Vanguard V5 Operator's Manual
|
Vanguard V5, O&M-V5-FAP-AVF-LCD R0 Operator’s Manual (Fire Alarm Panel c/w AVF & LCD) Pg 1 of 21 CONTENTS 1. GENERAL 1.1 Introduction 2 1.2 System Description 2 1.2.1 Zone Detection Module 3 1.2.2 System Control Module 3 1.2.3 LCD Event Logging Module 5 2. OPERATING INSTRUCTIONS 2.1. Normal Operating Conditions 5 2.2. Fire Alarm Condition 6 2.2.1. Silencing the Alarm Bells / Sounders
Vanguard V5, O&M-V5-FAP-AVF-LCD R0 Operator’s Manual (Fire Alarm Panel c/w AVF & LCD) Pg 2 of 21 1. GENERAL 1.1 Introduction This manual provided only the basis operator’s information on the control and operation of the Fire Alarm System. To ensure continuous reliability of the system, the owner or owner’s representative should establish an agreement to carry out regular maintenance of the installation with the manufacturer or manufacturer’s representative or a competent and qualified contractor trained to service and maintain this system. The arrangements for maintenance should be such as w
Vanguard V5, O&M-V5-FAP-AVF-LCD R0 Operator’s Manual (Fire Alarm Panel c/w AVF & LCD) Pg 3 of 21 1.2.1 Zone Detection Module Indicators and Control a) Fire (Red) : Zone in fire condition b) Fault (Amber) : Zone detection circuit open/short fault condition c) Disable (Amber) : Zone in disabled condition d) Disable Switch (Blue) : To disable zone fire & fault detection circuit (Note: Zone disable function only prior to an alarm activation.) 1.2.2 System Control Module Indicators a) Power On (Green) : System energised by Mains and/or Standby Batter
Vanguard V5, O&M-V5-FAP-AVF-LCD R0 Operator’s Manual (Fire Alarm Panel c/w AVF & LCD) Pg 4 of 21 d) Disabled (Amber) : General Disabled Indicator, system in disabled condition e) System Fault (Amber) : Indicate Programmable Micro Controller failure f) Fire Sent (Red) : Fire Signal to Alarm Remote Monitoring Station activated (Optional) g) Fire Line Trouble (Amber) : Fire Signal Line open/short (Optional) (Note: It shall not be suppressed during the Fir
O&M-V5-FAP-AVF-LCD R0 Operator’s Manual (Fire Alarm Panel c/w AVF & LCD) Pg 5 of 21 1.2.3 LCD Event Logging Module Indicators a) Power On (Green) : System energised by Mains and/or Standby Battery b) Processor Fault (Amber): Indicates that Micro Processor Unit failure in processing c) LCD Display : To display the Pane
O&M-V5-FAP-AVF-LCD R0 Operator’s Manual (Fire Alarm Panel c/w AVF & LCD) Pg 6 of 21 2.2 Fire Alarm Condition The panel / system shall enter into an alarm condition when an input device (such as smoke/heat detector, call point; or pressure/flow switch) is activated. Under Fire Alarm conditions: a) Twin “FIRE” LEDs (Red) of the alarm zone lighted b) General, “FIRE
Vanguard V5, O&M-V5-FAP-AVF-LCD R0 Operator’s Manual (Fire Alarm Panel c/w AVF & LCD) Pg 7 of 21 2.2.2 Resetting the System Before the system is reset, the cause of the alarm must be investigated and duly rectified. In the case of a false alarm, make sure that there is no incident of fire before resetting the system. Note : It is not possible to reset the system before the alarm is silenced. a) Re-instate the affected devices to normal b) Press “System Reset” Switch (Green) (3) c) Upon resetting, the system should resume to normal operating condition, if there are no other events to cause another alarm and the original cause of the alarm being rectified.
O&M-V5-FAP-AVF-LCD R0 Operator’s Manual (Fire Alarm Panel c/w AVF & LCD) Pg 8 of 21 2.4 Initiating Evacuate Alarm The system is provided with a “Sound Alarm” switch in the event of emergency. To sound alarms for emergency evacuate: a) Press “Sound Alarm” switch (Red) (6) b) Sound Alarm amber LED lighted c) External alarm bells/sound
Vanguard V5, O&M-V5-FAP-AVF-LCD R0 Operator’s Manual (Fire Alarm Panel c/w AVF & LCD) Pg 9 of 21 d) No outputs are activated (FIRE output, external Alarm Bells/ Aux output) e) When Retard State (20 sec) lapses, Retard State LED go off f) “CONFIRMATION STATE” LED (Amber) lighted (120sec) During Confirmation State (120sec) a) If no alarm activated, panel back to normal condition itself when Confirmation State (120 sec) expire b) If any zone goes into alarm, panel goes into FIRE condition 2.8 LCD Event L
Vanguard V5, O&M-V5-FAP-AVF-LCD R0 Operator’s Manual (Fire Alarm Panel c/w AVF & LCD) Pg 10 of 21 2.8.1.a VIEW FIRE ARCHIVE To view the recorded alarm zone event; a) Press “Menu” b) Select “VIEW FIRE ARCHIVE” by “Up” / “Down” key and press “Enter” (017TC: Total Event Counter “017”, Fire) (017: 17 th event of 017TC, M00-Z005: “Main” panel address “000” Zone “005” Fire) at (02/04/06: 2 nd April 2006, 15:32:12: 3:32:12PM) c) The rest recorded event are able to view by manual action (Down/Up key)
Vanguard V5, O&M-V5-FAP-AVF-LCD R0 Operator’s Manual (Fire Alarm Panel c/w AVF & LCD) Pg 11 of 21 (1) PNL ADR: To set the Panel Address, select by “Up” / “Down” key and press “Enter” to save (e.g. M000: Main Panel Address 000, S001: Sub Panel Address 001) (2) TIME: To set the Time, select the time by “Up” / “Down” key and press “Enter” to save (Hour:Minute:Second – 24Hr System) (3) DATE: To set the Date, select the Date by “Up” / “Down” key and press
Vanguard V5, O&M-V5-FAP-AVF-LCD R0 Operator’s Manual (Fire Alarm Panel c/w AVF & LCD) Pg 12 of 21 3. ROUTINE MAINTENANCE 3.1 Introduction To ensure continuous reliability of the fire alarm system, regular testing and servicing shall be carried out. Only trained and competent personal are allowed to performance the routine testing and maintenance. 3.2 Maintenance Responsibilities The owner shall appoint a competent person to supervise and coordinate all matters in relation to the fire alarm systems. This include arranging for the system to be checked, tested and serviced in accordance with the requirements as described in the Singapore Standard CP 10 :
Vanguard V5, O&M-V5-FAP-AVF-LCD R0 Operator’s Manual (Fire Alarm Panel c/w AVF & LCD) Pg 13 of 21 d) If possible, determine the cause of the fault or note the activities immediately prior to the area affected. e) Silence the fault buzzer. f) Inform the maintenance contractor responsible for servicing and arrange for repair. 3.4.2 Weekly Test The following tests and checks should be made by the operator or by the maintenance’s contractor responsible for servicing and performance of the syst
Vanguard V5, O&M-V5-FAP-AVF-LCD R0 Operator’s Manual (Fire Alarm Panel c/w AVF & LCD) Pg 14 of 21 d) Check charger voltage and battery terminals condition. Ensure that no faults signal are indicated on the panel. e) Disconnect the battery supply. The “POWER ON” and “BATTERY FAULT” indicators should be lighted and the buzzer sounding. Connect back the battery and system should normalise itself. f) Switch off incoming mains supply. The “POWER ON”, “MAINS FAULT” and “CHARGER FAULT” indicators should be lighted and the buzzer sounding. The standby battery should take over the supply to the s
O&M-V5-FAP-AVF-LCD R0 Operator’s Manual (Fire Alarm Panel c/w AVF & LCD) Pg 15 of 21 c) Where the heat-sensitive element of thermal detectors or the enclosure of other detectors are found to be coated with paint or any material likely to affect the operation of the detectors, such material should be cleaned off or if necessary have the detector repla
Vanguard V5, O&M-V5-FAP-AVF-LCD R0 Operator’s Manual (Fire Alarm Panel c/w AVF & LCD) Pg 16 of 21 4. FAULT FINDING TIPS CHECK LIST FAULT Specific Indication Possible Causes ACTION SHOULD BE TAKEN - Manual Call-point - Vandalise - Glass Broken - Heat / Smoke Detector - Environment - Faulty - Flow Switch - Leakage - Misused - Sub Alarm Panel - Activated Zone Fire (False Alarm) - EOL Resistor - Shall be 6.8K Ohm - Inspect the alarm activated zone IF FALSE ALARM 1. Check the possible causes
Vanguard V5, O&M-V5-FAP-AVF-LCD R0 Operator’s Manual (Fire Alarm Panel c/w AVF & LCD) Pg 17 of 21 CHECK LIST FAULT Specific Indication Possible Causes ACTION SHOULD BE TAKEN Earth “+VE” (Red) (@ FBM) - One or more Field “+VE” line and/or - Alarm “–VE” line (in normal condition) Earth Fault Earth “-VE” (Amber) (@ FBM) - One or more Field “-VE” line and/or - Alarm “+VE” line (in normal condition) - Shorted to Chassis / Trucking / Conduit 1. Press “Buzzer Silence” (Black-1) 2. Dismantle all
Vanguard V5, O&M-V5-FAP-AVF-LCD R0 Operator’s Manual (Fire Alarm Panel c/w AVF & LCD) Pg 18 of 21 CHECK LIST FAULT Specific Indication Possible Causes ACTION SHOULD BE TAKEN - Fire signal Line - Disconnected “1” (Amber) - Open (@ DIM) - Termination - Loose - Fire signal Line - Shorted Fire Line Trouble (Alarm Monitoring Station) “1” (Red) - Short (@ DIM) - Alarm Monitoring Transmitter Panel - Faulty - Fault signal Line - Disconnected “2” (Amber) - Open (@ DIM) - Termination - Loose - Fault signal Line - Shorted Fault Line Trouble (Alarm Monitoring Station) “2” (Red) – Short (@ DIM) - Alarm Monitoring Transmitter Panel - Faulty 1.
Vanguard V5, O&M-V5-FAP-AVF-LCD R0 Operator’s Manual (Fire Alarm Panel c/w AVF & LCD) Pg 19 of 21 V5 Technical Specification and Installation Diagram
Vanguard V5, O&M-V5-FAP-AVF-LCD R0 Operator’s Manual (Fire Alarm Panel c/w AVF & LCD) Pg 20 of 21 TECHNICAL SPECIFICATION Fire Alarm Panel S/N I/P – O/P Description Capacity / Rating End Of Line Resistor (EOLR) Feature 1 ZONE - Min 4 Zones (Multiple of 4 Zones) - Max 136 Zones - 40 Heat or 20 Smoke Detectors per Zone - Max 2.4 mA per Zone - Wire: 1.5mm 2 6.8K Ohm - Line Open / Short supervised 2 ALM - 1 Output - DC 24V - Fuse: Max 2Amp - Wire: 2.5mm 2 6.8K Ohm - Line Open / Short supervised c/w Fuse Protection - Expendable by additional module 3 ALM – 2 Output - DC 24V - Fuse: Max 2Amp - Wire: 2.5mm 2 6.8K Ohm - Line Open / Sho
Vanguard V5, O&M-V5-FAP-AVF-LCD R0 Operator’s Manual (Fire Alarm Panel c/w AVF & LCD) Pg 21 of 21 1 Z1 + - 2 -+ Z2 3 4 -+ Z3 5 6 -+ Z4 7 8 -+ Z5 9 10 -+ Z6 11 12 -+ Z7 13 14 -+ Z8 15 16 -+ ALM-1 17 18 -+ ALM-2 19 20 C+ NC- AUX-1 21 22 23 NO- C+ AUX-1 24 NO-NC- 25 26 3 C FIRE + - TO MAP 1 2 NC NOCNONC FAULT 864 5 7 109 ++ 1211 -- 1413 G-ALM IPOP 1615 G-SIL IPOP 1817 G-RST IPOP 2019 G-AUX IPOP AUX - DC 24V VC FC AUX-1 1 2 3 FC VC 1 3 2 AUX-2 ALM-1 ALM-2 AUX FUSES MAP SAP G-RST JS1 ZONE FUSE BELL AUX ALM-2 + - CO JS2 EARTH +VE -VE OS ALM-1 OS ALM-2 + - CO CO - + AC AC OFF ON SW1 24V DC + - BATTERY BATTE
DOWNLOAD |
Danfoss ECL Comfort 100M Smoke Alarm User's manual and installation instructions
ECL Comfort 100M |
Zeta Premier Quatro Smoke Alarm Installation manual
Premier Quatro |
Siemens FDA241 Smoke Alarm Technical manual
FDA241 |
usi MI106S Smoke Alarm Operation & user’s manual
MI106S |
Zooper Premier MX-16 Smoke Alarm User's operation manual
Premier MX-16 |
LIFETONE HLAC150 Smoke Alarm Operation & user’s manual
HLAC150 |
Viessmann Vitocontrol-S, WB2 Smoke Alarm Installation, start-up and service instructions manual
Vitocontrol-S, WB2 |
Ebode eSD18 Smoke Alarm Operation & user’s manual
eSD18 |
# | Manufacturer | Model | Document Type | File | Updated | Pages | Size |
---|---|---|---|---|---|---|---|
1 | Sony | VGC-RB49 Vaio | Operation & user’s manual | sony/vgc-rb49-vaio-C6V.pdf | 22 Dec 2022 | 2 | 0.7 Mb |
2 | Hitachi | DH 20PB | Technical data and service manual | hitachi/dh-20pb-CKH.pdf | 19 Oct 2023 | 6 | 0.21 Mb |
3 | Fossil | ANALOG AUTOMATIC MOVEMENT WITH DATE | Manual | fossil/analog-automatic-movement-with-date-2B3.pdf | 17 Sep 2023 | 1 | 0.04 Mb |
4 | DeWalt | DW511 | Instruction manual | dewalt/dw511-X76.pdf | 04 Mar 2024 | 7 | 2.68 Mb |
5 | LENCO | DVP-744 | Manual | lenco/dvp-744-751.pdf | 27 Feb 2024 | 18 | |
6 | Panasonic | DE-852D | Operating instructions manual | panasonic/de-852d-99T.pdf | 18 Aug 2022 | 8 | 0.47 Mb |
BRK electronic
1 INSIDE THIS MANUAL THIS USER’S MANUAL HAS BEEN RESIZED TO PRINT OUT ON 8-1/2 x 11” PAGES.BLACK page numbers reference the original printed document.RED page numbers reference this web version.Other Features Of Smoke Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1Special Compliance Considerations . . . …
2002(5 pages) |
ELRO
Skip to contentManuals+User Manuals Simplified.ELRO Smoke Alarm Instruction ManualHome » ELRO » ELRO Smoke Alarm Instruction Manual ELRO Smoke Alarm Instruction Manual
…
FS9010(10 pages) |
SILENT KNIGHT
Installation andOperations ManualAddressable Fire Alarm Control PanelDocument: 151295 Rev: TP/N 151295:T ECN: 15- 0644INTELLIKNIGHT®MODEL 5700
…
5700(184 pages) |
Bacharach
Why Te s t ?BACHARACH625 Alpha Drive, Pittsburgh, PA 152381-800-736-4666www.bacharach-inc.comIn Canada, call 1-800-328-5217Combustion testing todayis no longer an option.It’s a necessity.It used to be that fossil fuel-burning homeappliances could be adequately serviced byconducting visual tests. But with today’sregulatory, environmental and safety conce …
Model 105(2 pages) |
First Alert
INTRODUCTIONThank you for choosing BRK Brands, Inc. for your Smoke Alarm needs. You have purchaseda state-of-the-art Smoke Alarm designed to provide you with early warning of a fire. Key features include:Smart Technology designed to help reduce unwanted or nuisance alarms.Single Button Test/Silence eliminates confusion. Depending on what mode the alarm is in …
9120 Series(2 pages) |
Visonic
The MCT-426 is a fully supervised wire-less photoelectric smoke detector that is compatible with PowerMax® and other Visonic PowerCode™ wireless home security systems. Designed for a wide range of residential and com-mercial applications, this detector is easily installed and has a streamlined design to t any internal décor. MCT-426 Wireless Smo …
MCT-426(1 pages) |
Harbor Freight Tools Paint Sprayer 69704Harbor Freight Tools Product User Guide: 69704 PDF Owner's manual & safety instructions - DNUHMH 69704, 20 |
HP Server ProLiant SL390s G7 2UHP ProLiant SL390s G7 2U Server Maintenance and service manual ProLiant SL390s G7 2U, 91 |
Scytek electronic Car Alarm PRECISION 5500Scytek electronic Product Guide: PRECISION 5500 PDF Product manual - ZO9DY9 PRECISION 5500, 52 |
YUNEEC Kitchen Appliances E-GO 2YUNEEC E-GO 2 Guide (Doc Type: Kitchen Appliances Quick start manual) E-GO 2, 6 |
Denon Receiver AVR-2308Receiver PDF Specifications AVR-2308, 2 |
VTech Motorized Toy Car Safari Sounds MicrophoneVTech Product Manual: Safari Sounds Microphone PDF Operation & user’s manual - D4HSR9 Safari Sounds Microphone, 10 |
Healthrider Other Crosstrainer 950 S EllipticalHealthrider Crosstrainer 950 S Elliptical Manual (Manual ), @427PSN Crosstrainer 950 S Elliptical, 28 |
Aiwa Car Receiver CT-FX929M mAiwa Car Receiver CT-FX929M m Operating instructions manual CT-FX929M m, 56 |
Polycom Other ReadiManagerLX100Polycom ReadiManagerLX100 Guide (Doc Type: Other Release note) ReadiManagerLX100, 6 |
ProForm Other 790 Zlt Cwl TreadmillProForm 790 Zlt Cwl Treadmill Guide (Doc Type: Other Manual ) 790 Zlt Cwl Treadmill, 32 |
ICON Health & Fitness Hot Tub IMSB73910IMSB73910 (Hot Tub ePDF User Manual, #5F1YV9) IMSB73910, 20 |
KitchenAid Refrigerator KSSC42QMS02KitchenAid Product Guide: KSSC42QMS02 PDF Parts list - RNTW5D KSSC42QMS02, 26 |