  • AEC 6KS, Introduction True Online 6-20k UPS User Manual 3 1. ELECTROMAGNETIC COMPATIBILITY * Safety IEC/EN 62040-1-1 * EMI Conducted Emission.........IEC/EN 62040-2 Category C3 Radiated Emission............IEC/EN 62040-2 Category C3 *EMS ESD..................................IEC/EN 61000-4-2 Level 4 RS....................................IEC/EN 61000-4-3 Level 3 EFT..................................IEC/EN 61000-4-4 Level 4 SURGE............................IEC/EN 61000-4-5 Level 4 Low Frequency Signals..............:IEC/EN 61000-2-2 Warning: This is a product for commercial and industrial application in the second env

  • Production Specification and Performance True Online 6-20k UPS User Manual 9 4. PRODUCT SPECIFICATION And PERFORMANCE 4.1 Model Description This manual is applicable to the following models: “L” Model: Long backup time 4.2 Product Specification and Performance 1. General Specification Model 6KS 6KL 10KS 10KL 15KL 20KL Power Rating 6KVA/5.4KW 10KVA/9KW 1

  • AEC 6KS, Controls and Indicators True Online 6-20k UPS User Manual 22 Display Function Submenu Output information Output information: Voltage, current, frequency, PF Load information: Active power, apparent power, percent Status of UPS Alarms, S-code, firmware version, system information Set and function Set: language, contrast, communication set(SNT, Modbus), Modbus set Function: function 1(transfer to bypass/escape, fault clear, mute on/off), function 2(battery test, maintenance test, stop test) History log / Rated capacity: 10KVA 1phase in/out: 1/1 / Input voltage / Battery voltage and capacity remained / Out

  • AEC 6KS, Installation True Online 6-20k UPS User Manual 15 charging. 1. The nominal DC voltage of external battery pack is 192VDC. Each battery pack consists of 16 pieces of 12V maintenance free batteries in series. To achieve longer backup time, it is possible to connect multi-battery packs, but the principle of “same voltage, same type” should be strictly followed. 2. For UPS 15KL/20KL, select the UL1015 6AWG(25mm 2 ) wire or other insulated wire which complies with UL Standard for the UPS battery wirings. The procedure of installing battery bank should be comp

  • AEC 6KS, Important Safety Instructions True Online 6-20k UPS User Manual 2 ELECTRICAL SHOCK OR FIRE. TO ENSURE SAFETY, OBSERVE THE FOLLOWING PRECAUTIONS: l Turn off and unplug the UPS before cleaning it. l Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners. l Never block or insert any objects into the ventilation holes or other openings of the UPS. l Do not place the UPS power cord where it might be damaged.

  • AEC 6KS, Installation True Online 6-20k UPS User Manual 13 6) For 15KL/20KL,connect the input 3 line wires to input A/B/C separately as fig.4. Or connect 1 input wire to input C. (a)Cables entry (b) Wiring connection Fig 4. Input and Output Terminal Block Wiring Diagram of 15KL/20KL NOTICE:You must make sure that the input and output wires and the input and output terminals are connected tightly. NOTICE: Please make sure that if there is a copper bar shorting input A/B/C terminal for UPS 15KL/20KL, or else you

  • AEC 6KS, Rated Parameters Set on LCD True Online 6-20k UPS User Manual 37 Annex C. EPO EPO is used to quickly cut off machine under emergerncy, the function is triggered by customer’s connector. By shorting common-open point NO with +24V, EPO function is effective. Far-away EPO connector denotation: Pins Name Denotation P1 + 24V +24V , the same connect points for NC and NO P2 EPO_NO EPO function is effective by Shorting common-open point NO and +24V

  • Controls and Indicators True Online 6-20k UPS User Manual 20 6. CONTROLS And INDICATORS Fig.8 Display Panel Description of Panel Controls Description ON/OFF 1.Press on/off to start inverter when rectifier is OK NOTE Not available when UPS is set in automatically start mode 2.Press on/off directly when there is no main input, press again to start UPS 3.Pre

  • AEC 6KS, Product Specification and Performance True Online 6-20k UPS User Manual 10 3. Operating Environment Temperature Humidity Altitude Storage temperature 0°C-40°C <95% <1000m 0°C-70°C NOTICE:If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated in use, please refer to the following: Altitude (M) 1000 1500 2000 2500 3000 3500 4000 4500 5000 Derating Power 100% 95% 91% 86% 82% 78% 74% 70% 67% Output Voltage Regulation Power Factor Frequency tolerance. Distortion Over

  • AEC 6KS, Installation True Online 6-20k UPS User Manual 16 Fig.5 communication cables connection 2) Strictly follow the stand-alone wiring requirement to perform the input wiring of each UPS. 3) Connect the output wires of each UPS to an output breaker panel. 4) Each UPS need an independent battery pack. 5) Please refer to the wiring diagram in the next page, and opt suitable breaker. ■ The requirement of the output wiring is as follows: ● When the distance between the UPSs in parallel and the breaker panel is less than 20 meters, the difference between the wires of input & output of the UPSs is required to be less than 20%. ● When the distance between the UPSs

  • AEC 6KS, Trouble Shooting True Online 6-20k UPS User Manual 34 Annex A. Rated Parameters Set on LCD 1. Power on LCD 2. Press button together for 3 seconds, enters in rated setting menu as below 3. Press button “ENTER” to activate setting function as below. Shadow means the current parameter can be set now. RATE SET OP IP FREQ HZ 50 V(LN) 220 V(LN) 220 50 220 230 4. Input voltage setting is activated. Press to select the rated input voltage. The voltages are available for customer such as: 110V, 120V, 127V, 200V, 208V, 220V, 230V, 240V. 5. Press “ENTER” button to confirm input

  • AEC 6KS, Introduction True Online 6-20k UPS User Manual 6 Fig 2. Rear View Function instructions: 1. SNMP card slot 2. Dry contactor slot 3. USB port 4. RS232 5. EPO 6. Parallel ports 7. Fans 8. Reserved customer function 9. External battery connector. Optional for standard model. 10. Internal maintenance bypass 11. Input breaker 12. Cable entry protector 13. Terminal cover

  • AEC 6KS, Controls and Indicators True Online 6-20k UPS User Manual 21 flicker--rectifier is starting, red--rectifier fault, red flicker--rectifier alarm, dark—rectifier is not working INV Inverter indicator: green--inverter is normal, green flicker--inverter is starting or tracking with bypass(ECO), red—inverter fault and load is not on inverter, red flicker—inverter fault and load is on inverter, dark—inverter is not working BYP Bypass indicator: green—bypass is normal, dark—UPS is in normal mode and bypass is normal, red—bypass fault, red flicker—bypass alarm BAT Bat

  • Operation True Online 6-20k UPS User Manual 25 To transfer the UPS to Maintenance Mode, the following procedures should be followed. 1. Check the status before the Maintenance Mode. Before transferring to the Maintenance Mode, the circuit breakers (CB) are in the following status: Input and Output are closed (in the on

  • AEC 6KS, Contents True Online 6-20k UPS User Manual 1 CONTENTS IMPORTANT SAFETY INSTRUCTIONS ......................................................................................... 1 1. ELECTROMAGNETIC COMPATIBILITY .................................................................................. 3 2. INTRODUCTION ............................................................................................................................. 4 3. SYSTEM DESCRIPTION ..........................................................................

  • 6-10KVA Rack-mount UPS User Manual Annex A. Intelligent Slot True Online 6-20k UPS User Manual 35 7. Press “ENTER” button to confirm frequency selection, and the current parameters are shown on LCD as below 8. Shutdown UPS completely and restart UPS to activate the setting. Enter in and enter in system information to check if the rated setting has

  • AEC 6KS, Installation True Online 6-20k UPS User Manual 11 5. INSTALLATION The system should be installed and wired only by qualified electricians in accordance with applicable safety regulations. NOTICE:UPS operation in sustained temperature outside the range of 15-25°C (59°-77°F) reduces battery life. 5.1 Unpacking and Inspection 1) Unpack the packaging and check the package contents. The shipping package contains: ● 1 UPS ● 1 user manual ●2 connectors(red and white)for battery with 4 contacts (6KL and 10KL) ● 2 cable entry protector (6K and 10K) 2)

  • AEC 6KS, Trouble Shooting True Online 6-20k UPS User Manual 31 Seq. Items 0 1 Solution installed. 32 16 Positive bus over voltage OK Fault UPS requires service 33 A2 1 Negative bus over voltage OK Fault UPS requires service 34 2 Fan Fault OK Fault At least one of fans fail. 35 3 Reserved 36 4 Reserved 37 5 Positive bus under voltage OK Fault UPS requires service 38 6 Negative bus under voltage OK Fault UPS requires service 39 7 Battery rev

  • AEC 6KS, Trouble Shooting True Online 6-20k UPS User Manual 32 Seq. Items 0 1 Solution 56 8 Bypass SCR or relay fault OK Fault UPS requires service. 57 9 Reserved 58 10 Reserved 59 11 BYP frequency over track range OK Fault Check if bypass input frequency is abnormal 60 12 Reserved 61 13 Reserved 62 14 Over load time out OK Fault 63 15 Reserved 64 16 Reserved 65 A4 1 Manual shutdown normal shutdo wn 66 2 INV protect OK Fault 67 3 Transfer times limit in one hour OK Fault Tra

  • AEC 6KS, Installation True Online 6-20k UPS User Manual 12 other insulated wire which complies with AWG Standard for the UPS input and output wirings. 4) For 15kL/20kL UPS, it is recommended to select the UL1015 6AWG(25mm 2 ) wire or other insulated wire which complies with AWG Standard for the UPS input wires and output wirings. It is better to use 3 wires (UL1015 10AWG) connecting input A/B/C separately from same source as fig.4. NOTICE:Do not use the wall receptacle as the input power source for the UPS, as its rated curr

  • AEC 6KS, True Online 6-20k UPS User Manual Battery Maintenance True Online 6-20k UPS User Manual 27 8. BATTERY MAINTENANCE The UPS only requires minimal maintenance. The batteries used for standard models are value regulated, sealed lead-acid, maintenance free battery. When being connected to the utility power, whether the UPS is turned on or not, the UPS keeps charging the batteries and also offers the protective function of overcharging and over-discharging. lThe UPS should be charged once every 4 to 6 months if it has not been used for a long time. lIn the regions of hot climates, the battery should be charged and discharged every 2 month

  • AEC 6KS, Trouble Shooting True Online 6-20k UPS User Manual 36 Annex A. Intelligent Slot There are two types of intelligent slot for option: DB9, phoenix terminator. Max output current for intelligent slot is 1A. The functions of intelligent slot are listed as fig.10: 2 6 1 784935 Fig.10 User wiring diagram of intelligent slot Description of intelligent slot: Pin NO. Function Description 1 UPS fail Pin1 to pin5 is NO(Normally Open) if something is failure in UPS. If not, NC(Normally Close) 2 General alarm Pin2 to pin5 is NO if something is abnormal. If not, NC 3 GND External power supply GND 4 Remote shutdown UPS shutdowns rectifier and inverter if

Related Products and Documents (UPS):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 La Crosse Technology TX10U Instruction manual la-crosse-technology/tx10u-1SJ.pdf 18 Aug 2023 9
2 Sony PCG-V505AC Specifications sony/pcg-v505ac-WDI.pdf 13 Jan 2024 2 0.04 Mb
3 Datavideo DAC-50 Quick start manual datavideo/dac-50-539.pdf 22 May 2023 20
4 ARX Quadcomp II Owner's manual arx/quadcomp-ii-6FD.pdf 16 Aug 2022 4 0.09 Mb
5 Manor 3200 - Winchester User instructions manor/3200-winchester-MS6.pdf 24 Jan 2023 12
6 Bosch SE352 Instructions bosch/se352-FV8.pdf 24 Feb 2023 3 0.26 Mb

Similar Resources:

  • Lamarche

    ODUPS

    (23 pages)
    La Marche Manufacturing Company www.lamarchemfg.com ODUPS Outdoor UPS Installation and Operation Manual This manual is subject to change without notice. You may obtain the newest version of the manual at www.lamarchemfg.com 106 Bradrock Dr. Des Plaines, IL 60018-1967 CPN 144266 …
  • ETILIZE

    UPS1500RM2U

    (44 pages)
    UPS 1500VA RACK MOUNT 2U 2-HE-USV MIT 1.500 VA ZUR RACKMONTAGE ONDULEUR À MONTAGE SUR RACK 2U, 1500VA UPS 1500VA - PARA INSTALACIÓN EN BASTIDOR - 2 UNIDADES UPS DA 1500 VA MONTAGGIO RACK 2U UPS 1500VA RACK MOUNT 2UUPS1500RM2U2U UPS 1500VA RACK MOUNT • 2-HE-USV MIT 1.500 VA ZUR RACKMONTAGE • ONDULEUR À MONTAGE SUR RACK 2U, 1500VA2 UNIDADES UPS 1500VA P …
  • Tripp Lite

    OmniSmart

    (24 pages)
    Owner’s Manual1111 W. 35th Street Chicago, IL 60609 USACustomer Support: (773) 869-1234 • www.tripplite.comImportant Safety Instructions2Quick Installation3Basic Operation4Storage & Service7Warranty Registration7OmniSmart™UPS SystemCopyright © 2006 Tripp Lite. All rights reserved. OmniSmart™ is a trademark of Tripp Lite.Español8Français16WAR …
  • Ablerex

    1 kVA

    (18 pages)
    1, 2, and 3 kVA Intelligent True On-Line UPS For Corporate and IT Users User Manual 1 Table of Contents 1. Safety and Storage Instructions ............................................................ 2 1.1. Safety ................................................................................................... …
  • iTrust

    Adapt

    (50 pages)
    iTrust Adapt UPS 20kVA User Manual Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center. Copyright © 2010 by Emerson Network Power Co., Ltd. All rights reserved. The contents in this document are subject to change without notice. Emerson Network Power C …
  • Sven

    Power Pro+ 1000

    (16 pages)
    ЛинейноинтерактивныйисточникбесперебойногопитанияÈÍÑÒÐÓÊÖÈß ÏÎ ýêñïëóàòàöèèPRO+ 1000/1500Перед эксплуатацией системы внимательно ознакомьтесь с настоящей инструкциейи сохраните ее на весь пери� …

Comments, Questions and Opinions: