Mircom FA-102T Installation And Operation Manual

Mircom FA-102T Manual Online:

3.5, 2303 votes
Mircom FA-102T User Manual
Mircom FA-102T User Guide
Mircom FA-102T Online Manual

Text of Mircom FA-102T User Guide:

  • Mircom FA-102T, FA-102T Installation and Operation Manual 9 Figure 6: Alarm and trouble relay contacts and remote annunciation wiring instructions Auxiliary common alarm relay contacts 28VDC, 3A (resistive) Common trouble relay contacts 28VDC, 3A (resistive) Cut JW3 for N.O. Cut JW4 for N.C. N.O. C N.C. TB2 TRL TRB A.C. ON 24V+ 24VDC, 250 mA max. 24VDC, 50 mA max. unsupervised unsupervised 24VDC, 50 mA max. 1.5K 1.5K 1.5K remote trouble LED (amber) buzzer LED (green) remote trouble remote AC ON

  • Mircom FA-102T, FA-102T Installation and Operation Manual 7 Figure 3: Detection and signal wiring Legend Pull Station Smoke Detector Heat Detector Bell F FS R Alarm threshold current is 21 mA. Maximum loop resistance is 100 ohms. ELR 3.9K 1/2W F S R TB2 Detection zone 1 F F ELR 3.9K 1/2W Signal zone Detection zone 2 + - + - 22VDC 3mA STBY 5mV ripple 50 mA max. alarm 22VDC 3mA STBY 5mV ripple 50 mA max. alarm 24VDC unfiltered 1.25A max. F S R ELR 3.9K 1/2W

  • Mircom FA-102T, Sequence of Operation 4 Sequence of Operation Refer to Figure 2 on page 6 for the location of indicators and controls. Normal All indicators are normally OFF except for the green A.C. On LED. Alarm A red zone alarm LED will illuminate steadily for an incoming alarm. Signal Silence If the 60 second signal silence inhibit is selected, the signal cannot be silenced for 60 seconds after an alarm initiation. Once the 60 seconds have expired, pushing the signal silence switch to the right will silence all the bells and horns. Once the

  • Mircom FA-102T, 5 Figure 1: Backbox and flush trim mounting details 13 3 / 4 ” 12 3 / 4 ” 1 11 / 16 ” Optional flush mounting trim (model FA-102TR) Four 7/ 32 ” dia. 2 7 / 8 ” 7 1 / 8 ” 1 1 / 4 ” 10 3 / 8 ”

  • Mircom FA-102T, Canada 25 Interchange Way Vaughan, ON L4K 5W3 Tel: 905-660-4655 Fax: 905-660-4113 © Mircom 2009 Printed in Canada Subject to change without prior notice www.mircom.com U.S.A. 4575 Witmer Industrial Estates Niagara Falls, NY 14305 Tel: 1-888-660-4655 Fax: 1-888-660-4113

  • Mircom FA-102T, FA-102T Installation and Operation Manual 3 Remote Annunciation Annunciation outputs are provided for remote trouble indicator and buzzer. Refer to Figure 6 on page 9 for wiring instruction. A.C. Power and Batteries The A.C. power is connected to the terminal block above the transformer. Use Gel Cell or Sealed Lead-Acid type of batteries only. Connect the batteries after power up. Use 24V 4AH batteries for 24 hours standby and 5 or 30 minutes of alarm. For greater accuracy, use “Appendix B: Battery Calculations (Selection Guide)” on page 14. ELECTRICAL RATING: 120V, 60Hz / 240V, 50Hz Tr

  • Mircom FA-102T, List of Figures ii List of Figures Figure 1: Backbox and flush trim mounting details .............................................................. 5 Figure 2: Circuit Board Layout ............................................................................................. 6 Figure 3: Detection and signal wiring .................................................................................. 7 Figure 4: Wiring table for detection zone ........................................................

  • Wiring Tables and Information 8 Wiring Tables and Information Figure 4: Wiring table for detection zone Figure 5: Wiring table for bells and horns Signal circuits are rated for 1.25 amperes each. Wire Gauge Maximum Wiring Run to Last Device (ELR) (AWG) ft. m 22 2990 910 20 4760 1450 18 7560 2300 16 12000 3600 14 19000 5800 12 30400 9200 Note: Maximum loop resistan

  • Mircom FA-102T, FA-102T Installation and Operation Manual 15 Warranty & Warning Information Warning Please Read Carefully Note to End Users: This equipment is subject to terms and conditions of sale as follows: Note to Installers This warning contains vital information. As the only individual in contact with system users, it is your responsibility to bring each item in this warning to the attention of the users of this system. Failure to properly inform system end-users of the circumstances in which the system might fail may result in over-reliance upon the system. As a result, it is imperative that you properly inform each customer for whom you install the system of the possible forms of failure.

  • Mircom FA-102T, Canada 25 Interchange Way Vaughan, ON L4K 5W3 Tel: 905-660-4655 Fax: 905-660-4113 © Mircom 2006 Printed in Canada Subject to change without prior notice www.mircom.com FA-102T Fire Alarm Control Panel LT-514 Rev.7 December 2009 Installation and Operation Manual Advanced Life Safety Solutions Advanced Life Safety Solutions A.C. ON SIGNAL SILENCED 2 1 U.S.A. 60 Industrial Parkway Cheektowaga, NY 14227 Tel: 1-888-660-4655 Fax: 1-888-660-4113

  • Wiring 2 DIP switch DSW1 is used to set the preferred signal zone 1 output, the signal silence inhibit, and the common trouble flash rate. The default output for the signal zone is temporal code. • Temporal Code: 3 rounds of 0.5 second ON, 0.5 second OFF, then 1.5 second pause. • Steady: Signal on continuously. Wiring Detection Zone The system has two detection zones. Refer to F

  • Mircom FA-102T, Warranty & Warning Information 18 number of attempts will be limited to a replacement of the product, as the exclusive remedy for breach of warranty. Disclaimer of Warranties This warranty contains the entire warranty and shall be in lieu of any and all other warranties, whether expressed or implied (including all implied warranties of merchantability or fitness for a particular purpose) And of all other obligations or liabilities on the part of Mircom neither assumes nor authorizes any other person p

  • Mircom FA-102T, Warranty & Warning Information 16 •Automatic Alarm Initiating Devices Smoke detectors, heat detectors and other alarm initiating devices that are a part of this system may not properly detect a fire condition or signal the control panel to alert occupants of a fire condition for a number of reasons, such as: the smoke detectors or heat detector may have been improperly installed or positioned; smoke or heat may not be able to reach the alarm initiating device, such as when the fire is in a chimney, walls or roof

  • Mircom FA-102T, 6 Figure 2: Circuit Board Layout ALARM RELAY NO C NC RELAY TRL TRB A.C. ON 24V + 1 + - JW3 JW4 A.C. ON TRBL. SIG. SIL. BATT. GND TRANSFORMER P1 P2 P3 BATTERY P4 + - SIG.1 F1 2A BATTERY A.C. 2A F2 COM (-) JW2 JW1 1 + - TB2 2 + - TRBL. ALARM ZONE 1 TRBL. ALARM ZONE 2 AUX. TRBL ON DSW1 DIP SWITCHES 18 MD-733 DETECTION ZONE BUZZER SIL. REMOTE ANNUNCIATION ZONE 1 SIL. SIGNAL RESET ZONE 2 SIL.

  • Mircom FA-102T, FA-102T Installation and Operation Manual 17 •Security and Insurance Regardless of its capabilities, an alarm system is not a substitute for property or life insurance. An alarm system also is not a substitute for property owners, renters, or other occupants to act prudently to prevent or minimize the harmful effects of an emergency situation. IMPORTANT NOTE: End-users of the system must take care to ensure that the system, batteries, telephone lines, etc. are tested and examined on a regular basis to ensure the

  • Mircom FA-102T, Appendix B: Battery Calculations (Selection Guide) 14 Appendix B: Battery Calculations (Selection Guide) Use the form below to determine the required batteries. Total Current Requirement ALARM (B)______ Amps. Battery Capacity Requirement ( [STANDBY (A) ______ ] X [(24 or 60 Hours) ________ ]) + ([ALARM (B) ______ ] X [ ♣ Alarm in Hr.] ________) = (C) ________AH Battery Selection Multiply (C) by 1.20 to derate battery. * Assuming three Initiating Circuits in alarm. ♣ Use 0.084 for five minutes of alarm or 0.5 for thirty minutes of alarm as a multiplier figure. ♦ Using the MIR-525/U 2-wire smoke detector. See Appendix "A", for other available s

  • Mircom FA-102T, Appendix A: Compatible Devices 10 Appendix A: Compatible Devices Underwriters’ Laboratories of Canada (ULC) Canadian 2-Wire Smoke Detector Control Panel Notes: • Reset time, hold for five seconds minimum. • Whether mixing different models of compatible smoke detectors, or using the same model on the same Circuit, total standby current of all detectors must not exceed 3 mA. Make Model / Base Make Model / Base Make Model / Base Mircom Cerebrus Pyrotronics Fenwal MIR-525 D1-2 PSD-7131/70-201000-001 MIR-525T D1-3/DB-3S PSD-713

Related Products and Documents (Fire Alarms):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 Britax ROADSTER 2 IN 1 WALKER Manual  britax/roadster-2-in-1-walker-3VQ.pdf 25 May 2023 6 1.51 Mb
2 U-Line CLR2160 Features & benefits u-line/clr2160-1D1.pdf 23 Mar 2023 2 0.63 Mb
3 Alpine CVA-1005 Owner's manual alpine/cva-1005-A97.pdf 17 Apr 2023 239 2.68 Mb
4 Epson C11CA49201 - WorkForce 310 Color Inkjet Brochure & specs epson/c11ca49201-workforce-310-color-inkjet-FS2.pdf 23 Aug 2023 2 0.92 Mb
5 Fellowes POWERSHRED C-320C Specifications fellowes/powershred-c-320c-889.pdf 03 Jun 2023 2 0.45 Mb
6 Crestron QM-AMP3x80 Series Operation manual crestron/qm-amp3x80-series-K7L.pdf 08 Nov 2023 32 3.06 Mb

Similar Resources:

  • E2S

    GNExCP7-PT-S

    (8 pages)
    _______________________________________________________________________________________________________________________________ European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH Tel: +44 (0)208 743 8880 [email protected] www.e-2s.com Fax: +44 (0)208 740 4200 Document No. D202-00-201-IS_Issue_1 07-05-2019 …
  • EMS

    FireCell Radio Hub

    (4 pages)
    POWERFAU LTSYSTEMFAU LTPOWERFAU LTFIREFire Alarm ControlRadio HubControl PanelRadio ClusterCommunicator (RCC)230V AC230V ACWireless Diagnostics Quick Start Guide Iss 3 - MK252 AJMwww.emsgroup.co.ukWIRELESS DIAGNOSTICSQUICK START GUIDE …
  • Funke+Huster Fernsig

    2014/2

    (12 pages)
    Feuermelder / Fire alarmHandauslöseeinrichtung und Stopptaster / Manual triggering solution and Stop Device• Bereiche der Zone 1 und 2,21 und 22• Schutzklasse II und III• Schutzart IP 66 / IEC 60529• Temperaturbereich: -55ºC bis +70ºC oder +65ºC• Kunststoffgehäuse: glasfaserverstärktes Polyester• Alle Metallteile aus V4A-Edelstahl• Robust …
  • UniPOS

    FD7201

    (2 pages)
    CONVENTIONAL LINE-MONITORING MODULEType FD7201Instruction Manual 01-7201-11-051293TECHNICAL DATASupply voltage of the signal loop (15-30)V DCCurrent of the signal loop in Duty mode (4-8) mACurrent of the signal loop in Fire condition in the built-in detector 5 mA at 24 VDCCurrent of the signal loop in Fire condition in a detector integratedin the conventiona …
  • Notifier

    NAM-232

    (2 pages)
    DN-5331 • 08/19/04 — Page 1 of 2GENERALThe NAM-232 Network Adapter Module functions as an in-terface between the AFP-200, AFP-300, and AFP-400 FireAlarm Control Panels and the NOTI•FIRE• NET™. Thecontrol panels each consume a single-node address on thenetwork. The NAM-232 interfaces to the control panelsthrough the EIA-232 serial communications por …
  • Teletek electronics

    SensoIRIS BSOU IS

    (2 pages)
    SensoIRIS BSOU ISSensoIRIS BSOU IS е адресируема пожарна основа в самостоятелен корпус с вградена сирена и модул изолатор. Пожарната основа е предназначена за използване в пожароизвестителни алармени системи, п …

Comments, Questions and Opinions: