Text of Siemens FDCW221 User Guide:

  • Siemens FDCW221, Specifications Technical data for the radio gateway FDCW221 8 75 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 Battery Number of batteries 1 Voltage DC 9 V Type: Block / Li/MnO2 ULTRALIFE U9VL-J or EVE CR9V/P-S ● Capacitance 1200 mAh ● Service life >5 years Battery voltage monitored Yes Connections Detector line: ● Design Spring clips ● Cable cross section 0.2…1.5 mm 2 MC link: ● Design Plug connection Ambient conditions Operating temperature -10…+55 °C Storage temperature -30…+65 °C Air humidity ≤95 % rel. Protec

  • Siemens FDCW221, Specifications Technical data for the radio gateway FDCW221 8 74 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 8 Specifications 8.1 Technical data for the radio gateway FDCW221 You will find information on approvals, CE marking, and the relevant EU directives for this device (these devices) in the following document(s); see 'Applicable documents' chapter: ● Document 010087 Detector line Operating voltage DC 12…33 V Operating current Typ. 1 mA Maximum current connection factor 5 + n*1 (n=number of radio detectors) Quiescent current c

  • Siemens FDCW221, Planning Transmission field 4 45 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 4.3 Transmission field In the open, the field strength falls with a factor of 1/r², i.e. a doubling of distance in the open equates to a 6 dB increase in damping. In buildings, the factor in a first approximation is 1/r 5 , i.e. a doubling of distance means that damping increases by around 6 to 17 dB. The table below illustrates the relationship between distance and damping for the line of sight in the building: Distance [m] 40 30 25 20 15 10 5

  • Siemens FDCW221, Safety Safety instructions 2 13 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 2 Safety 2.1 Safety instructions The safety notices must be observed in order to protect people and property. The safety notices in this document contain the following elements: ● Symbol for danger ● Signal word ● Nature and origin of the danger ● Consequences if the danger occurs ● Measures or prohibitions for danger avoidance Symbol for danger This is the symbol for danger. It warns of risks of injury. Follow all measures identified by this symbol to avoid injury or death.

  • Siemens FDCW221, Commissioning Logging radio detectors on to the radio gateway 6 59 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 6.3 Logging radio detectors on to the radio gateway Radio detectors can log on to a radio gateway which has just started up or also be added to the existing configuration of a radio cell. In each case, the button in the radio gateway has to be pressed briefly to either change from the exited 'Scan mode for the basic channel' or from normal operation to configuration operation. The RadioSpy can be used to assist with configuration. The Reed contact can be activated instead of press

  • Siemens FDCW221, Structure and function Function 3 41 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 3.10.6 Status display on the radio smoke detector DOW1171 and on the radio base SMF6120 The radio smoke detector DOW1171 and the radio base SMF6120 have a status indicator. In configuration operation, the status indicator displays flash sequences to indicate the field strength. The status displays are listed in the following table: Flashing cycle of status indicator (red LED) / s (second) Meaning of flashing c

  • Structure and function Accessories for radio smoke detector DOW1171 3 33 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 3.8.5 Protective cage DBZ1194 ● To protect the devices against mechanical damage ● Can only be used in conjunction with the following accessories: ● Order no.: BPZ:4677110001 3.8.6 Designation plate DBZ1193A ● To identify th

  • Siemens FDCW221, Mounting/Installation Installing the radio base SMF6120 and manual call point SMF121 5 53 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 5.3 Installing the radio base SMF6120 and manual call point SMF121 Installing the radio base SMF6120 w Ensure that the radio base SMF6120 is connected to the radio gateway FDCW221 from its intended location. l Secure the radio base at a height of 1.3…1.6 m on a level surface using suitable screws. Use the mounting openings (1). Note the word 'TOP' on the radio base housing. Mounting openin

  • Siemens FDCW221, Commissioning Resetting the DOW1171 to d elivery status 6 64 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 Procedure: 1. Unscrew the radio smoke detector DOW1171 from the base. 2. Remove both batteries from the bracket and pull the clips out off the battery contacts. 3. Wait 10 seconds for the batteries to discharge. 4. Plug the clips back on to the two batteries and insert the batteries into the brackets. a The status indicator flashes three times repeatedly. 5. Press the 'New' log-on button until the status indicator only flashes once. 6. Screw the radi

  • Siemens FDCW221, Structure and function Function 3 42 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 3.10.7 Power supply Radio gateway FDCW221 The radio gateway is normally powered via the FDnet detector line. Should the mains voltage fail, the radio gateway is powered via the battery in the control panel. Brief open lines (<5 hours) on the detector line can be bridged by the 9 V lithium manganese dioxide batteries. DOW1171 radio smoke detector Power is supplied to the power supply via two 9 V lithium manganese dioxide batteries. Manual call point SMF121 and radio base SMF6120 Power is supplied to the m

  • Siemens FDCW221, Specifications Technical data for manual call point SMF121 and radio base SMF6120 8 77 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 8.3 Technical data for manual call point SMF121 and radio base SMF6120 You will find information on approvals, CE marking, and the relevant EU directives for this device (these devices) in the following document(s); see 'Applicable documents' chapter: ● Document 010087 The SMF6120 radio base may only be used as a replacement device in fire detection installations that were installed prior to April 1, 2011! Radio Number of radio detectors per radio gat

  • Siemens FDCW221, Commissioning Resetting the radio gateway to delivery status 6 62 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 6.6 Resetting the radio gateway to delivery status The radio gateway is reset to the delivery status if the existing configuration is to be deleted. For example, if the radio gateway is to occupy another basic channel. NOTICE Resetting the radio gateway to delivery status An existing configuration is deleted. ● Only reset the radio gateway to its delivery status if the existing c

  • Siemens FDCW221, About this document Revision history 1 12 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 The table below shows the published language versions with the corresponding modification index: Modification index en_-- de_-- fr_-- it_-- es_-- m X X X X X l X X X X X k – X – – – j – X – – – i X X X X X h X X X X X g – X – – – f X X X X X e – X – – – d X X – – – c X X – – – b X X X X X a X X X X X X = published – = no publication with this

  • Siemens FDCW221, Structure and function Accessories for the FDCW221 radio gateway 3 31 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 3.7.5 Radio test set DZW1171 ● For measuring the field strength in buildings ● Planning tool when setting up radio networks ● Two-part test unit: ● For details, see document 004446 ● Order no.: BPZ:5762200001 See also 2 Radio test set DZW1171 [➙ 47] 3.7.6 RadioSpy ● To assist with installing radio cells and analysis in the event of problems ● Components: ● Compatible with: ● For details, see A6V10229812 document ● Order no.: S24218-F65-A1 3.7.7 Cable ties 2.4

  • Siemens FDCW221, Safety Safety regulations for the method of operation 2 15 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 2.2 Safety regulations for the method of operation National standards, regulations and legislation Siemens products are developed and produced in compliance with the relevant European and international safety standards. Should additional national or local safety standards or legislation concerning the planning, mounting, installation, operation or disposal of the product apply at the place of operation, then these must also be taken into account together with the safety regulations in the product documentation. Electrical installations WARNING Electrical voltage

  • Siemens FDCW221, Commissioning Starting up the radio gateway 6 58 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 6.2 Starting up the radio gateway Before radio detectors can be logged on to the radio gateway, the radio gateway must be started up. WARNING Several radio gateways using the same basic channel The radio detectors communicate using several radio gateways. Faults or malfunctions will arise. ● Start up radio gateways one after in the same transmission field. If you want to start up several radio gateways, they have to be started up one after another in the same transmission field such that every radio gatew

  • Structure and function Function 3 37 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 3.10.2 Behavior in degraded mode Applicable for the FDnet: When the main processor of the fire control panel fails, the control panel works in degraded mode operation. Depending on the control panel type, the fire control panel can continue to perform the most

  • Siemens FDCW221, Saf ety Safety regulations for the method of operation 2 16 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 Testing the product operability ● Prevent the remote transmission from triggering erroneously. ● If testing building installations or activating devices from third-party companies, you must collaborate with the people appointed. ● The activation of fire control installations for test purposes must not cause injury to anyone or damage to the building installations. The following instructions must be observed: – Use the correct potential for activation; this is generally the potential of the building installation. – Only check contr

  • Siemens FDCW221, 3 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 Table of contents 1 About this document ............................................................................. 7 1.1 Applicable documents ................................................................................. 9 1.2 Download center ......................................................................................... 9 1.3 Technical terms .........................................................................................10 1.4 Revision history .........................................................................................11 2 Safety ..........................................

  • Siemens FDCW221, Maintenance / troubleshooting Replacing the glass plate on the manual call point SMF121 7 72 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 7.9 Replacing the glass plate on the manual call point SMF121 w A new glass plate is ready. w The manual call point SMF121 is installed on the radio base SMF6120. 1. Open the door using a suitable key. NOTICE! Keep the key in a safe place. 2. Remove the old glass pane. 3. Push the retainer (1) to the right. 4. Place the glass pane under the guide (2) and under the retainer (1). The glass pane is square-shaped and

  • Siemens FDCW221, Mounting/Installation Instal ling the radio base SMF6120 and manual call point SMF121 5 56 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 View inside manual call point SMF121 1 Reset slider 2 Alarm button See also 2 3.6 V lithium battery [➙ 34] 1 2

  • Siemens FDCW221, Planning Defining the place of mounting 4 47 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 4.4 Defining the place of mounting General restrictions/system limits Maximum number of radio detectors per radio gateway 30 Maximum distance between radio gateway and radio detector 40 m or 90 dB WARNING Several radio gateways using the same basic channel Faults or malfunctions will arise. ● Start up radio gateways one after in the same transmission field. If you want to start up several radio gateways, they have to be started up one after another in the same trans

  • Siemens FDCW221, About this document Applicable documents 1 7 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 1 About this document Goal and purpose This document describes the devices ● Radio gateway FDCW221 ● DOW1171 radio smoke detector ● Manual call point SMF121 ● Radio base SMF6120 and how to integrate the devices into the fire detection system FDnet. It contains all the information you'll need about setup, functions, planning, mounting, and commissioning. The SMF6120 radio base may only be used as a replacement device in fire detection installations that were

  • Structure and function Structure of the radio smoke detector DOW1171 3 24 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 3.2 Structure of the radio smoke detector DOW1171 Radio smoke detector DOW1171 with base DBW1171 1 DBW1171 base 2 DOW1171 radio smoke detector The radio smoke detector DOW1171 works in line with the scattered light principle. An infrared LED sends short

  • Structure and function Structure of the manual call point SMF121 and radio base SMF6120 3 27 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 3.3 Structure of the manual call point SMF121 and radio base SMF6120 Figure 1: Manual call point SMF121 and radio base SMF6120 1 Manual call point SMF121 2 Radio base SMF6120 The manual call point SMF12

  • Siemens FDCW221, Index 81 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 R Radio base Status indicator 41 Radio cell 18 Radio detector Logging on to the radio gateway 59 Radio module SPU60xx 22 Radio smoke detector Parameter sets 26 Smoke sensitivity 26 Status indicator 41 Radio test set 43 RadioSpy Tool 29 Recycling 79 Reed contact Magnet 23 S Short-circuit Line separator 38 Smoke sensitivity 26 Source language 8 Standards 75, 76, 77 Status indicator 41 Field strength 41 T Tool RadioSpy 29 Topology 38 Type

  • Structure and function Release Notes 3 19 | 82 Building Technologies 009865_m_en_ -- Fire Safety 2015-11-06 Features of the radio smoke detector DOW1171 ● Consistent response to different fires ● Dynamic analysis of the sensor signal in the radio smoke detector itself ● Built-in diagnosis algorithms with automatic selftest ● High degree of immunity tow

Related Products and Documents (Fire Alarms):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 Endress ESE 1304 DBG ES DIN Operating instructions manual endress/ese-1304-dbg-es-din-5S3.pdf 02 Jan 2024 88
2 Califone 2810 Specifications califone/2810-BDJ.pdf 24 Mar 2024 1
3 Balluff BNI IOL-104-S02-Z012 Operation & user’s manual balluff/bni-iol-104-s02-z012-O57.pdf 30 Jul 2023 34
4 Garmin 310 Quick reference manual garmin/310-J21.pdf 17 Jul 2023 2 0.71 Mb
5 Denon TU-6.5 Operating instructions manual denon/tu-65-X3X.pdf 17 Jun 2023 32
6 Musical Fidelity AMS50 Operation & user’s manual musical-fidelity/ams50-72D.pdf 09 Aug 2022 12

Similar Resources:

  • SLAT

    AES Series

    (48 pages)
    Code : 180160015Ba - NDU : NOT160016Ba Edition : 0719 NOTICE D'UTILISATION P 1 BEDIENUNGSANLEITUNG S 17 OPERATING INSTRUCTIONS P 33 NOTICE D’UTILISATION AES 150 W – 300 W …
  • enea

    ED100

    (4 pages)
    EneaAnalogue-addressable fire detectorsED100 - optical smoke detectorED200 - temperature detectorED300 - multicriteria detectorATTENTION!For information regarding device placement, coverage and method of installation, referto the established standard regulations and codes relating to Automatic fire-detectionsystems. Enea series detectors are compliant with E …
  • Kilsen

    KFP-CE4 Series

    (2 pages)
    P/N 501-415503-5-20 • REV 2.0 • ISS 08SEP11 1 KFP-CE4 Series Quick Operation Guide If you hear the buzzer Determine the cause of the buzzer If the buzzer is sounding and the Fire Alarm LEDs are flashing or steady, then it’s a fire alarm. WARNING: Depending on your fire alarm system configuration, the buzzer may be your first indication of a fire ala …
  • Edwards Signaling

    517T Series

    (6 pages)
    P/N 550-0171-002 © 2001CHESHIRE, CT 203-699-3300 FAX 203-699-3365517T, 517TH & 517TC Series Photoelectric TypeSingle Station/Multi-Station Smoke AlarmsAC Powered, 120V 60 HzINTRODUCTIONThe 517T Series Smoke Alarm is a Photoelectric Type Alarm for use asan evacuation device. Each alarm has a solid state piezo that emits a temporal3 signal to warn and …
  • Siemens

    DOW1171

    (8 pages)
    Building TechnologiesFire Safety & Security Products DOW1171 DBW1171 en Radio smoke detector Base de Funk-Rauchmelder Sockel fr Détecteur de fumée hertzien Embase es Detector de humos inalámbrico Zócalo it Rivelatore di fumo wireless Base en de fr es it Installation Montage Montage Montaje Montaggio 12 Fig. 1 500 mm20 mm2 34 Fig. 2 …
  • Siemens

    FDOOT221

    (130 pages)
    007004_n_en_-- Building Technologies01.07.2012 Control Products and Systems FDOOT221, FDOOT241-A3, FDOOT241-A4, FDOOT241-8, FDOOT241-9, FDOOT241-A9, FDO241, FDO221, FDT241, FDT221 Automatic fire detectors Technical Manual …

Comments, Questions and Opinions: