SharpEye 20/20CTIN User And Maintenance Manual
|
SharpEye 20/20CTIN, Spectrex Inc. - SharpEye TM CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005 III L IST OF FIGURES Figure 1: CCTV Model Flame Detector............................................................................. 4 Figure 2: Flame Detector Assembly - Outline Drawing .................................................... 5 Figure 3: Horizontal and Vertical Fields of View.............................................................. 8 Figure 4: Indication LEDs....................................................................................
SharpEye 20/20CTIN, Spectrex Inc. - SharpEye TM CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005 4 After careful investigation, three channels were selected which, when operating jointly, provide optimal fire detection characteristics: Channel 1: 4.2 µ - 4.6 µ Fire - the CO 2 peak Channel 2: 4.0 µ - 4.2 µ Eliminates false alarms from high temperature sources. Channel 3: 4.8 µ - 5.2 µ Eliminates false alarms from flickering of background radiation. Most IR sources, which create misleading IR alarm stimuli, including the sun, incandescent an
SharpEye 20/20CTIN, Spectrex Inc. - SharpEye TM CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005 16 4.4 Built In Test A. General The detectors’ Built In Test (BIT) checks the following: • Electronics circuitry • Sensors • Window cleanliness The detector can be set to perform the BIT automatically and manually or manually only. B. Principles If the result of a BIT is the same as the current status of the detector (NORMAL or BIT FAULT), the detector's status is unchanged. If the result of a BIT differs from the current sta
SharpEye 20/20CTIN, Spectrex Inc. - SharpEye TM CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005 9 3.2 False Alarms Prevention The detector will not provide an alarm or a warning signal as a reaction to the radiation sources specified below. Notes: IAD = Immune at Any Distance. All sources are chopped from 0 to 20Hz. Table 4: Immunity To False Alarm Sources Radiation Source Immunity Distance ft(m) Sunlight IAD Indirect or reflected sunlight IAD Vehicle headlights (low beam) conforming to MS53023-1 IAD Vehicle IR lights (low beam) conforming to MS53024-1 IAD Incandescent frost
SharpEye 20/20CTIN, Spectrex Inc. - SharpEye TM CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005 1 1. Scope 1.1 Product Overview The SharpEye CCTV Model Flame Detector (20/20CTIN and 20/20CTIP) is a self- contained, triple-spectrum, optical flame detector that incorporates a video color camera. The detector's IR sensors and spectral band pass filters have been selected to ensure the greatest degree of spectral matching to the radiant energy emissions of fire and the lowest degree of matching to non-fire stimuli. The color video camera enables the user to investigate the monitored area
SharpEye 20/20CTIN, Spectrex Inc. - SharpEye TM CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005 2 1.2 Document Overview This manual describes the detector and its features and provides instructions on the installation, operation and maintenance. This manual is divided into separate chapters as follows: Chapter 1. Scope - a general introduction and overview of the product and the Manual, with a brief description of its content. Chapter 2. Technical Description - the detector’s theory of operation. Chapter 3. Performance - the detector features and capabilities. Chapter
SharpEye 20/20CTIN, Spectrex Inc. - SharpEye TM CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005 45 Appendix C – RS-485 Communication Network Using the RS-485 network capability of the IR3 detector and additional software it is possible to connect up to 32 detectors in an addressable system with 4 wires only (2 for power & 2 for communication). Using repeaters, the number of detectors can be much larger (32 detectors for each repeater) up to 247 on the same 4 wires. When using the RS-485 network it
SharpEye 20/20CTIN, Spectrex Inc. - SharpEye TM CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005 35 7.5 Safety Precautions After Powering-up, the detector requires hardly any attention in order to function properly, but the following should be noted: 1 Follow the instructions in the manual and refer to the drawings and specifications issued by the manufacturer. 2 Do not expose the detector to radiation of any kind unless required for testing purposes. 3 Do not ope
SharpEye 20/20CTIN, Spectrex Inc. - SharpEye TM CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005 44 CCTV Wire Type The wire for the video picture must be Twisted Pair Wire. Network Wiring UTP Wire Gauge 24 AWG or thicker Category Type 2, 3, 4, 5 or better Impedance 100±200 ohms DC Loop Resistance 52 ohms per 1,000ft (300m) Differential Capacitance 19pF/ft max The Twist Pair must be connected to a PASSIVE or ACTIVE receiver depending on the length cable from the CCTV to the receiver. 0 - 1000 ft (300m) Require PASSIVE receiver 660 - 3300 ft (200m - 1000m) Require ACTIVE receiver The connection from the receiver should be
SharpEye 20/20CTIN, Spectrex Inc. - SharpEye TM CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005 30 • 4-20mA Output (Terminal Numbers 11, 12): Terminal Numbers 11 and 12 are used for analog, 4-20mA current output as specified in paragraph 4.e Terminal No. 11 - output Terminal. Terminal No. 12 - input Terminal (see appendix B for more details) • RS-485 (Terminal Numbers 13, 14): Terminal Numbers 13 and 14 are used for communication network as specified in appendix C. Terminal No. 13 - positive (+) lead. Terminal No. 14 - negative (-) lead. Figure 10: Termin
SharpEye 20/20CTIN, Spectrex Inc. - SharpEye TM CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005 18 5.Technical Specifications 5.1 Electrical Specifications A. Operating Voltage: 18-32 VDC B. Power Consumption : Max. 150mA in Stand-by Max. 200mA in Alarm C. Electric input protection: The input circuit is protected against voltage- reversed polarity, voltage transients, surges and spikes according to MIL- STD-1275A. D. Electrical Interface: Figure 6: Electrical Interface
Spectrex Inc. - SharpEye TM CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005 52 Figure 19: IR3 Detector Target Point Follow these instructions to simulate a fire: 1. Aim the Fire Simulator towards the detector’s “Target Point”. 2. For testing keep a distance of at least 20 inches (50cm) from the detector. 3. Press the
Spectrex Inc. - SharpEye TM CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005 24 6.3 Preparations for Installation Installation should comply with NFPA 72E, as applicable to flame detectors as required. The detectors can be installed with the use of general-purpose common tools and equipment. 1 Verify the appropriate Purchase Order. Rec
SharpEye 20/20CTIN, Spectrex Inc. - SharpEye TM CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005 11 4.2 Output Signals The detector controls the following outputs: • Alarm relay • Accessory relay • Fault relay • 4-20mA current output • RS-485 communication The detector can be in one of the following states. Normal: The detector is functioning normally. BIT: The detector performs a Built-In-Test. Warning: Fire detected - changed to warning – pre-alarm state.
SharpEye 20/20CTIN, Spectrex Inc. - SharpEye TM CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005 53 Specifications Mechanical Explosion Proof Enclosure: NFPA (designed to meet) Class I, Division 1 & 2 Groups B, C and D Class II, Division 1 & 2 Groups E, F, and G ATEX EX II2G, NEMKO 02ATEX255 EExd IIB T5 50˚C per En 50-014 & EN50-018 Electrical Power: 8 VDC Max. 6 x Rechargeable 1.2 VDC NiCad Batteries Current: 2.5A Avg. Charge: 40
SharpEye 20/20CTIN, Spectrex Inc. - SharpEye TM CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005 6 3. Performance 3.1 Detection Sensitivity A. Flame Detection sensitivity is the maximum distance at which the detector will reliably detect a specific size of fire & typical type of fuel (standard fire). Standard Fire: A 1ft x 1ft (0.3m x 0.3m) Gasoline pan fire with max. wind speed of 6.5 ft/sec (2 m/sec). Sensitivity Ranges: The detector has four user selectable sensitivity ranges. For each range there are two response levels. 1. WARNING (Pre-alarm) 2. ALARM The detection distance, for the WARNING level, is app
SharpEye 20/20CTIN, Spectrex Inc. - SharpEye TM CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005 32 6.8 Operation Mode When wiring is completed the operational mode can be selected. Mode selection is achieved through RS-485 using a PC with Spectrex Host software. Refer to TM784050. Programmable Function: Modes of operation are programmable with a PC or Handheld unit according to the selection table in Paragraph 4.3.1 and Refer to TM 784050. Refer to here in 4.3.1 etc. Address: The detector has the capability of acting as an addressable device. The detector provides 247 addresses, which can be used by the RS-485 communications link
SharpEye 20/20CTIN, Spectrex Inc. - SharpEye TM CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005 13 4.3 Mode Selection The setup screen allows viewing and programming of the detector functions. Figure 5: CCTV Screen Setup
SharpEye 20/20CTIN, Spectrex Inc. - SharpEye TM CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005 7 Other fuels The detector will react to other types of fires as follows: Pan Fire Size: 1ft x 1ft (0.3m x 0.3m) Maximum Wind Speed: 6.5 ft/sec (2 m/sec) Maximum Response Time: 10 sec Table 2: Response Sensitivity Ranges Type Of Fuel % Of Max. Distance at Each Sensitivity Range Gasoline 100% N-Heptane 100% Alcohol 95% 75% JP4 75% Kerosene 75% Diesel Fuel 70% M
SharpEye 20/20CTIN, Spectrex Inc. - SharpEye TM CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005 II 7.4 F UNCTIONAL TESTING...................................................................................33 7.4.1 Manual BIT Test .................................................................................34 7.4.2 Testing with fire simulator ...................................................................34 7.5 S AFETY PRECAUTIONS .................................................
SharpEye 20/20CTIN, Spectrex Inc. - SharpEye TM CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005 51 Appendix E - Long Range IR3 Fire Simulator Figure 18: Fire Simulator Product Description The SharpEye IR3 Long Range Fire simulator 20/20-310 is designed specifically for use with the IR3 flame detectors. The Fire Simulator emits IR radiation in a unique sequential pattern corresponding and recognizable by the IR3 detector as fire. This allows the IR3 detectors to be tested under real fire conditions without the associated risks of an open flame. There is a specially designed beam collimator model number 20/20-190 used for extended
Spectrex Inc. - SharpEye TM CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005 29 6.7 Terminal wiring (See Fig. No.10 and No.11.) The detector contains a Terminal Board consisting of two (2) terminal blocks (Item 4). The left terminal block is labeled 1 to 7, the right terminal block is labeled 8 to 14. The following describes the fun
SharpEye 20/20CTIN, CCTV Model Flame Detector Model 20/20CTIN-CTIP User and Maintenance Manual TM 788100, Rev. A January 2005 ATEX Approved Ex II 2G EExd IIB + H 2 T5 EExde IIB + H 2 T5 UL Approved Class I, Groups C and D Gost R Approved 1ExdIIBT5/H 2 218 Little Falls Rd., Cedar Grove, NJ 07009 USA; Phone: +1 (973) 239 8398 Fax: +1 (973) 239 7614 Web-Site: www.spectrex.net ; Email: [email protected]
Kidde 123I Smoke Alarm Owner's manual
123I |
First Alert SA302 Smoke Alarm Operation & user’s manual
SA302 |
Zeta Alarm Systems ZTZM/4 Smoke Alarm Operation & user’s manual
ZTZM/4 |
Visonic MCT-425 Smoke Alarm Brochure
MCT-425 |
LST HT-11003 Smoke Alarm Specification sheet
HT-11003 |
SharpEye 20 Smoke Alarm User and maintenance manual
20 |
Ei Electronics RadioLINK Relay Module Ei428 Smoke Alarm Instruction manual
RadioLINK Relay Module Ei428 |
Greenheck DH100ACDCLP Smoke Alarm Specifications
DH100ACDCLP |
# | Manufacturer | Model | Document Type | File | Updated | Pages | Size |
---|---|---|---|---|---|---|---|
1 | MartinLogan | Mikros 90 | Operation & user’s manual | martinlogan/mikros-90-3A7.pdf | 24 Nov 2022 | 28 | |
2 | Philips | 193V5 | Operation & user’s manual | philips/193v5-556.pdf | 07 Sep 2022 | 35 | |
3 | Lenovo | Aptiva | Benutzerhandbuch | lenovo/aptiva-3KT.pdf | 07 Nov 2023 | 218 | |
4 | Panasonic | KX-TGP500 | Administrator's manual | panasonic/kx-tgp500-J1I.pdf | 04 Oct 2022 | 284 | |
5 | Salton | WC22 | Owner's manual | salton/wc22-NGD.pdf | 01 Nov 2022 | 8 | 0.14 Mb |
6 | Indesit | FIU20 | Instructions for installation and use manual | indesit/fiu20-G8U.pdf | 30 Jun 2022 | 36 |
Visonic
MCT-427 is a fully supervised wireless heat and photoelectric smoke detector that is compatible with PowerMax® home security systems and other Visonic PowerCode™ wireless receivers. By sensing rapid temperature changes in areas where they may occur, such as kitchens or attics, MCT-427 activates an alarm when temperatures reach 50°C (122°F) and start in …
MCT-427(1 pages) |
Dyna-Glo
MODEL #DGY784BDP/DGY784BDP-DVERTICAL GAS SMOKERFrançais p. XXEspañol p. XXFrançais p. 27Español p. 53ATTACH YOUR RECEIPT HERESerial NumberPurchase DateQuestions, problems, missing parts? Before returning to your retailer, call our customer service department at 1-877-447-4768, 8:30 a.m. – 4:30 p.m. CST, Monday – Friday or log on to customerservice@gh …
DGY784BDP-D(81 pages) |
Dicon
SMOKE ALARMS& HEAT ALARMSA: GUIDANCE ON INSTALLATIONWARNING: Wiring should be installed by a qualified electrician in accordance with BS7671.Permanent connection to the fixed wiring of the building should be made in a suitable junction box.This alarm must not be exposed to dripping or splashing. Connect the alarm as late as possible inan installation, pa …
650M(2 pages) |
System Sensor
D100-101-00 1 I56-2806-003R2151/2151T Low ProfilePhotoelectronic Plug-in Smoke DetectorsINSTALLATION AND MAINTENANCE INSTRUCTIONS 3825 Ohio Avenue, St. Charles, Illinois 601741-800-SENSOR2, FAX: 630-377-6495www.systemsensor.comBefore Installing Please thoroughly read the System Sensor manual A05-1003, Applications Guide for System Smoke Det …
2151(4 pages) |
Mercury
www.avslgroup.com 350.129UK User Manual Photoelectric Smoke Detector with 10 Year Sealed Battery Order ref: 350.129UK User Manual An easy to use photoelectric smoke alarm that needs no battery maintenance during its 10 year lifespan. Simply engage t …
350.129UK(2 pages) |
Edwards Signaling
Installation Sheet 18AUG05 P/N: 3100686 REV: 2.0 SuperDuct Four-Wire Smoke Sensor (RJ-45 version) 1 / 3 SuperDuct Four-Wire Smoke Sensor (RJ-45 version) Product description The SuperDuct four-wire smoke sensor coupled with a compatible controller make up a SuperDuct four-wire duct smoke detector. The sensor sends an alarm signal to the controller whe …
SuperDuct TSD-SJ(3 pages) |
Colortrac Scanner Flatbed 24120Guide: Colortrac Flatbed 24120 (N2M6YB, Upd.12/01/2024) Flatbed 24120, 13 |
Vivanco Other LARGE TILT WALL BRACKET - PROGRAMMINGOther Package contents (Vivanco LARGE TILT WALL BRACKET - PROGRAMMING) LARGE TILT WALL BRACKET - PROGRAMMING, 4 |
Remington Heater Sun-Stream SSR-808R-IHR#7ITAP2 Sun-Stream SSR-808R-IHR: Remington Heater Owner Documentation Sun-Stream SSR-808R-IHR, 12 |
Philips DVD Player DVP3111/12DVD Player PDF Operation & user’s manual DVP3111/12, 19 |
Gionee Cell Phone S90Gionee Cell Phone S90 Operation & user’s manual S90, 21 |
Danby Refrigerator Designer DCR432BLRefrigerator #5EEYBO Designer DCR432BL, 23 |
Letus Lenses 35 extremeLenses PDF Operation & user’s manual 35 extreme, 16 |
minkaAire Fan KOLA-XLGuide: minkaAire KOLA-XL (BU4X2O, Upd.16th Dec 2023) KOLA-XL, 24 |
Coby Speakers CS-P46Coby CS-P46 Speakers Specifications CS-P46, 1 |
Sony Camcorder Accessories MPK-TRV3PDF User Manual (@374L7J), Sony MPK-TRV3 Camcorder Accessories (Monday 28-08-2023) MPK-TRV3, 92 |
Sylvania VCR 6220VB#84WRXF: 6220VB VCR Owner's manual 6220VB, 16 |
Kiev Camera Digital Camera 88 CM88 CM Instruciton for use - 4CBDNO 88 CM, 19 |