  • 10/80 Siemens Building Technologies Commissioning Guide CM1G5192en HVAC Products 4 EMC-compatible installation of SED2 26.02.2003 4.4.2 Routing of cables • Lay cables of different power sections, such as control, mains and motor cables, separately • Avoid undesired coupling caused by parallel running control, power and motor cables • Lay control, mains and motor cables separ

  • Siemens SED2, 63/80 Siemens Building Technologies Commissioning Guide CM1G5192en HVAC Products 10 Parameterization 26.02.2003 Note: It is possible to disable all reverse commands (i.e. the command is ignored). To do this, set P0719=0 (remote selection of command / setpoint source) and define the command sources (P1113) individually. This function does not disable the "reverse" command function; rather, a reverse command causes motor to run in the normal direction as described above P1120 Ramp-up time Time taken for motor to accelerate from standstill up to maximum motor frequency (P1082) wh

  • Siemens SED2, 23/80 Siemens Building Technologies Commissioning Guide CM1G5192en HVAC Products 6 Commissioning 26.02.2003 5.5 RS-485 shielding and grounding Hand Auto SED 2 0 I P Fn P(1) Hz 3029 SED2 +ve -ve RS485 2 Hand Auto SED2 0 I P Fn P(1) Hz 30 29 SED2 2 Hand Auto SED 2 0 I P Fn P(1) Hz 30 29 SED2 2 RS485 RS485 RS485 1 30 29 2 1 R2=470Ohm R1=1KOhm 0 V Building Management System (BMS) Shielding Shielding Shielding Earth Compensating Cable Termination on the last drive in the network 5192Z46en Recommended data ca

  • Siemens SED2, 20/80 Siemens Building Technologies Commissioning Guide CM1G5192en HVAC Products 5 Electrical installation 26.02.2003 Connection terminals of SED2 frame size F, IP20, with built-in EMC filter PE L1 L2 L3 L1 DC+ B DC+ B UV L2 L3 W DC- B- DC+ R+ View without cable entry guide and without lower terminal connection plate Mains voltage inputs EMC filter 5192Z09en 5.2.6 Tightening torque for connection terminals Frame size ABCD E F Tightening torque Nm 1.1 1.5 2.25 10 (max.) 10 (max.) 50 5.2.7 Dimensions of the cable entries in the gland plates of SED2 IP20 Fr

  • 54/80 Siemens Building Technologies Commissioning Guide CM1G5192en HVAC Products 10 Parameterization 26.02.2003 Note: 100% means: Z rated motor = P0304 (rated motor voltage) P0305 (rated motor current) P0400 Select encoder type Selects encoder type Unit: - Min: 0 Def: 0 Max: 12 Level 3 Settings: 0=disabled 1=Single channel encoder 2=Quadrature encoder without zero p

  • Siemens SED2, 39/80 Siemens Building Technologies Commissioning Guide CM1G5192en HVAC Products 7 Application examples 26.02.2003 7.8 Application example 8 Condenser tower shall be controlled with the help of the integrated PID controller. − ON / OFF by LLSV relay interlock − QBE620 for pressure control − Indication of operation via relay output 2 Hand Auto SED2 0 I P Fn P(1) Hz L1 L2 L3 PE L1 L2 L3 20 9 5 3 2 SED2 uvw M 3 21 22 23 24 25 6 M UG Fuses Building Management System (BMS) Inspection switch 5192A08en Error Com Run Com Relay 1 Relay 2 status to compressor start circuit LLSV relay interlock QBE620-P25 HP sensor 28 Pump Notes: When the chiller

  • Siemens SED2, 45/80 Siemens Building Technologies Commissioning Guide CM1G5192en HVAC Products 9 Error messages 26.02.2003 Error Cause Diagnosis and troubleshooting Res- ponse F0060 ASIC timeout Ø Internal communication error If error reappears, contact customer service Off2 F0070 CB setpoint fault Ø No setpoints from CB (communications board) during telegram off time Check communications module (CB) and communica- tions partner Off2 F0071 USS (BOP link) setpoint fault Ø No setpoints from USS during telegram off time Check communications to data transmission module. Check USS master Off2 F0072 USS (COM link) setpoint fault Ø No setpoints

  • Siemens SED2, 47/80 Siemens Building Technologies Commissioning Guide CM1G5192en HVAC Products 9 Error messages 26.02.2003 Error Cause Diagnosis and troubleshooting Re- sponse A0912 Vdc (min) con- troller enabled Ø Vdc min controller enabled if the DC link volt- age (r0026) drops below the min. value (P2172) Ø The motor's kinetic energy is used to buffer the DC link voltage and thus slow the VSD Ø Temporary supply failures do not automatically lead to undervoltage shutdown -- A0920 ADC parameters not set properly Ø ADC parameters must

  • Siemens SED2, 31/80 Siemens Building Technologies Commissioning Guide CM1G5192en HVAC Products 7 Application examples 26.02.2003 7.2 Application example 2 A motor shall run at 4 fixed speeds. − Control is accomplished via digital inputs − Error message via relay output 1 − Indication of operation via relay output 2 Note: With the settings for this application example, the assumption is made that the parameters use their de- fault values and that the connected motor has been commissioned with the standard parameters. If sever

  • Siemens SED2, 15/80 Siemens Building Technologies Commissioning Guide CM1G5192en HVAC Products 5 Electrical installation 26.02.2003 5.2.3 Access to connection terminals: Frame sizes D…F IP20 Removing the operator panel (BOP or AOP) Opening the housing: Frame sizes D and E 3 1 2 5 6 4 5 1 9 2 J 1 3 Opening the housing: Frame size F 2 3 4 1 5 1 9 2 J 1 4 5 6

  • Siemens SED2, 35/80 Siemens Building Technologies Commissioning Guide CM1G5192en HVAC Products 7 Application examples 26.02.2003 7.5.1 Parameter changes Start with quick commissioning according to application example 1 Par. no. Value Parameter function Function selection P0701(0) 16 Fixed setpoint (Direct selection + ON) P0702(0) 29 Function of digital input 2 in “Auto” mode In the event of an external alarm, fan will be stopped P0702(1) 29 Function of digital input 2 in “Hand” mode In the event of external alarm, fan will be stopped P0703(0) 15 Function of digital input 3 Fixed setpoint P0756(1) 1 Defines analog input 2 DC 0...10 V (default) P0757(1) 0 Scaling of

  • Siemens SED2, 24/80 Siemens Building Technologies Commissioning Guide CM1G5192en HVAC Products 6 Commissioning 26.02.2003 6.1 DIP switch settings Location of the DIP switches For all versions of the SED2, the DIP switches used to configure the analog in- puts are located on the I/O module. The I/O module is located under the operator panel, to which it is connected either directly (frame sizes A…C, IP20) or via a cable (frame sizes D…E, and all IP54 models). 20 21 22 23 24 25 29 3017 26 27 2812 13 14 15 16 10 116

  • 43/80 Siemens Building Technologies Commissioning Guide CM1G5192en HVAC Products 9 Error messages 26.02.2003 9 Error messages 9.1 Error code list Error Cause Diagnosis and troubleshooting Res- ponse F0001 Overcurrent Ø Motor power (P0307) is greater than VSD power (P0206) Ø Motor lead short-circuit Ø Earth faults Check the following: 1. Motor power (P0307)

  • Siemens SED2, 78/80 Siemens Building Technologies Commissioning Guide CM1G5192en HVAC Products 11 Appendix 26.02.2003 11 Appendix 11.1 Applicable standards European low-voltage guideline The SED2 product range corresponds to the requirements of the low-voltage guideline 73/23/EEC, supplemented by guideline 98/68/EEC. The devices have been certified to the following standards: EN 60146-1-1 Semiconductor inverters – General requirements and line com- mutated inverters EN 60204-1 Safety of machinery – Electrical equipment of machines European guideline for machin

  • Siemens SED2, 32/80 Siemens Building Technologies Commissioning Guide CM1G5192en HVAC Products 7 Application examples 26.02.2003 7.3 Application example 3 Temperature control: Cooling − When the demand for cooling increases, the fan will increase its speed − Switching on / off via digital input 1 (thermostat), on temperature rise ON − External alarm to digital input 2 (e.g. fire alarm); fan stops in the event of an alarm − Error message via relay output 1 − Indication of operation via relay output 2 Hand Auto SED2 0 I P Fn P(1) Hz L1 L2 L3 PE L1 L2 L3 20 9 5 11 2 SED2 uvw LG-Ni 1000 M 3 21 22 23 24 25 6 Fuses Building Manage

  • Siemens SED2, 6/80 Siemens Building Technologies Commissioning Guide CM1G5192en HVAC Products 2 Introduction 26.02.2003 2 Introduction 2.1 General These are the Operating Instructions for the SED2 and are to be used for quick and simple commissioning. For more details and the complete parameter list for specific applications, consult the relevant Reference Manual. The SED2 range comprises VSDs for controlling the speed of fans and pump motors. The SED2 can also be pro- grammed to manage many other motor functions and limits. These functions are set by parameters, which are programmed using the operator panel. 2.1.1 Types of system contr

  • Siemens SED2, 60/80 Siemens Building Technologies Commissioning Guide CM1G5192en HVAC Products 10 Parameterization 26.02.2003 Bit12 Motor holding brake active 0 NO, 1 YES Bit13 Motor overload 0 YES, 1 NO Bit14 Motor runs direction right 0 NO, 1 YES Bit15 VSD VSD overload 0 YES, 1 NO P0970 Factory reset P0970 = 1 resets all parameters to their default values Unit: - Min: 0 Def: 0 Max: 1 Level 1 Settings: 0=Disabled 1=Parameter reset Dependency: First set P0010=30 (factory settings) Stop VSD (i.e. disable all pulses) before you can reset parameters to default values Note: The following parameters retain their values af

  • Siemens SED2, 17/80 Siemens Building Technologies Commissioning Guide CM1G5192en HVAC Products 5 Electrical installation 26.02.2003 Terminal layout: Frame size F DC+DC+DC+DC- B- R+ B+ B+ L3 U V WL2L1 PE 5192Z08 5.2.5 Power connection for VSDs with a built-in EMC filter Power connection to the footprint filter for frame sizes A…C The SED2 with frame sizes A, B, and C are delivered with built-in ready wired EMC footprint filters. Route the power supply to the terminals of the preinstalled footprint filter. L 2 L 3 L 1 Incoming mains voltage Ground Filter output 5192J15en Filter

  • Siemens SED2, 77/80 Siemens Building Technologies Commissioning Guide CM1G5192en HVAC Products 10 Parameterization 26.02.2003 Continued: Overview of factory and user parameter settings Parameter number User settings Factory settings Parameter number User settings Factory settings P2191 3.00 P2374 30 P2192 10 P2375 30 P2200 0.0 P2376 25.0 P2201 0.00 P2377 30 P2202 10.00 P2378 50.0 P2203 20.00 P2380 0 P2204 30.00 P2390 0 P2205 40.00 P2391 0 P2206 50.00 P2392 0 P2207 60.00 P3900 0 P2208 70.00 P2209 80.00 P2210 90.00 P2211 100.00 P2212 110.00 P2213 120.00 P2214 230.00 P

  • Siemens SED2, 42/80 Siemens Building Technologies Commissioning Guide CM1G5192en HVAC Products 8 Additional functions 26.02.2003 8.3 Hibernation mode Carry out quick commissioning and modify the parameters for normal operation, then proceed as follows: f 0% T1 T2 T3 T4 T5 Output [Hz ] P2392 Restart freq. P2390 Hibernation freq. Min. freq. P2391 Hibernation timer Hibernation mode Restart Drive frequency PID frequency max. hibernation (-) error [%] Time [s] Time [s] 5192D06en PID error [% ] Start with quick commissioning according to application example 1 Par. no. Value Parameter function Function selection P0003 3 User access level Expert access P2390 …% Hib

  • Siemens SED2, 26/80 Siemens Building Technologies Commissioning Guide CM1G5192en HVAC Products 6 Commissioning 26.02.2003 6.3 Buttons and their functions on the operator panel (BOP and AOP) Operator panel / button Function Effects Status display The LCD (5-digit display for BOP, multiline clear text display for AOP) shows the settings presently used by the VSD or used to parameterize the VSD). Start motor Pressing this button starts the VSD. This button is enabled for manual mode as part of the factory setting. Stop motor OFF1 Pressing this button stops the VSD within the selected ramp-down time. This button is enabled for manual mode as part of the factory settin

  • 33/80 Siemens Building Technologies Commissioning Guide CM1G5192en HVAC Products 7 Application examples 26.02.2003 7.4 Application example 4 The speed of a fan motor shall be controlled with the help of the integrated PID controller − Switching on / off via digital input 1 − External alarm to digital input 2; in the event of an alarm, the fan will be stopp

  • Siemens SED2, 37/80 Siemens Building Technologies Commissioning Guide CM1G5192en HVAC Products 7 Application examples 26.02.2003 Par. no. Value Parameter function Function selection P0758(1) 0 Scaling of analog input 2: y1 (Default) P0759(1) 10 Scaling of analog input 2: x2 (Default) P0760(1) 100 Scaling of analog input 2: y2 (Default) P2201 80 % Fixed setpoint of digital input 1 P2202 20 % Fixed setpoint of digital input 2 P2253(0) 2224 PID setpoint Fixed P2306 1 PID acting direction Indirect P2200(0) 1 Enable PID controller PID controller enabled P2280 10 PID proportional gain P2285 30 PID integral a

  • Siemens SED2, 9/80 Siemens Building Technologies Commissioning Guide CM1G5192en HVAC Products 4 EMC-compatible installation of SED2 26.02.2003 4.4 EMC-compatible wiring • Use only shielded cables for the motor. The shielding should have the lowest possible HF impedance and must be continuous • Use only shielded cables for the signal, control and data lines (shielded twisted pair) • The HF transfer resistance at the connecting points between shielding and housing should be kept as low as possible • Connect the shielding of motor and control cables to ground at both ends. For that purpose, use EMC cable fittings (EMC fittings, EMC cable clamps, EMC terminals and similar that ensure 36

  • Siemens SED2, 22/80 Siemens Building Technologies Commissioning Guide CM1G5192en HVAC Products 5 Electrical installation 26.02.2003 5.3.3 External motor overload protection During operation below nominal speed, the cooling effect of the fan fitted to the motor shaft is reduced. For this reason, most motors require derating if operated continuously at low frequencies. To ensure that motors are pro- tected from overheating under these conditions, they must have a built-in PTC temperature sensor or a Klixon thermal switch which is to be connected to the VSD control terminals 14 and 15 according to the diagrams shown here. 14 15 SED2 Control terminals 5192Z11en 15 1 k Ω Klixon N.C. 14 5192Z11en SED2

  • Siemens SED2, 36/80 Siemens Building Technologies Commissioning Guide CM1G5192en HVAC Products 7 Application examples 26.02.2003 7.6 Application example 6 Ventilation equipment shall be controlled with the help of the integrated PID controller. − Switching on / off via 2 digital inputs (application matched for 2 different setpoints via central control unit RWI65.02, load-dependent fan control) − External alarm via digital input 3; in the event of an alarm, fan will be stopped − Error message via relay output 1 − Indication of

Related Products and Documents (DC Drives):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 Zipato Zipabox Quick installation manual zipato/zipabox-7UJ.pdf 20 Jan 2023 4
2 Cambridge Audio Azur 840C Operation & user’s manual cambridge-audio/azur-840c-GSP.pdf 09 Aug 2022 22 0.63 Mb
3 Gigabyte GA-VT890P Operation & user’s manual gigabyte/ga-vt890p-E38.pdf 06 Jul 2023 96
4 Siemens MC60 Service manual siemens/mc60-G6Z.pdf 22 Oct 2022 37
5 Epson Stylus Photo RX600 Specifications epson/stylus-photo-rx600-VCV.pdf 16 Aug 2022 2 0.12 Mb
6 KitchenAid KBFO42FSX00 Installation instructions manual kitchenaid/kbfo42fsx00-J2P.pdf 05 Mar 2023 60

Similar Resources:

  • Mark 7

    Evolution

    (30 pages)
    MARK 7® RELOADING EVOLUTION USER MANUAL VERSION 2.0, COPYRIGHT 2020 ALL RIGHTS RESERVED 1 Mark 7® EvolutionTM User Manual V 2.0 Read this manual. Understand all safety and operating instructions. Failure to comply with the warnings and instructions may result in serious injury, illness or even death. …
  • YASKAWA

    A1000 -

    (257 pages)
    To properly use the product, read this manual thoroughly and retain for easy reference, inspection, and maintenance. Ensure the end user receives this manual.YASKAWA AC Drive-A1000High Performance Vector Control DriveQuick Start GuideType: CIMR-AUA MANUAL NO. TOEP C710616 41BModels: 200 V Class: 0.4 to 110 kW (3/4 to 175 HP ND)400 V Class: 0. …
  • Danfoss

    VLT AQUA Drive FC 200

    (175 pages)
    Low Harmonic Drive Operating Instructions MG20T202MAKING MODERN LIVING POSSIBLEVLT® Low Harmonic DriveOperating InstructionsVLT® AQUA Drive FC 200www.danfoss.com/drives *MG20T202*130R0504 MG20T202 Rev. 2011-12-19 …
  • Fuji Electric

    Frenic lift

    (35 pages)
    Starting guide Dedicated Inverter for Lift Applications 3 ph 400 VAC 2.2 – 45 kW 1 ph 200 VAC 2.2 – 4.0 kW SG_LM2A_EN_1.1.0 …
  • Magnetek

    Impulse G+ series 4

    (3 pages)
    OVERVIEWThe following procedure is a supplement to other documentation available for the IMPULSE•G+/VG+ Series 4 variable frequency drive (VFD). This will guide the user in proper installation and setup of the system.Before using the VFD-controlled equipment, the operator shall read the operating manual of the hoisting machine, shall be trained, and has to …
  • Allen-Bradley

    PowerFlex 755T

    (48 pages)
    Product InformationOriginal InstructionsATTENTION: Read this document and the documents listed in the Additional Resources section about installation, configuration and operation of this equipment before you install, configure, operate or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition …

Comments, Questions and Opinions: