  • AirStage AJY040LBLAH, EnglishDeutschFrançaisEspañolItalianoEλληvIkάPortuguêsРусскийTürkçe INSTALLATION MANUAL INSTALLATIONSANLEITUNG MANUEL D’INSTALLATION MANUAL DE INSTALACIÓN MANUALE D’INSTALLAZIONE ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ MANUAL DE INSTALAÇÃO РУКОВОДСТВО ПО УСТАНОВКЕ KURULUM KILAVUZU OUTDOOR UNIT AUSSENGERÄT UNITÉ EXTÉRIEURE UNIDAD EXTERIOR UNITÀ ESTERNA ΕΞΩΤΕΡΙΚΉ ΜΟΝΆΔΑ UNIDADE EXTERIOR ВНЕШНИЙ МОДУЛЬ DIŞ ÜNİTE For authorized service personnel only. Nur für autori

  • AirStage AJY040LBLAH, En-1 1. SAFETY PRECAUTIONS • Be sure to read this Installation manual thoroughly before installation. • The warnings and precautions indicated in this Installation manual contain important information pertaining to your safety. Be sure to observe them. • After installing the unit, perform a test run to make sure the unit operates normally. Then, explain to the customer how to operate and maintain the unit. • Please pass this Installation manual together with the Operating manual to the custom- er. Please ask the customer to keep the Operating man

  • En-2 CAUTION This mark indicates procedures which, if improperly per- formed, might possibly result in personal harm to the user, or damage to property. This unit must be installed by qualifi ed personnel with a capacity certifi cate for handling refrigerant fl uids. Refer to regulation and laws in use on installation place. The installation must be carried out in com

  • AirStage AJY040LBLAH, En-3 2.4. Optional parts CAUTION The following parts are optional parts specifi c to R410A refrigerant. Do not use parts other than those listed below. 2.4.1 Separation tube kit Separation tube uses the following parts. Separation tube Total cooling capacity of indoor unit (kw) UTP-AX054A ALL 2.4.2 Header Header uses the following parts. A header is used for connecting the indoor units. Header Total cooling capacity of indoor unit (kw) 3-6 Branches 3-8 Branches UTR-H0906L UTR-H0908L ALL 2.4.3 External connect kit Model Usage UTY-XW

  • AirStage AJY040LBLAH, En-4 3.3.1 Single outdoor unit installation When the upward area is open (Unit: mm) (1) Obstacles at rear only 150 (2) Obstacles at rear and sides only 200 300 200 (3) Obstacles at front only 1000 or more (4) Obstacles at front and rear only 1000 or more 150 When an obstruction is present also in the upward area (Unit: mm) (1) Obstacles at rear and above only 300 Max. 500 1000 (2) Obstacles at rear, sides, and above only 1500 250 250 500 Max. 500 3.3.2 Multiple outdoor unit installation •

  • AirStage AJY040LBLAH, En-5 Table. B (Diameter of piping used between outdoor unit and fi rst separation tubes or headers) MODEL Outdoor unit cool- ing capac- ity [kW] Diameter of piping [mm (in.)] Between outdoor unit and the farthest indoor unit < 90m *3 Between outdoor unit and the farthest indoor unit ≥ 90m *3 Liquid pipe Gas pipe Liquid pipe Gas pipe AJ*040LBLAH 12.1 9.52 (3/8) 15.88 (5/8) 9.52 (3/8) 19.05 (3/4) AJ*045LBLAH 14.0 9.52 (3/8) 15.88 (5/8) 9.52 (3/8) 19.05 (3/4) AJ*054LBLAH 15.5 9.52 (3/8) 19.05 (3/4) 9.52 (3/8) 19.05 (3/4) *3: Pipe Length: “a + f” or “a + p” of “4.1. SYSTEM CONFIGURATION” Table. C (Diameter of piping use

  • AirStage AJY040LBLAH, En-6 5. PIPE INSTALLATION 5.1. Brazing CAUTION If air or another type of refrigerant enters the refrigeration cycle, the internal pressure in the refrigeration cycle will become abnormally high and prevent the unit from exerting its full performance. Pressure regulating valve Cap Nitrogen gas Brazing area Apply nitrogen gas while brazing the pipes. Nitrogen gas pressure: 0.02 MPa (= pressure felt suffi ciently on the back of your hand) If a pipe is brazed without applying nitrogen gas, it will create an oxidation fi lm. This can degra

  • En-7 CAUTION Hold the torque wrench at its grip, keeping it in a right angle with the pipe, in order to tighten the fl are nut correctly. Outer panel may be distorted if fastened only with a wrench. Be sure to fi x the elementary part with a holding wrench (spanner) and fasten with a torque wrench (refer to below diagram). Do not apply force to the blank

  • AirStage AJY040LBLAH, En-8 6. ELECTRICAL WIRING 6.1. The precautions of electrical wiring WARNING Wiring connections must be performed by a qualifi ed person in accordance with specifi - cations. The rated supply of this product is 50 Hz, 230 V of 1-phase, 2-wire. Use a voltage within the range of 198 to 264V. Make sure to perform earthing (grounding) work. Improper earthing (grounding) work can cause electric shocks. Before connecting the cables, make sure the power supply is OFF. Be sure to install an earth (ground) leakage breaker. Otherwise, it will cause electric shock or fi re. Select a breaker (Included with earth leakage circuit breaker) of appropriate capacity a

  • AirStage AJY040LBLAH, En-9 6.4. Transmission line CAUTION Caution when wiring cable: When stripping off the coating of lead wire, always use the exclusive tool such as a wire stripper. If there is no exclusive tool available necessarily, carefully strip the coat- ing by a cutter etc. so that the conductive wire is not damaged. If it is damaged, it may lead to an open circuit and a communication error. Pay attention to the following points while attaching wires on the terminal board. • Do not attach 2 wires on one side. • Do not twist wires. • Do not cross the wires. • Do not short

  • AirStage AJY040LBLAH, En-10 6.5.2 Wiring procedure • Remove the service panel. And connect the cable to the terminal in accordance with the terminal name plate. • Use a ring terminal to connect the electric cables to the power supply terminal board. • Keep the earth cable longer than the other cables. • After connecting the electric cable, secure them with a cable clamp. • Connect the cable without applying excessive tension. • Use the specifi ed cable type and connect the cable securely. Secure with a cable clamp as shown in the fi gure below. Tightening torque M3 screw 0.5 to 0.6 N·m (5 to 6 kgf·cm) M5 screw 2.0 to 3.

  • AirStage AJY040LBLAH, En-11 Operation behavior Each input terminal works as follows. Connector Input signal Status Input1 CN131 (Yellow) OFF Normal operation ON Low noise mode operation Input2 CN132 (Green) *1 OFF Cooling priority ON Heating priority Input3 CN133 (White) OFF Normal operation ON Outdoor unit operation peak control Input4 CN134 (Red) OFF Normal operation ON Batch stop or Emergency stop operation *2, *3 Input5 CN135 (Orange) *4 No pulse No information from electricity meter Pulse Power usage information from electricity meter The operations of each input terminal and the selection of function are set with the push button on the PC board of outdoor unit. About the sett

  • AirStage AJY040LBLAH, En-12 24 (Forbidden) 2 4 0 0  (Factory default) 25 (Forbidden) 2 5 0 0  (Factory default) 26 (Forbidden) 2 6 0 0  (Factory default) 27 (Forbidden) 2 7 0 0  (Factory default) 28 (Forbidden) 2 8 0 0  (Factory default) 29 (Forbidden) 2 9 0 0  (Factory default) 30 Energy saving level setting *1 Level 1 (stop) 30 00  Level 2 (operated at 40% capacity) 01 Level 3 (operated at 60% capacity) 02 Level 4 (operated at 80% capacity) 03 Level 5 (operated at 100% capacity) 04 The capacity limit can be selected by the external input terminal (CN133) when operating with

  • AirStage AJY040LBLAH, En-13 73 Electricity meter pulse setting 2 *3 Setting number (00xx) 73 00  Setting number (01xx) 0 1 ······ ··· ··· Setting number (98xx) 9 8 Setting number (99xx) 9 9 Set the hundreds digit and thousands digit of the electricity meter pulse setting connected to CN135. 90 (Forbidden) 9 0 0 0  (Factory default) *1: Do not set this for outdoor units with Slave setting. *2: When electricity meter No. is set to “000” and “201 to 299”, the pulses input to CN135 become ineffective. Available setting number is "001

  • AirStage AJY040LBLAH, En-14 1: Function setting First 2 digits Last 2 digits (the display when the main power is turned on) (When [F4] to [F9] are displayed, continue to press the “SELECT” button until [F3] is displayed.) Automatic address setting for signal amplifi ers Press the “SELECT” button until “10” is displayed. Press the “ENTER” button for more than 3 seconds. Setting is complete when the number of units is displayed End 7.6. Indoor unit address setting 7.6.1 Indoor unit address setting Address must be set for the indoor unit. Manual

  • En-15 8. PIPE INSTALLATION II Fig. A Connection system Fig. B Outdoor unit Pressure gauge Vacuum pump Scale Pressure regu- lating valve Nitrogen Indoor unit Indoor unit Service hose with valve core Charging port Charging port cap 3-way valve Connecting pipe Blank cap Hexagon wrench 4 mm (5/32") Table . A Pipe 3-way valve Blank capCharging port cap Liquid valv

  • AirStage AJY040LBLAH, En-16 (1) Calculation of additional amount for pipe length A = Total length of ø 9.52 mm liquid pipe a × 0.058 (kg/m) + Total length of ø 6.35 mm liquid pipe a × 0.021 (kg/m) mm kg kg = Total kg (Round up A to 2 decimal place) (2) Calculation of total refrigerant amount C = A+B = kg (B : Factory charged amount) NOTE: Check the total refrigerant amount under the following conditions Condition Computational formula Total amount of refrigerant C ≤ 15.7 kg <Calculation> Outdoor unit: AJ*054LBLAH (1) Calculation of additional amount for outdoor unit If liquid pipe piping length is the

  • AirStage AJY040LBLAH, En-17 Test operation setting method Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons on the indoor unit PC board to confi gure settings according to the procedures below. Settings for starting test run operation Settings for stopping test run operation Press the “ENTER” button for more than 3 seconds. Press the “ENTER” button for more than 3 seconds. Press the “ENTER” button for more than 3 seconds. Press the “ENTER” button for more than 3 seconds. This will be dis- played when the cooling operation mode is canceled. This will be dis- played when the heating operation mode is canceled. This will be dis- played when the cooling

  • En-18 9.4. Checklist Check description Check method Criteria 1 High and low pressure values are normal. Check it with a pres- sure gauge. Cooling: low pressure ap- prox. 0.8 MPa Heating: high pressure approx. 3.0 MPa 2 Drain water is discharged smoothly through the drain hose. Check it by pouring water. ― 3 Indoor and outdoor unit fans are operating. Check th

Related Products and Documents (Air Conditioner):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 Best UP27I SERIES Installation instructions manual best/up27i-series-T1J.pdf 12 Aug 2022 16 4.18 Mb
2 Teac LP-R500 Owner's manual teac/lp-r500-326.pdf 26 Nov 2022 96 3.12 Mb
3 RCA VS2000 Operation & user’s manual rca/vs2000-739.pdf 19 Dec 2023 19 2.02 Mb
4 DXG DXG DXG-308 Operation & user’s manual dxg/dxg-dxg-308-193.pdf 12 Aug 2023 29 2.26 Mb
5 Visonic SR-730 PG2 Installation instructions visonic/sr-730-pg2-L1H.pdf 21 Sep 2022 4 1.4 Mb
6 AB Amps SUB 1850 Owner's manual ab-amps/sub-1850-68H.pdf 15 Apr 2023 13 0.65 Mb

Similar Resources:

  • Hitachi

    RAF50NH4

    (29 pages)
    SPLIT TYPE AIR CONDITIONER INDOOR UNITS/OUTDOOR UNIT RAD25QH4RAD40QH4ûCHRAF25NH4RAF50NH4RAM70QH4RAM80QH4RAM70QH4(MULTIZONE 70H)RAM80QH4(MULTIZONE 80H)RAF25NH4RAF50NH4RAD25QH4RAD40QH4 …
  • Mitsubishi Electric

    PKA-M-HA

    (268 pages)
    INSTALLATION MANUALFor safe and correct use, read this manual and the outdoor unit installation manual thoroughly before installing the air-conditioner unit.INSTALLATIONSHANDBUCHAus Sicherheitsgründen und zur richtigen Anwendung vor Installation der Klimaanlage die vorliegende Bedienungsanleitung und das Installationshandbuch gründlich durchlesen.MANUEL D� …
  • Tekno Point

    iCFV-xxC/H

    (34 pages)
    iCFV-xxC/H INSTALLATION MANUAL IDRA INVERTER Water cooled air conditioners IDRA INVERTER …
  • Carrier

    42C Series

    (132 pages)
    Copyright 2011 Carrier Corporation Form 42-7PDCarrier’s 42C,D,S,V Series fan coil units offer:• Design flexibility, occupying minimum space• Easy, low-cost installation• Permanent split capacitor motors deliver peak operating efficiency• High performance, low cost• Greater zone comfort controlFeatures/BenefitsCarrier’s extensive range of superi …
  • DeLonghi

    PAC 166

    (15 pages)
    4Important Safe-guardsWhen using electrical appliances, basic safety precautions should always be taken, withparticular reference to the following:- Read all instructions.-To protect against fire, electric shock and personal injury, do not immerse cable, plugor appliance in water or other liquid.- Close supervision is necessary when any appliance is used by …
  • LG

    Multi V ARNU153B1G2

    (2 pages)
    Date:JobName/Location:PONo.:Architect:Engr:GC:Rep:For:FileApprovalMech:ResubmitOther(Company)(ProjectManager)Tag#:ARNU153B1G2MultiV™Ducted(LowStatic)Btu/hIndoorUnitPerformance:CoolingNominalTestConditions: HeatingNominalTestConditions:Indoor:80°FDB/67°FWBOutdoor:95°FDBIndoor:70°FDBOutdoor:47° …

Comments, Questions and Opinions: