Text of SILENT KNIGHT INTELLIKNIGHT 5808 User Guide:

  • SILENT KNIGHT INTELLIKNIGHT 5808, IntelliKnight 5808 Installation Manual 6-18 151274 System Options (cont.) Misc. Options 3 Alarm Verification time Enter time from 1 to 250 seconds *60 Seconds Section 7.6.6.1 Plex Door Y (Enabled) Disabled Section 7.6.6.2 N (Disabled) DST Start Select week: 1st, 2nd, 3rd, 4th or Last Select month Section 7.6.4.3 and 7.6.6.3. See also DST settings in Misc. Options 1, above. DST End Edit Banner Internal Message Section 7.6.7 Custom Message Edit Line 1 Edit Line 2 JumpStart AutoPrg No Section 7.7 Yes Computer Account Computer Account # *123456 Section 7.8Computer Access Code *0 Computer Phone # Up to 24 digits Menu Options/Defaults Comments

  • SILENT KNIGHT INTELLIKNIGHT 5808, IntelliKnight 5808 Installation Manual 1-4 151274 1.4 How to Contact Silent Knight If you have a question or encounter a problem not covered in this manual, contact Silent Knight Technical Support at 800-328-0103 (or 763-493-6455). To order parts, contact Silent Knight Sales at 800-446-6444 (or 763-493-6435).

  • SILENT KNIGHT INTELLIKNIGHT 5808, Programming 151274 7-39 A screen similar to the one shown in Figure 7-18 will display. Figure 7-18 Internal Banner Message 6. Press the or arrow to select "Custom", then press . A screen similar to the one shown in Figure 7-19 will display. Figure 7-19 Custom Banner Edit Screen 7. Select each character of a word by pressing the or arrow, then press to move to the next character. 8. When word or sentence is complete press to move to line two of the custom banner. Repeat step 7 and 8.

  • SILENT KNIGHT INTELLIKNIGHT 5808, IntelliKnight 5808 Installation Manual 7-20 151274 6. Enter the number of the point you wish to edit, then press . 7. Select the type of device by pressing the or arrows. Refer to Table 7-4 under col- umn heading "Type Selection" for a list of choices. Table 7-4: Point Programming Module Type Type Selection Function Latching Option Comments SLC Loop UNUSED DETECTOR PHOTO ION HEAT PHOT DUCT ION DUCT 2WIRE SMK SUP DET SUP PHOTO Latching Non LatchingSUP ION SWITCH MAN_PULL Use this switch type for manual pull stations. This input is always latched. The switch can clear only when an alarm is reset. This switch type has the highest priority; it over

  • SILENT KNIGHT INTELLIKNIGHT 5808, Compatible Devices 151274 A-13 Wheelock con’t E60  Speaker E60-24MCW Speaker/Strobe E60-24MCHW Speaker/Strobe E60-24MCC Speaker/Strobe E60-24MCCH Speaker/Strobe E70  Speaker E70-MCW Speaker/Strobe E70-24MCWH Speaker/Strobe E70-24MCC Speaker/Strobe E70-24MCCH Speaker/Strobe E70-241575W Speaker/Strobe MB-G6-24 Motor Bell MB-G10-24 Motor Bell MB-G6-12 Motor Bell MB-G10-12 Motor Bell MIZ-24-R Mini-Horn MT-12/24-R Multitone Horn MT4-12/24 Multitone Horn E70-241575W Speaker/Strob

  • SLC Device Installation 151274 5-7 5.5.2 SLC Devices with Dip Switches Input and relay module addresses are set using the dip switches on the module board. The chart below shows the available addresses. For example, to select address 3, place dip switches 1 and 2 in the up position. The range of valid addresses is 1-127. 0 is an invalid address. Figure 5-6 SLC Device Addressi

  • SILENT KNIGHT INTELLIKNIGHT 5808, Control Panel Installation 151274 4-7 These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet, regardless of gauge used. (The formula used to generate this chart is shown in the note below). Note: The following formulas were used to generate the wire distance chart: Table 4-2: Wiring Distances Per Wire Gauge Using Copper Wire Wiring Distance: SBUS Modules to Panel Total Worst Case Current Draw (amps) 22 Gauge 18 Gauge 16 Gauge 14 Gauge 0.100 1852 ft. 4688 ft. * 6000 ft. * 6000 ft. 0.200 926 ft. 2344 ft. 3731 ft. 5906 ft. 0.300 617 ft. 1563 ft. 2488 ft. 3937 ft. 0.400 463 ft. 1172 ft. 1866 ft. 2953 ft. 0.500 370 ft. 938 ft. 1493 ft. 2362 f

  • SILENT KNIGHT INTELLIKNIGHT 5808, Compatible Devices 151274 A-9 Wheelock AH-12  Horn AH-24  Horn AH-12WP  Horn Weatherproof AH-24WP  Horn Weatherproof AMT-241575W Multi-Tone Horn Strobe AMT-24MCW  Mutli-Tone Horn Strobe AMT-241575W-NYC Multi-Tone Horn Strobe AMT-12/24  Multi-tone Horn AMT-12/24 NYC  Multi-tone Horn AS-121575W  Horn/Strobe NH-12/24  Horn AS-241575W Horn/Strobe AS-24MCC Horn/Strobe AS-24MCCH Horn/Strobe AS-24MCW Horn/Strobe AS-24MCWH Horn/Strobe Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type

  • SILENT KNIGHT INTELLIKNIGHT 5808, IntelliKnight 5808 Installation Manual 7-22 151274 7.5.2 Point Programming For Internal or External Power Module (5496) To program for an internal or external power module points, follow these steps: 1. Enter the installer code. 2. Press or to display the main menu. 3. Select for Program Menu. Display reads: Initializing Please wait . . . 4. Press to enter point menu. 5. Press the or arrows to select the desired module, then press . Refer to Section 6.5 for available choices. 6. Enter the number of t

  • SILENT KNIGHT INTELLIKNIGHT 5808, IntelliKnight 5808 Installation Manual 4-10 151274 4.5.1 Mounting the 5860 This section of the manual describes mounting the remote annunciator. The annunciator can be flush- or surface-mounted. Figure 4-9 shows the parts of the annunciator. Instructions for disassembling and mounting appear on the following pages. Figure 4-9 Annunciator Parts

  • SILENT KNIGHT INTELLIKNIGHT 5808, IntelliKnight 5808 Installation Manual 9-4 151274 Water flow switch disabled Disable Point Event pi Exp. ID SB Pnt # 1 571 Exp. ID Pnt # Supervisory/Tamper switch or supervisory duct dectector disabled Disable Point Event pi Exp. ID SB Pnt # 1 571 Exp. ID Pnt # Water flow switch alarm restore Restore Point Event pi Exp. ID SH Pnt # 3 113 Exp. ID Pnt # Water flow switch trouble restore Trouble Point Event pi Exp. ID SJ Pnt # 3 373 Exp. ID Pnt # Supervisory/Tamper switch or supervisory duct dectector trouble restore Trou

  • IntelliKnight 5808 Installation Manual A-6 151274 Gentex con’t ST24-60  Strobe ST24-75  Strobe ST24-110  Strobe ST24-1575  Strobe WGEC24-75W Weatherproof Horn/Strobe WGES24-75W  Weatherproof Strobe WGMS-24-X Horn/Strobe SSPKWR  Speaker SSPKWW  Speaker SSPK-15WR Speaker/Strobe SSPK-15WW Speaker/Strobe SSPK-15/75WR Speaker/Strobe SSPK-15/75WW S

  • SILENT KNIGHT INTELLIKNIGHT 5808, IntelliKnight 5808 Installation Manual 2-4 151274 4. The AC Loss Hours option must be set from 1-3 hours. 5. The Attempts to Report option must be set for 5. 2.2.3 Requirements for Local Protected Fire Alarm Systems At least one UL listed supervised notification appliance must be used. Minimum system requirements are one Silent Knight addressable initiating device. 2.2.4 Requirements for Remote Station Protected Fire Alarm Systems Minimum system requirements are one Silent Knight addressable initiating device and either a 5220, Keltron 3158 or the built-in Digital Alarm Co

  • SILENT KNIGHT INTELLIKNIGHT 5808, Introduction 151274 1-5 Limitations of Fire Alarm Systems Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer’s recommendations, State and local codes, and the recommendations contained in Guide for the Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emer

  • Control Panel Installation 151274 4-31 4.14.3 NFPA 72 Polarity Reversal Note: Intended for connection to a polarity reversal circuit of a control unit at the protected premises having compatible rating. 4.14.3.1 Using the 5220 Module When the 5220 is wired and programmed for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override trouble conditi

  • SILENT KNIGHT INTELLIKNIGHT 5808, Programming Overview 151274 6-17 System Options (cont.) Phone Lines (cont.) Select Phone Line (cont.) Answering Machine Bypass Yes = en ab l e d *Y = Enabled Section 7.6.2.7 No = disabled System Event Outputs Trouble Events System Trouble Select Group None selected Section 7.6.3.1 Select Cadence Alarm Silence Select Group None selected Select Cadence Trbl Silence Select Group None selected Select Cadence User Selected Group Tr Select Group SBUS Com SBUS Pwr SLC Loop AC Loss Battery Gnd Flt Select Cadence Phone Ln Account Printer Aux Pwr Sys Sw Sys Ala

  • SILENT KNIGHT INTELLIKNIGHT 5808, Control Panel Installation 151274 4-27 4.12.2 Auxiliary Power Installation NAC Circuits 1-4 on the control panel can be used as auxiliary power circuits. The three types of auxiliary power available are: • Door Holder (see section 4.12.2.1) • Constant (see section 4.12.2.2) • Resettable Power (see section 4.12.2.3) Auxiliary power circuits are power limited. Each circuit can source up to 3A (total current for all NAC circuits must not exceed 6A). To install an auxiliary power circuit: 1. Wire the NAC circuit(s) that will be used for auxiliary power. See Figure 3-2 for location of NAC circuits. 2. Configure the auxiliary powe

  • Control Panel Installation 151274 4-3 4.3 Battery Connection The control panel battery charge capacity is 7.0 to 35 AH. The main control cabinet can house batteries up to 18 AH, larger capacity batteries can be housed in a RBB (see Section 4.3.1 for details). Use 12V batteries of the same AH rating. Determine the correct AH rating as per your current load calculation (

  • SILENT KNIGHT INTELLIKNIGHT 5808, System Operation 151274 8-9 8.5.17 Communicating with a Remote Computer An installer at the panel site can initiate communications between the panel and a computer running the Silent Knight Software Suite 5660. You can use this feature to upload a panel configuration. For example, if you have made programming changes to an installation on site using an annunciator, you can send your changes to the computer, so that the central station will have the latest data about the installation. See the software manual for more information (PN 151240). To initiate communication, follow the steps below. 1. From the Main Menu, select for Up/Download. 2. From the next screen that displays, select th

  • SILENT KNIGHT INTELLIKNIGHT 5808, IntelliKnight 5808 Installation Manual 7-18 151274 7.4.4 View Group Points 1. Enter the installer code. 2. Press or to display the main menu. 3. Select for Program Menu. Display reads: Initializing Please wait . . . 4. Press to enter group menu. 5. Press to view group points. 6. Enter the group number, then press . 7.4.5 Edit Output Group Templates Some installations may require that zones be mapped to more than 8 output groups. With output group templates you can combine one or all output groups into one template, which can be used when the same combination of outputs are used for several zones. For example, lets say an installat

Related Products and Documents (Smoke Alarm):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 LG 60PM9700 Specifications lg/60pm9700-S18.pdf 03 Jun 2023 2
2 Yamaha TG300 Owner's manual yamaha/tg300-53Y.pdf 15 Nov 2022 102 4.34 Mb
3 Shimaden SR23 series Instruction manual shimaden/sr23-series-Q16.pdf 13 Aug 2023 154
4 Roda DA04 SERIES Operation & user’s manual roda/da04-series-EHB.pdf 16 Mar 2023 79
5 Nokia X Get started nokia/x-437.pdf 07 Jan 2024 2
6 Gigafast EE2400-G Operation & user’s manual gigafast/ee2400-g-9N7.pdf 28 Jul 2022 30 1.05 Mb

Similar Resources:

  • American Sensor

    ESA5010

    (1 pages)
    24 hour voltage circuit that cannot be turned off by a switch or aground fault interrupter. It is highly recommended that smokealarms be wired on a separate circuit (one with no other lights orappliances) to ensure maximum reliability of AC power supply. Forinstallation of smoke alarms in Dwelling Units, it is important tofollow the National Electrical Cod …
  • Honeywell

    5800COMBO

    (2 pages)
    5800COMBO Quick Installation Guide / Guía Rápida de Instalación This wireless smoke / carbon monoxide detector is intended for use with Honeywell controls that suppor …
  • Smartwares

    RM149

    (2 pages)
    GWARANCJA NA PRODUKTTen produkt ma gwarancję zgodnie z przepisami UE. Gwarancja obowiązuje przez kilka lat, jak określono na opakowaniu, zaczynając od daty zakupu. Należy zachować paragon; dowód zakupu jest wymagany do korzystania z gwarancji. W razie problemów należy skontaktować się ze sklepem, gdzie nabyto produkt. Aby uzyskać więcej informac …
  • Firex

    2650-660

    (2 pages)
    TThhee pprrooffeessssiioonnaall cchhooiiccee iinn ffiirree ssaaffeettyy..FIREX®the recognized leader in residential fire protection,brings you the latest in duct smoke detection technology.FIREX®Duct Smoke Detectors provide early detection ofsmoke and products of combustion present in air movingthrough an HVAC duct. These devices are designed forpreve …
  • NAPCO

    GEM-SMK

    (4 pages)
    Description. The GEM-SMK is a high-quality photoelec-tric smoke detector with built-in supervised digitally-coded radio transmitter. It is compatible with Napco’s GEM-RECV Series supervised security receivers that monitor alarms, restores, low battery and status. The GEM-SMK sounds a local alarm as soon as smoke is detected and the transmitter will send a …
  • Gasmate

    GM160-018

    (20 pages)
    Vertical Gas SmokerRetain these instructions for future use.Important: The installer or seller must leave these instructions with the consumer.4768-07/17Model No. GM160-018FOR OUTDOOR USE ONLY - OPERATES ON LPG …

Comments, Questions and Opinions: