  • Elgar GUPS 2400A–107, ELGAR ONE–YEAR WARRANTY Elgar Electronics Corporation (hereinafter referred to as Elgar) warrants its products to be free from defects in material and workmanship. This warranty is effective for one year from the date of shipment of the product to the original purchaser. Liability of Elgar under this warranty shall exist provided that: • the Buyer exposes the product to normal use and service and provides normal maintenance on the product; • Elgar is promptly notified of defects by the Buyer and that notification occurs within the warranty period; • the Buyer receives a Return Material Author

  • Elgar GUPS 2400A–107, Operation 3-6 GUPS 2400A–107 Operation Manual 3. To turn OFF the output, press the OUTPUT ON switch again; the switch has a alternating ON/OFF action. The unit will shut down (with no AC input present); the inverter and all control circuits will turn off. 3.8.1 Battery Care and Handling The battery used in the GUPS 2400A-107 requires proper storage and recharging to maintain reliability. During storage, the self-discharge of the battery results in a sulfate coating that builds up on the plates. This coating reduces the effective surface area of the plates which reduces the available

  • Operation GUPS 2400A–107 Operation Manual 3-5 3.7 3.8 Start-Up and Shutdown Sequences To run the GUPS 2400A-107 from an AC input, perform the following steps: 1. Turn on the AC input circuit breaker located on the front panel. 2. Wait approximately 10 seconds for completion of the start-up routines. During this time, the GUPS performs a self-test to assure proper functionality, an

  • Elgar GUPS 2400A–107, Contents 3.9 RS-232 Data Communications Port.................................................................3-7 3.9.1 Hardware Interface...............................................................................3-7 3.9.2 Software Interface................................................................................3-7 3.9.3 RS-232 Protocol...................................................................................3-8 3.9.4 Test Data Request Commands............................................................3-8 3.9.5 Elgar Terminal Interface (ETI) Data

  • Elgar GUPS 2400A–107, Operation 3-2 GUPS 2400A–107 Operation Manual TEMP A two-color LED that indicates an over-temperature condition within the GUPS. The LED is green under normal operating conditions and red when an over-temperature shutdown occurs. TEST A two-color LED that indicates the results of the internal self-test. The LED blinks while a self- test is in progress. When the test is complete, the LED turns green if the test is passed and red it the test is failed. Figure 3–1. GUPS 2400A-107 Control and Indicator Panel

  • Elgar GUPS 2400A–107, Installation GUPS 2400A–107 Operation Manual 2-7 The following notes apply to Table 2–2 and to the power cable definition: 1. The above figures are based upon insulated copper conductors at 25°C (77°F), two current carrying conductors in the cable plus a safety (chassis) ground. Columns 3 and 4 refer to "one way" ohms and IR drop of current carrying conductors (e.g., a 50-foot cable contains 100 feet of current carrying conductor). 2. Determine which wire gauge for the application by knowing the expected peak load current (I peak ),

  • Elgar GUPS 2400A–107, Installation 2-2 GUPS 2400A–107 Operation Manual When returning the instrument to Elgar, suitable shipping containers and packing material must be used. If the instrument needs to be shipped and proper packing material is not available, contact Elgar to provide containers and shipping instructions. 2.3 2.4 Installation The Model GUPS 2400A-107 is 7" (178 mm) high and is designed to be installed in a standard 19" (483 mm) wide cabinet enclosure or a transit case. Refer to Figure 2–1 through Figure 2–3 for information on outline and mounting dimensions. Air Intake and Exh

  • Installation 2-8 GUPS 2400A–107 Operation Manual 5. Derate the above wire gauge (use a heavier gauge) for an increased number of current carrying conductors. This offsets the thermal rise of bundled conductors. Number of Current Conductors Capability 3 to 6 80% Above 6 70% 6. The preferred insulation material is application dependent. Elgar recommends any flame reta

  • CONTENTS SECTION 1 GENERAL DESCRIPTION ...............................................1-1 1.1 Introduction...................................................................................................... 1-1 1.2 General Description......................................................................................... 1-1 1.3 Specific

  • Elgar GUPS 2400A–107, SECTION 2 2.1 Introduction INSTALLATION The Elgar Model GUPS 2400A-107 has been aligned, calibrated, and tested prior to shipment. The instrument is ready for immediate use upon receipt. However, the following checks should be made to ensure that the instrument was not damaged during shipment. CAUTION! The GUPS 2400A-107 weighs 75 pounds (34 kg) without the battery pack. The battery pack adds an additional 48 pounds (22 kg). A minimum two–person lift is required! WARNING Hazardous voltages are present when

  • Elgar GUPS 2400A–107, Operation GUPS 2400A–107 Operation Manual 3-11 3.9.6 Status Words The status words may be used to examine the current state of the GUPS 2400A-107, but are not meant to be used in applications that are time–critical such as AC line loss detection. The “Line Loss Detected” message sent from the GUPS 2400A-107 (refer to Section 3.9.7), or the AC Line Loss signal (relay contact closure) will have the quickest response time. 3.9.6.1 Status Word 1 Format Table 3–5 provides the bit position information and definition of the data in Status Word 1. Bit Name Def

  • Elgar GUPS 2400A–107, SECTION 4 4.1 Introduction MAINTENANCE This section contains general information about maintenance of the GUPS 2400A-107. There are no adjustments accessible to the user. WARNING Hazardous voltages are present when operating this equipment. Please read the SAFETY NOTICE on page iv prior to installation, operation, or maintenance. 4.2 4.3 4.4 Service Information Questions concerning the operation, repair or service of this instrument should be directed to the nearest Elgar representative or to the Elgar Service Department, Elgar Electronics Corporation, 9250 Brown Deer Road, San Diego, CA 92121-2294. Include the m

  • Elgar GUPS 2400A–107, Operation 3-16 GUPS 2400A–107 Operation Manual Pass/Fail System Self-Test (Status Word 2, Bit 9) The Pass/Fail System Self-Test status bit indicates the results of the last run system self test. A binary value of 1 indicates that the unit passed the last self-test, while a binary value of 0 indicates that the unit failed the last self-test. System Down (Status Word 2, Bit 10) The System Down status bit indicates that the unit is in shutdown mode. A binary value of 0 indicates that the unit is ope

  • Elgar GUPS 2400A–107, Operation 3-4 GUPS 2400A–107 Operation Manual If SHUTDOWN is asserted while the AC input is not present and the inverter is running from the battery, the output relay will open and output power will be turned off; the inverter and control circuits will also be shut down. After shutdown, the OUTPUT ON switch must be manually toggled to turn the output back on. RS-232 TRANSMIT/RECEIVE RS-232 transmit and receive for data communications. Refer to Section 3.9 for more information on RS-232 interface. OUTPUT CURRENT An AC voltage signal that is pro

  • Elgar GUPS 2400A–107, Operation 3-12 GUPS 2400A–107 Operation Manual 3.9.6.2 Status Word 1 Status Bit Condition Definitions The definitions of the conditions and usage of the bits in Status Word 1 are defined below. Over Temperature (Status Word 1, Bit 0) The Over Temperature status bit indicates that the thermostat internal to the GUPS 2400A-107 has exceeded its trip point. A binary value of 0 indicates normal operation, while a binary value 1 indicates that the thermostat sensor has exceeded its trip point value of 95ºC. Alarm Sense (Statu

  • Elgar GUPS 2400A–107, Operation GUPS 2400A–107 Operation Manual 3-13 Output Relay (Status Word 1, Bit 8) The Output Relay status bit indicates the state of the units output relay. A binary value of 0 indicates that the units output relay is open, while a binary value of 1 indicates that the output relay is closed. Impending Shutdown (Status Word 1, Bit 9) The Impending Shutdown status bit indicates the status of the battery of the unit. A binary value of 0 indicates more than 1 minute of back-up time is available or that the battery voltage is greater than 177 volts, while

  • Elgar GUPS 2400A–107, Operation GUPS 2400A–107 Operation Manual 3-15 3.9.6.4 Status Word 2 Status Bit Condition Definitions The definitions of the conditions and usage of the bits in Status Word 2 are defined below. Running on Battery (Status Word 2, Bit 0) The Running on Battery status bit indicates that the unit is operating on batteries. A binary value of 0 indicates that the unit is running on AC input, while a binary value of 1 indicates that the unit is running on battery. Status Word 2, Bit 1 Reserved. Inverter Keypress (Status Word 2, Bit 2) The Inverter Keypress status bit indicates that a front panel keypres

  • Elgar GUPS 2400A–107, General Description 1-2 GUPS 2400A–107 Operation Manual Battery Recharge Time: 4 hours to 90% full charge following discharge at 2400VA/1920W and 25°C Output Voltage: 115V, ±2% Output Frequency: 60Hz, ±0.1% Output Current: 20.9A(RMS) Output Distortion: 2% THD, maximum with linear load Output Power: 1920W with resistive load; 2400VA/1920W with a reactive load or a non-linear load Efficiency: 77% AC to Battery Crossover: 159V, maximum low-line voltage; 232V, minimum high-line voltage Battery to AC Crossover: 169V, maximum low-line voltage; 232V, minimum high-line voltage AC Input Voltage Unbalance: 7V (RM

  • Elgar GUPS 2400A–107, Operation 3-14 GUPS 2400A–107 Operation Manual 3.9.6.3 Status Word 2 Format Table 3–6 provides the bit position information and definition of the data in Status Word 2. Bit Name Definition 0 Running on Battery 0 = Running on AC 1 = Running on battery 1 Reserved 2 Inverter Keypress 0 = No Keypress Pending 1 = Inverter Keypress Pending 3 System Shutdown 0 = System Operating 1 = System Shutdown 4 Reserved — 5 Running on AC Line 0 = Running on Battery 1 = Running on AC Line 6 150% Overload Sense 0 = Normal Operation 1 = 150% Overload Detected 7 Float Timer Time-out 0 = Not Float Charging 1 = Float Timer Time-out 8 Wait to equalize 0 = No Equaliza

  • Elgar GUPS 2400A–107, Maintenance 4-2 GUPS 2400A–107 Operation Manual 4.5 Troubleshooting In the event that a problem arises during unit operation, refer to the guidelines listed in Table 4–1 to assist in determining the cause and to repair the unit as quickly as possible. Symptom Probable Cause Suggested Solution No indicators are illuminated. The AC line voltage is not present. Energize the input circuit breaker; press the OUTPUT ON pushbutton. All indicators are illuminated red. The battery module is unplugged. Op

  • Elgar GUPS 2400A–107, SECTION 3 3.1 3.2 3.2.1 Indicators OPERATION Introduction This section provides detailed information on the controls and indicators, input/output connections, start-up and shutdown sequences, battery operation, and the RS-232 data communications port. Control and Indicator Panel All controls and indicators for the GUPS 2400A-107 are located on the front panel of the unit. There are no operator adjustments inside the unit. Refer to Figure 3–1 for the location of the controls and indicators listed below. There are eight i

  • Elgar GUPS 2400A–107, Operation GUPS 2400A–107 Operation Manual 3-3 3.2.2 3.3 3.4 3.5 Pushbutton Switches OUTPUT ON A momentary pushbutton switch on the front panel that alternately turns the output power on and off. TEST A momentary push button switch on the front panel that initiates the internal self-test. ALARM SILENCE A momentary pushbutton switch on the front panel that silences the audible alarm. Circuit Breaker The AC input breaker is located on the front panel below the Control and Indicator Panel. It is turned ON by pushing in the actuator button, and it is turned OFF by pulling out the actuator button. Audible Ala

  • Operation 3-10 GUPS 2400A–107 Operation Manual 3.9.5 Elgar Terminal Interface (ETI) Data Request Commands The GUPS 2400A-107 RS-232 text data mode commands have been developed for use by a program running on a host computer. The ETI mode data request commands provide formatted responses of only the measured value data in a formatted form. Each of the ETI data

  • SECTION 1 1.1 Introduction 1.2 1.3 Specifications GENERAL DESCRIPTION The Elgar Model GUPS 2400A-107 is a 2400 VA Global Uninterruptible Power Supply (GUPS) that provides regulated 115 VRMS, 60 Hz output power at up to 20.9 Amps RMS load current. The GUPS 2400A-107 accepts 3-phase AC input line voltages from 159V to 232V at frequencies from 370 Hz to 430 Hz. A battery back

Related Products and Documents (UPS):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 NETGEAR DG834Gv3 - 54 Mbps Wireless ADSL Firewall Modem Specifications netgear/dg834gv3-54-mbps-wireless-adsl-firewall-modem-YPG.pdf 20 Feb 2023 2
2 Canon PIXMA MX350 Network setup manual canon/pixma-mx350-5TC.pdf 30 Oct 2022 17 0.48 Mb
3 RCA F25442 Operation & user’s manual rca/f25442-RR4.pdf 05 Sep 2022 64 2.75 Mb
4 Sony PCV-RX301 Software manual sony/pcv-rx301-Z8D.pdf 24 Apr 2023 96 0.85 Mb
5 Tiger ED 9-009-03 Instruction manual tiger/ed-9-009-03-D45.pdf 16 Nov 2022 12 6.41 Mb
6 Samson QKICK Owner's manual samson/qkick-7I8.pdf 18 Aug 2022 8 0.95 Mb

Similar Resources:

  • Hewlett Packard Enterprise

    R/T2200 G5

    (35 pages)
    HPE R/T2200 G5 UPS, R/T3000 G5 UPS, and ERM User Guide Abstract This document is for the person who installs, administers, and troubleshoots power products. Hewlett Packard Enterprise assumes you are qualified in the servicing of high-voltage equipment and trained in recognizing hazards in products with hazardous energy levels. Part Number: 881628-001a June …
  • Acumentrics

    Rugged-UPS 1252 Series

    (31 pages)
    Operator’s Guide for Rugged-UPSTM 1252 Series 91-0120 Rev. B 1 © Acumentrics Corporation 2007-2008 1252 Rugged-UPS Series …
  • HP

    2700

    (4 pages)
    InstalaceInstallationInstallatieAsennusΕγκατάστασηTelepítésInstalasiInstalleringInstalacjaInstalaçãoInstallInstallationInstallationInstallazioneInstalaciónУстановкаInstallationKurulum© 2006 Hewlett-Packard Development Company, L.P.www.hp.com12*Q5985-90902**Q5985-90902*Q5985-90902 …
  • GE

    VH UL series

    (25 pages)
    Critical Power User Manual Uninterruptible Power Supply GE Consumer & Industrial SA General Electric Company CH – 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 52 52 www.gecriticalpower.com …
  • Toshiba

    G9000 SERIES

    (61 pages)
    Part # 98485-002December 2019Manufactured in the USA© Copyright 2019 TOSHIBA International Corporation All rights reserved.G9000 SERIESSCiB Energy Storage SystemINSTALLATION AND OPERATION MANUAL …
  • CyberPower

    649532009237

    (2 pages)
    4241 12th Ave E #400, Shakopee, MN 55379 • 1-877-297-6937 • www.CPSww.com Model #: CP900AVR UPC: 649532009237 MSRP: $129.99 The AVR Series CP900AVR UPS offers advanced power protection in a sleek and rugged tower. Automatic Voltage Regulation (AVR) ensures that all your electronics are receiving clean and stable AC power. Designed for mid-level …

Comments, Questions and Opinions: