ICM Controls SC 4211 Installation, Operation & Application Manual
|
ICM Controls SC 4211, 5 Single Compressor heat pump with electric backup Dual Compressor heat pump with electric backup * outdoor sensor only reads outdoor temperature Transformer 120 VAC 24 VAC Reversing Valve Compressor Auxiliary Heat Optional remote or outdoor sensor Service Led Wire Emergency Heat Fan Compressor #2 Transformer 120 VAC 24 VAC Reversing Valve Compressor #1 Auxiliary Heat Optional remote or outdoor sensor Service Led Wire Emergency Heat Fan Wiring Diagrams Note: For systems without emergency strip heat, a jumper wire should be placed between W2 & E.
ICM Controls SC 4211, 10 5. Minimum Deadband (1°F to 9°F) (1°C to 5°C) Set the minimum separation between heat setpoint and cool setpoint in Auto Changeover Mode. Press the up or down button to set deadband value. Press the right button to advance to the next screen. Press the up or down button to select. Press the right button to advance to the next screen. 6. System – Set for reversing valve operation and number of compressors in your system. Choose System Reversing Valve Active Number of Compressors or Compressor Stages Heat Pump HP O 1 HP b 1 HP O 2 HP b 2
ICM Controls SC 4211, ONE-YEAR LIMITED WARRANTY The Seller warrants its products against defects in material or workmanship for a period of one (1) year from the date of manufacture. The liability of the Seller is limited, at its option, to repair, replace or issue a non-case credit for the purchase prices of the goods which are provided to be defective. The warranty and remedies set forth herein do not apply to any goods or parts thereof which have been subjected to misuse including any use or application in violation of the Seller’s instructions, neglect, tampering, impr
ICM Controls SC 4211, 12 12. Maximum Cycles Allowed Per Hour (- -, 2-6) - - = as many as needed, 2-6 = maximum cycles/hour Press the up or down button to select. Press the right button to advance to the next screen. 11. Room Temperature Offset (+9°F to -9°F) (+4.5°C to -4.5°C) Adjust to calibrate displayed room temperature to match actual room temperature. Note: When not set to 0, will display Press the up or down button to select. Press the right button to advance to the next screen. 13. T
ICM Controls SC 4211, 11 7. Auxiliary Delay ON – (0-30 minutes) Set the delay time in minutes for auxiliary heat to be locked out after a call for second stage. Press the up or down button to select. Press the right button to advance to the next screen. 8. Lockout (0-8°, COOL-HEAT) Select the number of degrees set temperature can be changed during keypad lockout. COOL-HEAT lockout allows adjustment of the set temperatures to the maximum heat set temperature selected in Step 9 and minimum cool set temperature selected in Step 10. Note: The mode cannot be changed when the thermostat is
ICM Controls SC 4211, 2 Specications Icon Descriptions Fan operation icon Cooling operation icon Heating operation icon Lock mode activated Room temperature offset activated Electrical rating: • 24 VAC (18-30 VAC) • 1 amp maximum per terminal • 3 amp maximum total load Temperature control range: 45°F to 90°F (7°C to 32°C) Accuracy: ± 1°F (± 0.5°C) System configuration: 2-stage heat pump Timing: Anti-short Cycle: 4 minutes (bypass anti-short cycle delay by returning to OFF mode for 5 seconds) Backlight Operation: 10 seconds Terminations: S1, S2, L, R, C, O/B, Y1, W2, Y2, G, E Emergency heat
ICM Controls SC 4211, 8 Conguration Mode OFF 1. Verify the SC4211 is in the OFF mode. Press the SYS (left) button until off mode displays. 2. Remove the cover of the thermostat by gently pulling near one of the corners at the top of the thermostat. 3. Press the CONFIG button for 1 second while the SC4211 is in OFF mode. To exit configuration mode, press the CONFIG switch for 1 second. Press the up or down button to change settings within each screen. Down button Up button Press the right button to advance to the next screen. Note: Pressing the left button will return you to the previous screen. L
ICM Controls SC 4211, 6 Remote Sensor Installation (Optional) 1. Remove cover from remote sensor housing. 2. Select an appropriate location for mounting the remote sensor. 3. Mount remote sensor unit using hardware provided. 4. Install two strand shielded wire between remote sensor and thermostat. Shielded wire must be used. Do not run remote sensor wire in conduit with other wires. • Wire 1 should run between the S1 terminal on the thermostat and the S1 terminal on the remote sensor • Wire 2 should run between the S2 terminal on the thermostat and the S2 terminal on the remote sensor •
3 Package Contents/Tools Required Package includes: SC4211 thermostat on base, thermostat cover, wiring labels, screws and wall anchors, Installation, Operation and Application Guide Tools required for installation: Drill with 3/16” bit, hammer, screwdriver Important Safety Information WARNING! : Always turn off power at the main power supply before installing, cleaning, or
ICM Controls SC 4211, 2-Stage Heat Pump Auto Changeover Hardwire SC 4211 Installation, Operation & Application Guide For more information on our complete range of American-made products – plus wiring diagrams, troubleshooting tips and more, visit us at www.icmcontrols.com • Configurable • 2-Stage Heat Pump Systems • Large Display With Backlight • Selectable Fahrenheit or Celsius • SimpleSet™ Field Programming • Status Indicator Lights • Relay Outputs (minimum voltage drop in thermostat) • Remote Sensor Compatible • Ideally Suited for: – Residential (New Construction/Replacement) – Light Commercial Non-Programmable Electron
ICM Controls SC 4211, 7 Terminal Designator Descriptions 1 ST Cool 2 ND Cool 1 ST Heat 2 ND Heat Heat Pump (One Compressor) Y1, G, O Y1, G, O Y1, G, B Y1, W2, G, B Heat Pump (Two Compressors) Y1, G, O Y1, Y2, G, O Y1, G, B Y1, Y2, G, B Emergency Heat N/A N/A E, G E, W2, G SC4211 Output Chart L – Service Led indicator R – 24 VAC hot C – 24 VAC common O/B – Configurable O – cool active reversing valve B – heat active reversing valve Y1 – 1st stage cool, 1st stage heat W2 –
ICM Controls SC 4211, Table of Contents Parts Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Icon Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 Important Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ICM Controls SC 4211, 4 To Install Thermostat ELECTRICAL SHOCK HAZARD – Turn off power at the main service panel by removing the fuse or switching the appropriate circuit breaker to the OFF position before removing the existing thermostat. IMPORTANT: Thermostat installation must conform to local and national building and electrical codes and ordinances. Note: Mount the thermostat about five feet above the floor. Do not mount the thermostat on an outside wall, in direct sunlight, behind a door, or in an area affected by a vent or duct. 1. Turn off power to the heating and cooling system by removing the fuse or switching the appropriate circu
ICM Controls SC 4211, 21 Troubleshooting Symptom Remedy No display Check for 24 VAC at thermostat; display is blank when 24 VAC is not present System fan does not come on properly Verify wiring is correct All thermostat buttons are inoperative Verify 24 VAC is present; unit locks out when 24 VAC is not present No response with first button press First button press activates backlight only Thermostat turns on and off too frequently Adjust temperature differential (see Configuration Mode Settings 2 & 3, Page 9) Fan runs continuously Press FAN (right) button to turn fan off Emer status
ICM Controls SC 4211, 17 Cool Mode • In this mode, the thermostat controls the cooling system. When the cooling outputs, the snowflake icon apprears on the display. Note: There is a four minute delay for your compressor to restart after it has turned off. To bypass the compressor time delay, go to OFF mode for 5 seconds. Cool and Heat Mode (Auto Changeover) • In this mode, the thermostat controls the cooling and heating systems, automatically changing over from one to the other as needed. • The timing displ
14 Mode of Operation The SC4211 is a non-programmable, manual or auto changeover, 2-stage heat pump thermostat. An outdoor sensor can be used to monitor the outdoor temperature. The thermostat activates the heating appliance when the room temperature is below the set heat temperature (by the differential temperature) and the red AUX indicator light (during electric strip heat o
ICM Controls SC 4211, 19 Lockout Feature The SC4211 has a button lockout feature so the mode cannot be changed and the temperature adjustment is limited. Select the appropriate lockout from Configuration Mode Settings (Step 8, Page 11) of this guide. To activate the LOCK feature: 1. Simultaneously press the SYS, FAN and UP buttons for 10 seconds. 2. will display and the lockout function will be enabled. To deactivate the LOCK feature, repeat steps 1 and 2 above.
20 SimpleSet TM Field Programming This feature is used for transferring the configuration from the master to the target thermostat. All thermostats for a job can be mounted and powered up. Configure one thermostat. This will be the master. The master will be used to copy the configuration to the rest of the thermostats. Preparing the master to Send: 1. The master m
ICM Controls SC 4211, 16 Operating Modes There are five possible operating modes for the SC4211. Off, Heat, Emergency Heat, and Cool & Heat modes are accessed by pressing the SYS (left) button. OFF Mode • In this mode, the thermostat will not turn on the heating or cooling devices Note: The indoor fan can be turned on manually in every operating mode by pressing the FAN (right) button. The word FAN shows on the display and the fan icon appears when the fan operates. OFF Heat Mode • In this mode, the thermostat controls the heating system. When the heat outputs, the flame icon apprears on the display. Note: There is a four m
ICM Controls SC 4211, 15 Button Functions UP Used to increase the time, set temperatures and to adjust configuration settings. DOWN Used to decrease the time, set temperatures and to adjust configuration settings. SYS (left) Used to change from OFF, HEAT, EMER HEAT, COOL and COOL & HEAT modes FAN (right) Used to turn on and off the indoor fan. UP, SYS and Fan Held in simultaneously for 10 seconds to lock and unlock the thermostat. DOWN and SYS Pressed simultaneously to display outdoor temperature if outdoor remote sensor is connected. SYStem (left) FAN (right) Down button Up button
ICM Controls SC1901L Thermostat Installation, operation & application manual
SC1901L |
ICM Controls SC 3801 Thermostat Installation, operation & application manual
SC 3801 |
ICM Controls SC 2001 Thermostat Installation, operation & application manual
SC 2001 |
ICM Controls SimpleComfort 1600 Thermostat Specifications
SimpleComfort 1600 |
ICM Controls SC1001 Thermostat Installation, operation & application manual
SC1001 |
ICM Controls SimpleComfort SC2211L Thermostat Specifications
SimpleComfort SC2211L |
ICM Controls SC 1800 Thermostat Installation, operation & application manual
SC 1800 |
ICM Controls SC3000L Thermostat Installation, operation & application manual
SC3000L |
# | Manufacturer | Model | Document Type | File | Updated | Pages | Size |
---|---|---|---|---|---|---|---|
1 | Amana | 36-308798-03-0 | Use and care manual | amana/36-308798-03-0-8C2.pdf | 22 Mar 2023 | 28 | 4.93 Mb |
2 | Audiovox | LCMR4N | Owner's manual | audiovox/lcmr4n-MG7.pdf | 22 Nov 2023 | 6 | 0.24 Mb |
3 | Frymaster | PASTAMAGIC 17BC | Installation & operation manual | frymaster/pastamagic-17bc-85B.pdf | 20 Oct 2023 | 20 | 0.3 Mb |
4 | Samsung | DVD-P380K | Operation & user’s manual | samsung/dvd-p380k-259.pdf | 18 Nov 2023 | 70 | 53.31 Mb |
5 | Accusplit | 705MX | Operating instructions | accusplit/705mx-PGK.pdf | 03 Jul 2023 | 1 | 1.32 Mb |
6 | Denon | CHR-F103 | Operating instructions manual | denon/chr-f103-978.pdf | 09 Mar 2023 | 43 | 1.19 Mb |
TOTALINE
NON-PROGRAMMABLE DIGITAL THERMOSTAT TST-EGND06413SCS09 / TST-EGND06413SCS10 TST-EGND06423SCS09 / TST-EGND06423SCS10 -Cool, Heat and Ventilation -Large, Easy To Read Display -Blue Backlight -Fahrenheit or Centigrade -Auto Recovery -2-pipe or 4-pipe Selection -DA or DB Type Selection -Key Card Function Specification Set-Point Range: 5� …
TST-EGND06413SCS09(2 pages) |
Siemens
A5W90008184 Smart Thermostat Receiver RCR114.1 en Quick guide de Kurzanleitung cs Stručný návod el Σύντομος οδηγός es Guía Rá pida fr Prise en main rapide hu Gyors ú tmutató it Guida rapida nl Wegwijzer zh-CN 快速向导 fi Pikaohje pl Szybki przewodnik tr Hızlı Kılavuz
…
RCR114.1(30 pages) |
Honeywell
PRODUCT DATA33-00096-01VisionPRO® 8000 with Wi-Fi®APPLICATIONThe VisionPRO® 8000 with Wi-Fi features an effortless, 7-Day programmable touchscreen thermostat that provides control of temperature and one of the following: humidification, dehumidification, or ventilation. Up to 3 Heat/2 Cool heat pump systems or up to 2 Heat/2 Cool conventional systems are …
VisionPRO 8000(92 pages) |
ICM Controls
16 1917 2018123ONE-YEAR LIMITED WARRANTYThe Seller warrants its products against defects in material or workmanship for a period of one (1) year from the date of manufacture. The liability of the Seller is limited, at its option, to repair, replace or issue a non-case credit for the purchase prices of the goods which are provided to be defective. The warrant …
SC3211L(2 pages) |
Herz
H7990 series Touch Pad fan coil unit thermostats are designed to control the room temperature in air-conditioning fan coil unit system or dust pipe channel system. H7990 series thermostats with microprocessor and big LCD display. It shows the following items: working status (cool, heat or ventilation), fan speed, room temperature, set-point tempera …
H7990 Series(4 pages) |
CMS
CNC Machining Centres C.M.S. S.p.A. Costruzioni Macchine Speciali Via Antonio Locatelli, 49 (I) - 24019 ZOGNO (Bergamo) Tel. (0345) 64.350 - Fax (0345) 64.330 Autore Fausto Zanardi C:\DATI\WORD\Refrigeratori\TexaProgTermFTX050.doc Pag. 1Servizio Assistenza T E X A C h i l l i n g U n i t Electronic Thermostat TX050 Convert from C …
TX050(3 pages) |
Plantronics Headsets Savor M1100#9WXS53: Savor M1100 Headsets Declaration of conformity Savor M1100, 1 |
Fujitsu Motherboard D1421Fujitsu D1421 User Manual (Technical manual), @BJMK93 D1421, 20 |
Samsung Air Conditioner AW05N0 SeriesAW05N0 Series Operation & user’s manual - 98VB73 AW05N0 Series, 12 |
Sonicare Electric Toothbrush FlexCareElectric Toothbrush #847L79 FlexCare, 1 |
LG Refrigerator GR-642APA#85K368: GR-642APA Refrigerator Service manual GR-642APA, 44 |
K-array Subwoofer KR400S#32I7R3: KR400S Subwoofer Operation & user’s manual KR400S, 44 |
DAPAudio Amplifier Vision 1600 ORDERCODE D4151#87T747: Vision 1600 ORDERCODE D4151 Amplifier Manual Vision 1600 ORDERCODE D4151, 18 |
Sony Car Receiver CDXGT300SSony CDXGT300S User Manual (Operating instructions manual), @GH4QM7 CDXGT300S, 100 |
Whirlpool Refrigerator ET16EPWhirlpool ET16EP Refrigerator Use & care manual ET16EP, 12 |
Telex Intercom System XCP-32-DB9Intercom System PDF Technical manual XCP-32-DB9, 4 |
Cygnett Clock Radio GrooveBase CY-A-GBAGrooveBase CY-A-GBA Operating instructions - 3M2R1V GrooveBase CY-A-GBA, 3 |
Currys Essentials TV DVD Combo C15DVDB10C15DVDB10 (TV DVD Combo ePDF Manual, #XD22V9) C15DVDB10, 1 |