight "trickle" current continues to flow into the batteries to keep them fully charged and "floating" at the normal DC Voltage level. A full recharge usually requires approximately

  • Toshiba Satellite 4200, TOSHIBA 30 6.12 Shutdown Procedure When turning off the UPS, the following shutdown procedure should be used: 1) Move the unit's STOP/RUN key switch, located on the front panel, to STOP. Operation of the UPS unit's inverter stops. Output power is now provided to the load through the unit's bypass circuit. While in this state of operation; if a power failure occurs in the commercial power source, then the UPS will lose power and power to the load device will be interrupted. The UPS unit's battery charging circuit and chopper circuit remains activated. DANGER Do not touch the UPS termi

  • Toshiba Satellite 4200, TOSHIBA 34 When the battery test is completed, the previous operation will be resumed and the main system MONI screen will be displayed. If the battery test detects a low DC battery voltage, then the message screen will display: - UPS ON-LINE - OUTPUT VOLTAGE=208V CURRENT=38/55/48% * LOW BATTERY * If the battery test passes then the following screen message will be displayed: - UPS ON-LINE - OUTPUT VOLTAGE=208V CURRENT=38/55/48% * UPS "OK" * If the inverter is not operating when the BATT

  • Toshiba Satellite 4200, TOSHIBA 4 TABLE OF CONTENTS GENERAL SAFETY INSTRUCTIONS................................................................................. 3 TABLE OF CONTENTS....................................................................................................... 4 IMPORTANT SAFETY INSTRUCTIONS ............................................................................. 6 1.0 Product Description.................................................................................................. 8 1.1 Theory of Operation.........................

  • TOSHIBA 19 5.0 Specifications 5.1 4200 Series Specifications 75 and 100kVA @ Standard 208Vac Output Model Number U42B3F750C6CB U42B3F10KC6CB Rated Output Capacity 75kVA 100kVA External Dimensions 0 0 Rated Voltage 208V/120V Voltage Variation +10% to –15% ; (-15% to –30%) **** Rated Frequency 50/60 Hz Number Phases / Wires 3 Phases ; 4 Wire + GND * Power Factor

  • Toshiba Satellite 4200, TOSHIBA 32 6.14 Key Functions 6.14.1 MONI After the UPS has been successfully started, the system will be in the normal 'AC input mode' of operation. The LCD screen will automatically display the main MONI (monitor) function. If the MONI key is pressed at this time the screen output will not change. The MONI function automatically monitors the entire UPS system. The LCD screen will automatically switch "off" after a period of keypad inactivity and switch "on" if any key is pressed. It will switch "on" automatically during battery discharge or if an abnormality develops in the system (see Section 6.15.3 "

  • TOSHIBA 29 6.11 Start-up Procedure The UPS batteries must be charged before the UPS is used for the first time or if the unit has not been used (ac power source removed) for more than 10 days (Refer to Section 6.10). If the batteries are charged then use the following start-up procedure: 1) Verify that all power switches are off, and that the "RUN / STOP

  • Toshiba Satellite 4200, TOSHIBA 13 4.0 UPS Connections 4.1 Power Connections 75 and 100kVA The following illustrates the wiring connections to the Input and Output Terminations points for the 75 and 100kVA UPS Models 4.1.1 H1 H2 H3 Input (N) L1 L2 L3 GND (N)

  • TOSHIBA 18 4.3.2 RS-232C The RS-232C serial communication interface is available through a DB9 female connector located on the backside of the UPS (see Section 9 for DB9 connector location). This interface allows control of the UPS from a personal computer running special Toshiba software. The computer and the UPS are connected through a serial RS-232C communication port. T

  • Toshiba Satellite 4200, TOSHIBA 35 6.15 Menu Data Screens 6.15.1 Settings for Calendar and Clock Press the MENU key to access the menu data screens and press the 'down' arrow key to scroll to the present date and time adjustment screen: CALENDER / CLOCK DATE (DAY) TIME >*F1: DATA SET MODE >∆/∇ PRV/NEXT SCREEN Press the F1 key to display the following active adjustment screen: CALENDER / CLOCK DATE (DAY) TIME > ∆/∇ : UP/DOWN >ENTER:NEXT DATA Press the "up/down" arrows to increment, or decrement the character(s) above the flashing cu

  • TOSHIBA 26 6.9 Liquid Crystal Display (LCD) Functions The liquid crystal display (LCD) screen is a 4-line by 20-character wide display. The LCD display contains information about the operation of the UPS. It should be used in conjunction with the LED display (see Section 6.8) and the audible alarms (see Section 6.7) for total system monitoring. The LCD displays

  • Toshiba Satellite 4200, TOSHIBA 7 WARNING Personnel knowledgeable of batteries and the required precautions should perform installation and servicing of batteries. Keep Unauthorized personnel away from the batteries. WARNING Proper maintenance to the battery system of this unit must be done by a qualified service technician, this is essential to the safety and reliability of your UPS system. Refer to service manual. A battery can present a risk of electrical shock and high short DANGER circuit current. The following precautions should be observed when working with batteries. 1) Verify that the UPS is off and is disconnected from the power source. 2) Remo

  • Toshiba Satellite 4200, TOSHIBA 5 6.14.3 OUT ............................................................................................................................................... 32 6.14.4 BATT Key ...................................................................................................................................... 33 6.14.5 MENU, F1, ENTER, UP, & DOWN Keys....................................................................................... 33 6.14.6 BATT TEST Key ............................................................................................................................ 33 6.14.7 BUZ

  • Toshiba Satellite 4200, TOSHIBA 28 6.10 Initial Battery Charge The UPS System's battery must be charged before it is used for the first time or when the unit has not been used (AC power source removed) for more than 10 days. Use the following procedure to recharge the UPS System's battery: 1) Switch on power at the UPS input distribution panel. 2) Move the UPS unit's MCCB1 power switch to "on" (see Section 9 for location). Note: The UPS units’ battery charging circuit is now activated. The AC IN lamp will be "on". The LCD

  • Toshiba Satellite 4200, TOSHIBA 9 2.0 Uncrating/Inspection/Storage/Disposal 2.1 Uncrating the new UPS equipment: Upon receipt of the UPS, a careful inspection for shipping damage should be made. 1) Remove the screws that attach the shipping crate to the pallet; remove the crate and foam packing material. 2) Unbolt the rails from both the unit and the shipping pallet. Place the rails on the front of the pallet as shown in figure 2.2 and figure 2.3. Use the four 1/2x3" bolts used to secure the rails to the shipping pallet t

  • Toshiba Satellite 4200, TOSHIBA 12 3.2 Pre-start Precautions Before connecting the UPS to a power source; move the MCCB switch (ON/OFF), on the side panel, to the OFF position and move the operation STOP/RUN key switch, on the front panel (See Section 9 for location), to the STOP position. 3.3 Operating Precautions 1) The UPS should not be powered up until the entire operation manual has been reviewed, and understood. 2) The input power source voltage must be within +10% to -15% of the rated input voltage. The input frequency must be within the rated input frequency range. Voltages and frequencies outside of the permissible range may cause internal prote

  • Toshiba Satellite 4200, TOSHIBA 16 4.2 Control Circuit and External Battery Interface Connections 75 and 100kVA The following illustrates the wiring connections of the Control Circuits, and Battery Interface Circuits. 4.2.1 Recommended Wire Size and Tightening Torque UPS Control and Battery Interface Minimum Wire Size and Tightening Torque for UPS Control and Battery Interface Circuits USE MINIMUM 75° C COPPER WIRING TERMINAL (TERMINAL #) 75kVA 100kVA AWG TIGHTENING TORQUE AWG TIGHTENING TORQUE UPS CONTROL CIRCUITS (1-24)* 14-16 8 in-lbs. 14-16 8 in-lbs. BATTERY CONTROL CIRCUITS

  • Toshiba Satellite 4200, TOSHIBA 43 9.2 Shipping Dimensions 75, and 100kVA Shipping Dimensions 75Kva 100kVA Width- Inches (cm) 64.0 (162.6) 64.0 (162.6) Depth- Inches (cm) 42.5 (108.0) 42.5 (108.0) Height- Inches (cm) 72.438 (184.0) 72.438 (184.0) Model Shipping Weights U42B3F10KC6CB 2600 Pounds 1180 Kilograms U42B3F750C6CB 2600 Pounds 1180 Kilograms

  • Toshiba Satellite 4200, TOSHIBA 8 1.0 Product Description 1.1 Theory of Operation An Uninterruptible Power Supply (UPS) is a system that is installed between the commercial power and the load equipment. The UPS provides steady AC output power during commercial power fluctuations and interruptions. During normal operation the UPS utilizes commercial AC power and removes high voltage spikes and transients caused by switching and faults on the main utility. The result of this process is maximum power conditioning and regulation.

  • Toshiba Satellite 4200, TOSHIBA 37 6.15.6 Output Voltage Adjustment When the MENU key is pressed and held 3-4 seconds during normal 'ac input mode' of operation, the LCD screen displays the output voltage on the present output voltage adjust screen: OUTPUT VOLT. ADJUST OUTPUT VOLTAGE.=###% >F1:DATA SET MODE > ∆/∇ :PREV/NEXT SCREEN Press the F1 key to display the following active adjustment screen: OUTPUT VOLT. ADJUST REFERENCE ADJUST: ## > ∆/∇ :CHANGE DATA >ENTER: ACCEPT CHANGE The locations marked ## will show the numerical value of the allowable voltage adjustment parameter values. Press the 'up' and 'down&apo

More Instructions:

DOWNLOAD

Related Products and Documents (UPS):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 Toyota Corolla E12-A Installation instructions manual toyota/corolla-e12-a-742.pdf 17 Feb 2023 35
2 Fisher-Price LittlePeople N6010 Instructions fisher-price/littlepeople-n6010-6DV.pdf 05 Jan 2024 4
3 Walkera furious 320 Quick start manual walkera/furious-320-VU2.pdf 24 May 2023 22
4 Desa (V)T36ENA Owner's operation and installation manual desa/v-t36ena-1K1.pdf 31 Oct 2023 38 2.3 Mb
5 Quest Engineering K0016 Instruction manual quest-engineering/k0016-U2Y.pdf 03 Feb 2024 7
6 CUE AIRCUE-6X10 Operation & user’s manual cue/aircue-6x10-73M.pdf 27 Oct 2023 28

Similar Resources:

  • HP

    T1500 XR

    (2 pages)
    hp ups T1500 xr/T2200 xr models extended runtime module installation instructions Read Instructions Completely Before Beginning Installation Procedures Hewlett-Packard Company shall not be liable for technical or editorial errors or omissions contained herein. The information in this document is provided “as is” without warrant …
  • Tripp Lite

    SmartOnline

    (68 pages)
    1Owner’s ManualSmartOnline® Rack/Tower On-Line UPS SystemsNot suitable for mobile applications.1. Important Safety Instructions 22. Installation 3 2.1 Mounting (Rack) 3 2.2 Mounting (Tower) 4 2.3 Connection and Start-Up 4 2.4 Optional Connections 53. Operation 8 3.1 Front Panel Switches 8 3.2 Advanced Operational 8 Settings 3.3 F …
  • LEGRAND

    LIMOGES Cedex 87045

    (13 pages)
    87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 – Fax :+33 05 55 06 88 88 DPX3 160 + earth leakage DPX3-I 160 + earth leakage Reference(s) : 420 030/ 031/ 032/033/ 034/ 035/ 036/ 037/ 070/ 071/ 072/ 073/ 074/ 075/ 076/ 077/ 110/ 111/ 112/ 113/ 114/ 115/ 116/ 117/ 150/ 151/ 152/ 153/ 154/ 155/ 156/ 157/ 197 1/1 Technical sheet: F01361EN/02 Update: 09/0 …
  • OPTI-UPS

    ES1000C-RM

    (1 pages)
    Line Interactive UPS SeriesOn Line UPSSeriesAVR SeriesNetworkingSeriesInverter SeriesSurge Series Green Power Series Standby UPSSeriesEnhanced SeriesProtection for small electronic equipmentES550C / ES800C / ES1000C / ES1500CFeaturesThe ESC series offer the highest power capacity and the best equipment protection around. Not only do they protect against blac …
  • Eaton

    9PX 1:1

    (13 pages)
    Eaton® setUPS Firmware upgrade procedure Eaton®setUPS_9PX_1-1_1to3k_firmware_upgrade_rev_02 Page 1/13 UPS model : 9PX 1:1 1 to 3kVA Date : 02/09/2016 …
  • Siemens

    SITOP DC-UPS-Module 40

    (8 pages)
    © Siemens AG 2016 1 of 8 SITOP DC USV Modul 40 A5E38473872, 08.2016 SITOP DC-USV-Modul 40 / SITOP DC-UPS-Module 40 6EP1931-2FC21 6EP1931-2FC42 Betriebsanleitung A5E38473872 Operating Instructions Manuel d'utilisation https://support.industry.siemens.com/cs/fr/fr/view/20781697 Manuale di servizio https://support.industry.siemens.com/cs/ …

Comments, Questions and Opinions: