  • Turbo Air TAS-09EH/O, 1 SERVICE MANUAL FOR AMERICA DC Inverter Multi-Split Air-Condition Unit TAS-09EH/O TAS-12EH/O TAS-18EH/O TAS-24EH/O TAS-24MVH/O TAS-18MVH/O Indoor Unit Outdoor Unit TAS-09MVH TAS-18MVH/O TAS-24MVH/O TAS-12MVH TAS-09EH TAS-09EH/O TAS-12EH TAS-12EH/O TAS-18EH TAS-18EH/O TAS-24EH TAS-24EH/O REFRIGERENT HEAT PUMP R410A SERVICE MANUAL

  • Turbo Air TAS-09EH/O, 60 SERVICE MANUAL FOR AMERICA 4 REFRIGERANT TUBING CONNECT THE INDOOR TO THE OUTDOOR UNIT The indoor unit contains a small quantity of nitrogen.Do not unscrew the nuts from the unit until you are ready to connect the tubing.The outdoor unit is supplied with suffcient refrigerant charge(R410A). Refer to outdoor unit nameplate. To prevent crushing,bend tubes using a bending tool. NOTE:Use refrigeration R410Atype copper tubing only. 1.Open the valve cover. 2.Use tubing diameter that corresponds to the tubing diameter of the indoor and outdoor units. Not

  • Turbo Air TAS-09EH/O, 44 SERVICE MANUAL FOR AMERICA 4. Leakage or reverse valve fault The air conditioner shutdown immediately when meet one of below conditions. 1) Heating: coil pipe temp. of outdoor unit can’t decrease 3 degree within setting time and coil pipe temp. of indoor unit can’t increase 3 degree all along. 2) Cooling: coil pipe temp. of outdoor unit can’t increase 3 degree within setting time and coil pipe temp. of indoor unit can’t decrease 3 degree all along. 5. High temp. protection of compressor discharge 1) The protection don’t effect if the temp. sensor of compressor discharge fault. 2) The air c

  • Turbo Air TAS-09EH/O, 50 SERVICE MANUAL FOR AMERICA 13.3 outdoor unit : TAS-18EH/O NO. description name number NO. description name number 1 前网罩 Front Grill 1 11 四通阀组 件 Four-way valve assembly 1 2 面 板 Front Plate 1 12 电子膨胀 阀 Electronic expansion valve 1 3 轴流风轮 Axial flow fan 1 13 右侧板 Right panel 1 4 电 机 Motor 1 14 电器盒盖 Top of the Electric Box 1 5 左侧板 Left panel 1 15 阀座板 Valve installation plate 1 6 电

  • 35 SERVICE MANUAL FOR AMERICA  Turn off air conditioner in heating mode, if the coil pipe temp. of indoor unit is more than 104 O F, indoor blower fan is running at low speed. If the coil pipe temp. of indoor unit is less than or equal to 104 O F or turn off air conditioner over 2 minutes, It shutdown indoor blower fan. 4. Auto mode 

  • Turbo Air TAS-09EH/O, 13 SERVICE MANUAL FOR AMERICA 5.2.1 Indoor Units Capacity For 12000BTU Capacity Model 12000BTU TAS-12MVH TAS-12EH 5.2.1.1 Cooling Capacity (BTU)---Run Model (Unit A,B,C or D),230/115V,Indoor fan at high speed INDOOR ENTERING AIR DB/WB TEMPERATURE [ 0 F] OUTDOOR ENTERING AIR DB TEMPERATURE[ 0 F] DATA 72/59 75/63 81/66 84/70 90/73 14~68 (protection range) TC 80 - 110 % of nominal SC 80 - 105 % of nominal PI 25 - 50 % of nominal 77 TC 11616 12336 13104 13872 14640 SC 10421 10603 10845 11027 11269 PI 0.72 0.73 0.75 0.76 0.77 86 TC 11040 11808 12576 13296 14064

  • Turbo Air TAS-09EH/O, 57 SERVICE MANUAL FOR AMERICA 2 ELECTRICAL CONNECTION BETWEEN OUTDOOR AND INDOOR UNIT ELECTRICAL REQUIREMENTS Electrical wiring and connections should be made by qualified electricians and in accordance with local electrical codes and regulation.The air conditioner units must be grounded. The air conditioner units must be connected to an adequate power outlet from a separate branch circuit protected by a time delay circuit breaker,as specified on unit's nameplate. Voltage should not vary beyond ± 10% of the rated voltage. 1 .Remove the power supply cable that is connected to the indoor unit! 2.To connect the indoor units to the outdoor units,use

  • Turbo Air TAS-09EH/O, 49 SERVICE MANUAL FOR AMERICA 13.2 outdoor unit : TAS-12EH/O NO. description name number NO. description name number 1 顶盖板 Top panel 1 12 高压阀 High-pressure valve 1 2 电控盒 Electric box 1 13 压缩机 Compressor 1 3 背网 Rear Grill 1 14 底盘 Base 1 4 中隔板 Partition board 1 15 冷凝器 Condenser 1 5 四通阀 Four-way valve 1 16 电机支架 Motor support 1 6 电子膨胀阀 Electronic expansion valve 1 17 电机 Motor 1 7 干燥过滤器 Desiccation filter 1 18 轴流风机 Axial flow fan 1 8 右侧板 Right panel 1

  • Turbo Air TAS-09EH/O, 7 SERVICE MANUAL FOR AMERICA 3. RATING CONDITIONS Standard conditions in accordance with ANSI/AHAM RAC-1-2003, and UL 484. Cooling: Indoor: 80 o FDB 67 o F WB Outdoor: 95 o F DB 75 o F WB Heating: Indoor: 70 o F DB 60 o F WB Outdoor: 47 o F DB 43 o F WB 3.1 Operating Limits Outdoor Cooling Upper limit (DB) 110 o F Lower limit (DB) 5 o F Heating Upper limit (DB) 75 o F Lower limit (DB) 5 o F Voltage 2PH 198–264V/115V 3PH N/A 4. OUTLINE DIMENSIONS 4.1 outdoor Unit: TAS-09EH/O

  • 40 SERVICE MANUAL FOR AMERICA Control of Expansion Valve in Cooling Mode 1. Reset of Expansion Valve In the first time ,the expansion valves in all channels shall be shut down 600 steps, then the expansion valve corresponding to the indoor unit in normal communications with the outdoor unit shall be opened to standby mode steps. If accomplished, the outdoor un

  • Turbo Air TAS-09EH/O, 6 SERVICE MANUAL FOR AMERICA 2.2 Indoor Units Data 2.2.1 TAS-09MVH Specifications Indoor TAS-09MVH FAN MOTOR Model YDK-16-4C Input (W) 54 Capacitor (UFD) 1.2/450VAC Fan Motor FLA (A) 0.25 Speed (Hi/Med/Low) (RPM) 1150 / 950 / 750 Evaporator Number of rows 22 Tube pitch row / pitch (in) .69 / .50 Fin spacing (in) 0.0614 Fin Type Louvered Fin Tube outside dia.(in) / Type 0.2756 Rifled Tube Coil Length x height x width (in) 25.39 x 11.06 x 1 Air Flow (Hi/Med/Low) (CFM) 353 / 306 / 194 Noise Level (dB(A) ≤42 Fan Type Cross Flow Fan Diameter (in) 3.661 Fan Length (in) 24.921 Design Pressure (PSI) 551.14 Unit Dimensions (W

  • Turbo Air TAS-09EH/O, 47 SERVICE MANUAL FOR AMERICA P4: 1: discharge temp. too high.---maybe leak refrigerant, add refrigerant. 2:outdoor ambient temp. too high, if (T<-4 O F,T>131 O F), it will alarm. 3:temp. switch of compressor cut off.。 4:Communication interfere. (earth wire can’t with communicate wire in same cable)---check cable. P7: 1,PFC board fault.---change PFC board. 2,Communication of main board and PFC board fault.---check wires of main board and PFC board. P8: 1,

  • 18 SERVICE MANUAL FOR AMERICA 5.2.4.2 Heating Capacity (BTU)---Run Model,230V,Indoor fan at high speed ID COIL ENTERING AIR DB TEMPERATURE [ 0 F] OD COILENTERING AIR DB/WB TEM PERATU RE[ 0 F] DATA 59 68 77 5/3 TC 15680 14455 13475 PI 1.35 1.49 1.63 14/10 TC 17395 16170 15190 PI 1.63 1.76 1.93 20/18 TC 18620 17640 164

  • Turbo Air TAS-09EH/O, 48 SERVICE MANUAL FOR AMERICA 13. EXPLODED VIEWS AND SPARE PARTS LISTS 13.1 outdoor unit : TAS-09EH/O NO. description name number NO. description name number 1 前网罩 Front Grill 1 11 电器盒盖 Top of the Electric box 1 2 面 板 Front Plate 1 12 阀座板 Valve installation plate 1 3 轴流风轮 Axial flow fan 1 13 低压阀 Low-pressure valve 1 4 电 机 Motor 1 14 高压阀 Ligh-pressure valve 1 5 电机支架 Motor support 1 15 毛细管组件 Capillary Assy 1 6 冷凝器 Condenser 1 16 电子膨胀阀 Electronic expansion valve 1 7 顶盖板 Top

  • Turbo Air TAS-09EH/O, 43 SERVICE MANUAL FOR AMERICA 八.Control of oil return circle 1. Oil return circle period When air conditioner has run for 10 minutes or accumulate time T msro is end, it execute oil return circle once. 2. When compressor is running to oil return circle, the indoor unit which have communication is return oil, expand valve is open fully and compressor’s frequency increase more than 3/5 of max frequency for 90 seconds, the expand valve of indoor unit which no communication is close. 九. Operation mode control of outdoor unit(dehumidify、cooling or heating) The indoor unit can require coolin

  • Turbo Air TAS-09EH/O, 20 SERVICE MANUAL FOR AMERICA 6. Pressure Curve 6.1 Model TAS-09EH/O TAS-18MVH/O TAS-12EH/O TAS-24MVH/O TAS-18EH/O TAS-24EH/O 6.1.1 Suction Pressure Curve 6.1.2 Discharge Pressure Curve

  • Turbo Air TAS-09EH/O, 15 SERVICE MANUAL FOR AMERICA Heating Capacity Ratio Vs. Outdoor Temperature Heating Capacity Correction Factor 0 0.2 0.4 0.6 0.8 1 1.2 1.4 5 14203036455059 Outdoor Temp.(deg F) Capacity Ratio 59 68 77 5.2.3 Indoor Units Capacity For 18000BTU Capacity Model 18000BTU TAS-18EH 5.2.3.1 Cooling Capacity (BTU)---Run Model ,230V,Indoor fan at high speed INDOOR ENTERING AIR DB/WB TEMPERATURE [ 0 F] OUTDOOR ENTERING AIR DB TEMPERATURE[0F] DATA 72/59 75/63 81/66 84/70 90/73 14~68

  • Turbo Air TAS-09EH/O, 14 SERVICE MANUAL FOR AMERICA 5.2.1.2 Heating Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at high speed ID COIL ENTERING AIR DB TEMPERATURE [ 0 F] OD COILENTERING AIR DB/WB TEM PERATU RE[ 0 F] DATA 59 68 77 5/3 TC 8960 8260 7700 PI 0.66 0.73 0.80 14/10 TC 9940 9240 8680 PI 0.80 0.87 0.95 20/18 TC 10640 10080 9380 PI 0.91 0.97 1.04 30/28 TC 11060 10500 9800 PI 0.96 1.02 1.08 36/34 TC 11340 10640 10080 PI 0.99 1.06 1.12 45/43 TC 14560 14000 13440 PI 1.04

  • 3 SERVICE MANUAL FOR AMERICA 1. INTRODUCTION 1.1 General The new CMV and CS is a high efficiency DC inverter technology outdoor unit, since it’s a lego concept unit, it can be matched to several inverter indoor units such as wall mounted type with a capacity range of 9000 – 12000 BTU for each single indoor unit. 1.2 Main Feature

  • Turbo Air TAS-09EH/O, 30 SERVICE MANUAL FOR AMERICA When the outdoor unit is installed above the indoor unit an oil trap is required every 5m along the suction line at the lowest point of the riser. Incase the indoor unit is installed above the outdoor, no trap is required 11. CONTROL SYSTEM TUBE (Inch) ¼” ~” ½” ~” ¾” TORQUE (Nm) Flare Nuts 11-13 40-45 60-65 70-75 80-85 Valve Cap 13-20 13-20 18-25 18-25 40-50 Ser

  • 58 SERVICE MANUAL FOR AMERICA 3 INSTALLATION/SERVICE TOOLS (ONLY FOR R410A PRODUCT) CAUTION New Refrigerant Air Conditioner Installation This air conditioner adopts the new HFC refrigerant (R410A) which does not destroy ozone layer. R410A refrigerant is approx . 1.6 times of refigerant R22. Accompanied with the adoption of the ne

  • Turbo Air TAS-09EH/O, 38 SERVICE MANUAL FOR AMERICA 1、Cooling Condition Entering Method label Capacity Pressing Tubro for 5 times+Setting temp.77 O F A2 Pressing Tubro for 5 times+Setting temp.75 O F B2 Pressing Tubro for 5 times+Setting temp.73 O F B1 Pressing Tubro for 5 times+Setting temp.71 O F F1 Pressing Tubro for 5 times+Setting temp.69 O F EV Pressing Tubro for 5 times+Setting temp.67 O F A2:Indoor temp. 95 OF,Compressor max B2:Indoor temp. 82 OF,Compressor max B1:Indoor tem

  • Turbo Air TAS-09EH/O, 16 SERVICE MANUAL FOR AMERICA 5.2.3.2 Heating Capacity (BTU)---Run Model,230V,Indoor fan at high speed ID COIL ENTERING AIR DB TEMPERATURE [ 0 F] OD COILENTERING AIR DB/WB TEM PERATU RE[ 0 F] DATA 59 68 77 5/3 TC 12160 11210 10450 PI 0.96 1.05 1.15 14/10 TC 13490 12540 11780 PI 1.15 1.25 1.37 20/18 TC 14440 13680 12730 PI 1.31 1.40 1.50 30/28 TC 15010 14250 13300 PI 1.39 1.46 1.56 36/34 TC 15390 14440 13680 PI 1.42 1.52 1.62 45/43 TC 19760 19000 18240 PI 1.50 1.60 1.70 50/48 TC 20900 20140 19190 PI 1.6

  • Turbo Air TAS-09EH/O, 59 SERVICE MANUAL FOR AMERICA Flare tool (clutch type) 0 By incressing the clamp bar'receiving hole size , strength of spring in the tool has been improved. Gauge for projection adjustment _ Used when flare is made by using conventional flare tool. Vacuum pump adapter 0 Connected to conventional vacuum pump,it is necessary to use an adapter to prevent vacuum pump oil from flowing back into the charge hose , The charge hose connecting part has two ports-one for conventional

  • 51 SERVICE MANUAL FOR AMERICA 13.4 outdoor unit : TAS-24EH/O NO. description name number NO. description name number 1 顶盖板 Top panel 1 13 维修板 Maintenance plate 1 2 减振块 Anti-vibration pad 1 14 小抽手 Small handle 2 3 中隔板 Partition board 1 15 压缩机 Compressor 1 4 �

  • Turbo Air TAS-09EH/O, 52 SERVICE MANUAL FOR AMERICA 13.5 outdoor unit : TAS-18MVH/O NO. description name number NO. description name number 1 前网罩 Front Grill 1 14 电器盒盖 Top of the Electric Box 1 2 面 板 Front Plate 1 15 阀座板 Valve installation plate 1 3 轴流风轮 Axial flow fan 1 16 A 机 DN4 截止阀 DN4 valve 1 4 左侧板 Left panel 1 17 A 机 DN10 截止阀 DN10 valve 1 5 电机支架 Motor support 1 18 B 机 DN4 截止阀 DN4 valve 1 6 冷凝器 Condenser 1 19 B 机 DN10 截止阀 DN10 valve 1 7 顶盖板 Top panel 1 20 维修板 Maintenance plate 1 8 电器盒 Electric

More Instructions:

DOWNLOAD

Related Products and Documents (Air Conditioner):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 Sennheiser GP 03-M Technical data sennheiser/gp-03-m-16G.pdf 24 Sep 2023 1 0.12 Mb
2 White-Westinghouse WDE216RB Operating instructions white-westinghouse/wde216rb-627.pdf 04 Mar 2024 2 0.15 Mb
3 Elkay ILCGR4822L1 Specification sheet elkay/ilcgr4822l1-I5J.pdf 12 Nov 2022 2 0.38 Mb
4 Phase Technology PC-9.1 Brochure phase-technology/pc-9-1-ZUM.pdf 13 Feb 2024 3 0.27 Mb
5 GE E1450W Návod k použití ge/e1450w-PM3.pdf 22 Jan 2023 85 5.73 Mb
6 Braun SkinSpa 5377 Instructions manual braun/skinspa-5377-3MW.pdf 18 Jul 2022 17 5.82 Mb

Similar Resources:

  • Samsung

    A717 - SGH Cell Phone 26 MB

    (189 pages)
    A717_UCGD6_ATT_WB_051507_F6 SGH-A717 TELÉFONO MÓVILPORTATIL DE BANDA CUADRUPLEManual del usuarioPor favor lea este manual antes de usar el teléfono y consérvelo para consultarlo en el futuro. …
  • Daikin

    R32 Split Series

    (76 pages)
    Installer reference guide R32 Split series3AMXM52N2V1B93MXM40N2V1B93MXM52N2V1B93MXM68N2V1B94MXM68N2V1B94MXM80N2V1B95MXM90N2V1B9 3AMXF52A2V1B93MXF52A2V1B93MXF68A2V1B9 …
  • Danby

    Diplomat DAC7037M

    (12 pages)
    USE AND CAREMANUALMANUELD'UTILISATIONModel • Modèle DAC7037MCAUTION:Read and Follow All Safety Rulesand Operating Instructions BeforeFirst Use of This Product.PRÉCAUTION:Veuillez lire attentivement les consignes de sécurité et lesinstructions d'utilisation avantl'utilisation initiale de ce produit.Room Air ConditionerTable of conten …
  • Impecca

    ITAC-08KS21

    (50 pages)
    1Impecca Through-the-WallAir ConditionerUsers ManualITAC-08KS21(115V) • ITAC-10KSA21 (115V) ITAC-12KSA21 (115V) • ITAC-12KSB21 (208/230V)This manual covers the following models: …
  • Mitsubishi Electric

    City Multi Series

    (44 pages)
    TECHNICAL & SERVICE MANUALIndoor unit[Model Name] [Service Ref.]PLFY-EP06NEMU-EPLFY-EP08NEMU-EPLFY-EP12NEMU-EPLFY-EP15NEMU-EPLFY-EP18NEMU-EPLFY-EP18NEMU-E1PLFY-EP24NEMU-EPLFY-EP30NEMU-EPLFY-EP36NEMU-EPLFY-EP48NEMU-ECONTENTS 1. SAFETY PRECAUTION.......................... 2 2. PARTS NAMES AND FUNCTIONS........ 4 3. SPECIFICATIONS....................... …
  • arcelik

    01M-8897723200-5220-10

    (92 pages)
    Split type wall mountedair-conditionerHomeWhiz FunctionOwner’s Manual01M-8897723200-5220-10 - 01M-8897733200-5220-1001M-8897693200-5220-10 - 01M-8897673200-5220-10EN - DE- IT - ES - PL - FR - RO - NL - TH BS - HR - MK - SL - SQ - SR - BG - PT …

Comments, Questions and Opinions: