Siemens 7KG6106 Operating Instructions Manual
|
Siemens 7KG6106, SIMEAS-T - Transducer with auxiliary power 7 Operating Instructions 1 Area of application Transducers are used to convert different measured signals from high-voltage and low-voltage systems into proportional output variables. Areas of application are, for example Power supply and distribution for areas in which measured signals must be sent over a large distance. The active SIMEAS transducers convert the alternating input voltage or the alternating input current from the high-current power network (45 to 65Hz) into a load-independent direct output current or a load-independent direct output voltage. Up to the maximum permissible load, multip
Siemens 7KG6106, SIMEAS-T - Transducer with auxiliary power 14 9 Ordering data Ordering data for alternating voltage (G) MUU Name Order no. Code Device 7KG 6 1 0 6 - - B ↑ ↑ ↑ ↑ Input signal EN │ │ │ │ Rated frequency fEN 50 Hz 2 │ │ │
SIMEAS-T - Transducer with auxiliary power 5 Safety instructions ......................................................................................................................... 2 Operating Instructions ..................................................................................................................... 7 1 Area of application ..............................
Siemens 7KG6106, SIMEAS-T - Transducer with auxiliary power 21 Arrangement of the balancing potentiometers Transducer with linear characteristic curve from 0 to AN Full-scale value Feed E = EN ± 0.05% EN , set output end value with trim potentiometer R33 Set A = AN ± 0.2% AN . Check intermediate values. Transducer with linear characteristic curve from IA 4 mA to 20 mA 4 mA only connect auxiliary power, input (short terminals 11 and 12) and set the output value A = 4 mA ± 0.2% AN with trim potentiometer R34. 20 mA Feed E = EN ± 0.05% EN , set output end value with trim potentiometer R33 Set A
Siemens 7KG6106, SIMEAS-T - Transducer with auxiliary power 24 Contact Please talk to your Siemens contact (http://www.siemens.com/automation/partner) at one of our agencies or local offices if you have any questions about the products described here and do not find the answers in this manual. Technical Support: Siemens Industry Online Support You can contact Technical Support for about the products described as follows: • Telefon: + 49 (0) 911 895 7222 • E-Mail (
Siemens 7KG6106, SIMEAS-T - Transducer with auxiliary power 10 6 Technical specifications General input transducer Only for connecting to alternating voltage systems! Maximum voltage to earth 500 V ~ Power consumption of the measuring circuit approx. 0.06 VA Permissible modulation range 1.2 I EN or 1.2 U EN Rated frequency fEN 50 Hz, 60 Hz Frequency range fE 45 Hz to 65 Hz Curve form Sine, square, triangle, phase control Crest factor i/Ieff ≤ 2, but I ≤ 2.1 IEN T/U EN I ≤ 2, but ≤ 2.1 I EN Input transducer Alternating current Standard rated currents IEN See ordering table Measur
SIMEAS-T - Transducer with auxiliary power 22 Transducer with expanded start range and suppressed end range Example: Transducer with range: 0 to 0.05 to UEN ≙ 0 to 0.8 to AN Basic settings R32: Stop left R33: Stop right Break point Feed UE = 0.05 UEN ± 0.05% UEN , set the output value with trim potentiometer R51 Set A = 0.8 AN ± 0.05% AN. T
Siemens 7KG6106, SIMEAS-T - Transducer with auxiliary power 12 Safety in accordance with DIN EN 61010 Part 1 Overvoltage category III Degree of pollution 2 Fire resistance class V-0 electrically isolated Dielectric strength (test voltage) with type test – input relative to output – input relative to auxiliary power – output relative to auxiliary power U eff = 5.5 kV, 50 Hz, sine U eff = 5.5 kV, 50 Hz, sine Ueff = 3.7 kV, 50 Hz, sine Electromagnetic compatibility Emitted interference according to EN 50081-1 – Radio interference field st
Siemens 7KG6106, SIMEAS-T - Transducer with auxiliary power 20 Test circuit for voltage and current transducers (example for current output). 1 Alternating voltage encoder (THD ≤ 1%) 0 to 600 V or Alternating current encoder (THD ≤ 1%) range 0 to 10 A 2 Voltmeter, class 0.01 (for voltage input) 3 Ammeter, class 0.01, Ri ≤ 0.1 Ω (for current input) 4 Test specimen, voltage or current transducer 5 Decade resistor 0 to 20 kΩ 6 Ammeter, class 0.01, Ri ≤ 10 Ω 7 Alternating and direct voltage en
Siemens 7KG6106, SIMEAS-T - Transducer with auxiliary power 15 Continued: Ordering data for alternating voltage (G) MUU Name Order no. Code Device 7KG 6 1 0 6 - - B ↑ ↑ │ │ Auxiliary power │ │ 24 to 60
Siemens 7KG6106, SIMEAS-T - Transducer with auxiliary power 17 10 Mounting and operation WARNING! When electrical devices are operated, certain parts necessarily conduct dangerous voltages. Failure to heed the operating notices can therefore lead to serious injury or property damage. The device should only be mounted and electrically connected by appropriately qualified personnel. In particular, all warning notices must be observed. 10.1 Installation • Before installing the device, check for extern
SIMEAS-T - Transducer with auxiliary power 8 3 Performance characteristics • High measuring precision • Powerful output signal circuits • High system safety and reliability • CE mark • High immunity to EMC interference • Compliance with relevant national and international standards • Electrical isolation at a high test
Siemens 7KG6106, SIMEAS-T - Transducer with auxiliary power 13 8 Description The transducers in the enclosure are permanently wired and tested functional units. They have a snap-on mounting for a 35 mm standard mounting rail according to DIN EN 50022. Inputs and outputs can be safely connected to the screw terminals. The devices are silicone-free, halogen-free and flame-resistant. Balancing potentiometers are accessible after the modules have been removed from the enclosure. Weight: approx. 0.33 kg Degree of protection: Enclosure: Terminals: DIN VDE 0470 T.1 / EN 60529 IP40 IP20 Connection: Screw terminals
Siemens 7KG6106, 1 Operating Instructions Operating Instructions Transducer with auxiliary power for alternating voltage or alternating current (RMS) with expanded start range with expanded end range with non-linear characteristic curve 7KG6106 and 7KG6113 Compact device for DIN rail mounting Operating Instructions A5E38679986B / RS-AB Operating Instructions SIMEAS-T s
SIMEAS-T - Transducer with auxiliary power 16 Ordering data for alternating current (G) MUI Name Order no. Code Device 7KG 6 1 1 3 - - 0 B ↑
Siemens 7KG6106, SIMEAS-T - Transducer with auxiliary power 19 13 Calibrating and testing WARNING! The work must be done in accordance with the specifications and performance instructions of accident prevention regulation VBG 4.0. in particular 8. "Permissible discrepancies while working on active parts". A suitable electrical tool must be used. The transducer has to be opened and the modules removed for calibration. After disconnecting the external electrical power cables, the enclosure cover is removed and the modules pulled out. The circuit from the following modules: • Measuring module G3493
Siemens 7KG6106, SIMEAS-T - Transducer with auxiliary power 9 4 Operating principle The transformer (1) transfers the input signal IE or UE to the effective value Direct voltage converter (2) which drives the output amplifier (4) via the expansion circuit (3). Fed by the auxiliary source (6), the output amplifier provides load- independent current IA or load-independent voltage UA proportional to the input value IE or UA . The protective circuit (5) protects the output against no-load and transient overvoltage. 5 Overview circuit diagram 1
Siemens 7KG6106, SIMEAS-T - Transducer with auxiliary power 18 Notes for the fuses to be used: For devices that are supplied with AC auxiliary energy, a 100 mA time-lag fuse according to IEC 60127-2 must be connected upstream in the control cabinet installation. Appropriate protection must be provided for the measuring circuits during the installation: • Current measuring circuits: the fuse must prevent the values presented in the table 6 Technical specifications from being exceeded. • Voltage measuring circuits: the fuse must limit the current to 100 mA, be suitably arranged and be easily accessible to the user. 10.3 Installation material Measurin
Siemens 7KG6106, SIMEAS-T - Transducer with auxiliary power 3 QUALIFIED PERSONNEL Unqualified intervention in the device/system or failure to heed the safety warnings in this manual can lead to serious injury or material damage. Therefore, only suitably qualified personnel are permitted to service this device/system. Qualified personnel in the sense of the safety-related notices in these operating instructions or on the product itself are persons who • are either familiar with the safety concepts of automation engineering as configuration personnel • or have been trained to handle automation engineering equipment as operating personnel and are familiar with
Siemens 7KG6106, SIMEAS-T - Transducer with auxiliary power 11 Auxiliary power U H Rated input voltage UHN – Direct voltage – Alternating voltage 24-60 V; 110-220 V 100; 115; 230 V ~; 50/60 Hz Input range – Direct voltage – Alternating voltage ± 20% ± 20% Power consumption – Direct voltage – Alternating voltage with U H = U HN ; typical value 3 W 3 VA Errors and influencing effects The relative error information with signs "+" and "-" Errors in reference conditions 0.3% relative to A N Reference conditions – Input current I E – Input voltage UE – Frequency fE – Curve for
Siemens ST-H Series Transducer Operation manual
ST-H Series |
Siemens Echomax XCT Series Transducer Operation manual
Echomax XCT Series |
Siemens 7XV5653-0BA00 Transducer Manual
7XV5653-0BA00 |
Siemens 7XV5653-0BA00 Transducer Operating instructions manual
7XV5653-0BA00 |
Siemens XPS Transducer Operating instructions manual
XPS |
Siemens ERN 1387 Transducer Assemble & disassemble
ERN 1387 |
Siemens XPS10 Transducer Operating instructions manual
XPS10 |
Siemens SIMEAS-T 7KG6111-2LK11-0B Transducer Operating instructions manual
SIMEAS-T 7KG6111-2LK11-0B |
# | Manufacturer | Model | Document Type | File | Updated | Pages | Size |
---|---|---|---|---|---|---|---|
1 | ProForm | 795 Treadmill | Manual | proform/795-treadmill-84A.pdf | 19 Feb 2024 | 36 | |
2 | Extreme Networks | Altitude 4700 Series | Installation manual | extreme-networks/altitude-4700-series-3EQ.pdf | 03 Sep 2023 | 68 | 1.71 Mb |
3 | ESP | REKHDC36FBG | Operation & user’s manual | esp/rekhdc36fbg-1J9.pdf | 26 Mar 2024 | 4 | |
4 | Wonde Proud | WondeX SPT 100 Series | Operation & user’s manual | wonde-proud/wondex-spt-100-series-684.pdf | 14 Jul 2022 | 7 | |
5 | Gaggia | PLATINUM SWING UP | Operation and maintenance manual | gaggia/platinum-swing-up-N13.pdf | 17 Jul 2023 | 55 | |
6 | Loewe | Art 37 LED | Operating instructions manual | loewe/art-37-led-SKL.pdf | 31 Jan 2023 | 72 |
Airmar
17-467-01 rev.04 09/08/11In-Hull, 2-3kWTransducerModels: R199, R299, R399R111LH, R111LM, R599LH, R599LMU.S. Patent No. 7,369,458. UK Patent No. 2 414 077. U.S. Patent PendingTools & MaterialsSafety gogglesDust maskWrench: 9/16" wrenchRopeDetergent (some installations)Weak solvent (such as alcohol)Disk sander (some installations)Thin sealable plastic …
R199(4 pages) |
novotechnik
LWG/LWX GebrauchsanleitungLWG/LWX ManualArtikelnummer / Item number: 515533/09 Änderungen vorbehalten / Subject to change without notice 2012/071Allgemeine BeschreibungDie Baureihe LWG/LWX ist ein potentiometrischer Wegaufnehmer für die direkte, genaue und absolute Messung von Wegen bzw. Längen in der Steuerungs-, Regelungs- und Messtechnik.2Sicherheitsh …
LWG Series(2 pages) |
Siemens
MICROMASTER 440 GXEdition 12/02© Siemens AG, 2002, Subject to change without prior notificationMaintenance Instructions Fan132,0 kW MLFB: 6SE6440-2UD41-3GA1 MLFB: 6SL3362-0AG00-0AA1160,0 kW MLFB: 6SE6440-2UD41-6GA1 MLFB: 6SL3362-0AG00-0AA1200,0 kW MLFB: 6SE6440-2UD42-0GA1 MLFB: 6SL3362-0AG00-0AA1MICROMASTER 440 FanSiemens AGAutomation and Drives (A&D)S …
MICROMASTER 440 GX(2 pages) |
Rotronic
ROTRONIC AG, CH-8303 Bassersdorf, Tel. +41 44 838 11 44, www.rotronic.com • ROTRONIC Messgeräte GmbH, D-76275 Ettlingen, Tel. +49 7243 383 250, www.rotronic.de • ROTRONIC SARL, 56, F - 77183 Croissy Beaubourg, Tél. +33 1 60 95 07 10, www.rotronic.fr ROTRONIC Italia srl, I- 20157 Milano, Tel. +39 2 39 00 71 90, www.rotronic.it • ROTRONIC Instrumen …
CF1 Series(4 pages) |
Pribusin
Manufacturers of ProcessControls and InstrumentationInstruction ManualModel:Serial #:X=2: 4-20 mAX=3: 0-1 mAX=4: 10-50 mA117 VAC, 60 Hz, 6 VA24 VDC, 160 mAX=1: 1-5 mAOutput:X=5: 1-5 VDCX=6: 0-10 VDCX=7:Function: Isolated Watts TransducerCalibration:IUC-7X-WTYPower:(If special or required)Y=2: Dual ElementY=1: Single ElementInput:P.T.: / C.T.: :Full Scale Wat …
IUC-7X-WTX(6 pages) |
NK TECHNOLOGIES
INSTRUCTIONS1. Run the wire you are monitoring through aper-ture.2. Mount the sensor to a surface if needed.3. Connect output wiring.A. Use up to 14 AWG 75/90˚ C copper wires. B. Make sure output load does not exceed product specifi cations.C. Connect 24 VDC power supply and load in series.4. Select RangeA. Chose correct range by positioning the Ra …
AT 2 Series(2 pages) |
Philips DVD Player DVP3560K/93Philips DVP3560K/93 User Manual (Operation & user’s manual), @Q238L3 DVP3560K/93, 21 |
ENERGY SISTEM Remote Control Unniversal 4100#2TO572 Unniversal 4100: ENERGY SISTEM Remote Control Owner Documentation Unniversal 4100, 25 |
Palm PDA TXPDA #57833L TX, 2 |
Uplogix Switch 500Switch PDF Startup manual 500, 23 |
Philips Flat Panel TV 50PF973ID#6E3922: 50PF973ID Flat Panel TV Specification sheet 50PF973ID, 3 |
Samsung LCD TV LW32A23WSamsung LCD TV LW32A23W Connecting manual LW32A23W, 5 |
Lumens Document Camera CL510Operation & user’s manual for Lumens CL510 Document Camera CL510, 42 |
Saeco Coffee Maker 10002574Operating instructions manual for Saeco 10002574 Coffee Maker 10002574, 72 |
Conair Clock Radio TCR500Conair Product Manual: TCR500 PDF Owner's manual - 996F84 TCR500, 5 |
Fisher-Price Baby Accessories C7050#LZ9Z27: C7050 Baby Accessories Instructions manual C7050, 8 |
Gearmore Log Splitter LS20EGearmore Log Splitter LS20E Assembly, parts & operator's manual LS20E, 31 |
Toyotomi Timer OM-180PDF User Guide (@6C2635), Toyotomi OM-180 Timer (10.02.2024) OM-180, 16 |