  • Secutron MMX-2009-12NDS, Front Panel Menu Operation 26 Audible Test During this test, alarm activation of any input device will activate all signals for one half second. Trouble activation on any input device will activate all signals continuously for one second. If audio amplifier is configured for alarm and trouble events, it will sound words “Alarm” and “Trouble” respectively. Use and to scroll the cursor through the devices in the Walk Test list. Pressing the up/down keys will switch the view to display the Walk Test list. This view allows selection of the device to be tested. Note

  • Secutron MMX-2009-12NDS, Front Panel Menu Operation 30 Walk Test Report The Walk Test Report provides on screen and printer logs for both the One Man Walk Test and the Assisted Walk Test. To enter the Walk Test Menu, you must be in the Command Menu. To enter the Command Menu, press when the display is in normal mode. Walk Test Screen Report Step 5: Main Walk Test Screen During the Assisted Walk Test the display will be as shown. 1. Use and to scroll the cursor through the devices. A = number of Walk Test alarm events T = number of Walk Test trouble eventss D = number of duplicate events other than alarm and troubles R = number of remaining events from the Walk Test list Press to exit

  • Secutron MMX-2009-12NDS, MMX TM User Guide 15 For example, if you select loop two, the screen will appear as follows: • The first and second lines pinpoint the exact device. •The current level is a point of reference number that is helpful to our technicians. •The percent alarm shows how close the device is to going into alarm: 0% is the least likely, and 80% is the most likely. Verified Counts This option reports on any pre-alarmed devices that are set to verification mode. This report lists each time a device pre-alarms. If no devices are set to verification mode, then no report will display. Step 1: Select Verified Counts 1. Use and to scroll the cursor to “Verif

  • Secutron MMX-2009-12NDS, Front Panel Menu Operation 24 At this point the display will vary, depending on your choice: • If you selected “yes”, the display will either show the message “Input Zone bypassed” or “Input Zone unbypassed”, then return to the Command Menu. • If you selected “no”, the display will show the message “Operation cancelled” and will then return to the Command Menu. Unbypassing an active loop When you unbypass a input zone that went into alarm while it was bypassed, you will see the following message: If

  • MMX TM User Guide 41 Page to Alert LED Illuminates steady green when the Page to Alert pushbutton is active. AC ON LED This green LED illuminates steadily to Indicate that AC power is present. Page Ready LED Illuminates steady green when the push-to-talk (PTT) on the microphone is depressed (active). Lamp Test LED This amber LED illuminates steadily to indicate that t

  • Front Panel Menu Operation 38 8. Network Restart Use the Network Restart after downloading the MMX TM configuration. To select the Network Restart, you must be in the Comman Menu. To enter the Command Menu, press when the display is in normal mode. At this point the display will vary, depending on your choice: • If you selected “no”, the display sho

  • Secutron MMX-2009-12NDS, MMX TM User Guide 13 Alarm Log The Alarm Log reports on all alarm events. Alarm events are listed in order of the most recent event to the earliest. The maximum number of recorded alarm log entries is 1000. Once the system reaches 1000 entries, any new entry will cause 500 of the oldest entries to be deleted. At this point the display will vary, depending on whether or not a printer is connected to the panel. If a printer is not connected to the panel, the Alarm Log will print to the display. • Use and to scroll the cursor through the log. • Hold down for more information on the logged event. Press to exit to the Reports Menu. If a printer i

  • Secutron MMX-2009-12NDS, Front Panel Menu Operation 14 If a printer is connected to the panel, follow Step 2, below. Current Levels This option reports on the current levels of addressable devices. If you view the Current Levels on the screen, • Use and to scroll the cursor through the log. • Press and hold for more information on the current level. • Press to exit to the Reports Menu. Step 2: Print the Event Log •To print the Alarm Log to the printer, press when the cursor flashes beside “Printer”. •To view the Alarm Log on the screen, press then to select “Screen”. Follow the instructions

  • Secutron MMX-2009-12NDS, MMX TM User Guide 33 Alternate Menu Option #3: Manual Control Enable This option provides security on the panel control buttons by requiring the user to enter a passcode or activate a key switch before a specific button will operate. This “manual control” feature is set up using the Configurator, and can affect any number of control buttons. Selecting the Enable Required option in the Command Menu or turning the key switch allows you to activate and deactivate this feature. Selecting Manual Control Enable from the Menu To select the Enable Required option, you must be in the Comm

  • Secutron MMX-2009-12NDS, MMX TM User Guide 35 5. Set Time To enter the Set Time option, you must be in the Command Menu. To enter the Command Menu, press when the display is in normal mode. Note: Select this option if you would like to set the time only.You must use the Configurator to change the date. Step 1: Select Set Time 1. Press to select the Command Menu. 2. Use and to scroll the cursor to “Set Time”. 3. Press when the cursor flashes beside “Set Time” to select the Set Time option. Step 2: Enter your

  • Secutron MMX-2009-12NDS, Front Panel Menu Operation 36 6. Clear Event Log Select this option if you would like to clear the Alarm Log, Event Log, or all the logs. To enter the Clear Event Log option, you must be in the Command Menu. To enter the Command Menu, press when the display is in normal mode. Step 1: Select Clear Event Log 1. Use and to scroll the cursor to “Clear Event Log”. 2. Press to continue. Step 2: Enter your passcode (if required) Enter your passcode. See page 10 for instructions on entering passcodes. Step 3: Sele

  • Secutron MMX-2009-12NDS, MMX TM User Guide 27 Press or to switch to the Main Walk Test screen. Press to exit the Walk Test at anytime. Silent Test During this test, alarm and trouble activation of any input device will be recorded by the system but it will not sound the signals. For the system to register a trouble, you must keep the device in a trouble condition for 10 seconds. Step 5: Device View During the Walk Test During the Walk Test the device display will be as shown. A = total number of alarm events for the device. T = total number of trouble events for the device. Step 1: Sel

  • Secutron MMX-2009-12NDS, MMX TM User Guide 29 Assisted Walk Test Assisted Walk Test must be configured using the Configurator. When the Assisted Walk Test is configured, the One Man Walk Test is replaced by the Assisted Walk Test. The Assisted Wall Test shall be in silent mode only. To enter the Walk Test Menu, you must be in the Command Menu. To enter the Command Menu, press when the display is in normal mode. Step 1: Select the Walk Test Menu 1. Use and to scroll the cursor to “Walktest”. 2. Press to select the Walk Test Menu. Step 2: Enter your passcode (if required) Enter your passcode.

  • Secutron MMX-2009-12NDS, MMX TM User Guide i Table of Contents Introduction.............................................................................................................................. 1 About this Manual................................................................................................................. 1 Front Panel Indicators, Controls, and Operation.................................................................. 2 Front Panel Indicators and Control Locations (Model DSPL-420).............

  • Secutron MMX-2009-12NDS, MMX TM User Guide 21 2. Bypass Menu Use the Bypass Menu when you want to bypass or unbypass devices, hardware circuits, complete addressable loops, or outputs such as relays and signals. To enter the Bypass Menu, you must be in the Command Menu. To enter the Command Menu, press when the display is in normal mode. The following subsections provide instructions on using each Bypass Menu option. Step 3: Select Node • Select a Node by using and to scroll through the numbers, then when the correct Node number appears. Step 4: Pwr Src Report The battery vo

  • 12 Front Panel Menu Operation 1. Reports Menu Use the Reports Menu to print the Alarm Log, Event Log, Current Levels, Verified Counts, Maintenance report, Current PWs, Obscuration, CO Maintenance report, and Battery Voltage. You can view on screen, or print directly to a printer connected to the panel, or to your laptop computer. To enter the Reports Menu, you must be in the Co

  • Secutron MMX-2009-12NDS, MMX TM User Guide 1 Introduction About this Manual This user guide provides information on the Command Menu features of the MMX TM Network Fire Alarm and Audio system which includes MMX-2003-12NDS, MMX-2003-12NXTDS, MMX-2009-12NDS, and MMX-2017- 12NDS. Using the instructions provided in this manual, you will be able to: • Print reports • Bypass devices, circuits, loops, and disconnect relays • Perform a walk test • Change your passcode • Clear logs and counters • Set Day/Night mode

  • Secutron MMX-2009-12NDS, MMX TM User Guide 25 3. Walk Test Menu Use the Walk Test Menu when you want to test the devices in a system. Performing a walk test will place the system in trouble (non-latching). To enter the Walk Test Menu, you must be in the Command Menu. To enter the Command Menu, press when the display is in normal mode. The subsections following provide instructions on using each One Man Walk Test Menu option, Audible Test and Silent Test. Note: Walk test records that are viewed on the screen will be stored in the event log. Step 1: Select the Walk Test Menu 1. Use and to scroll the curs

  • Secutron MMX-2009-12NDS, MMX TM User Guide 11 Menu Mode Press the button to activate the menu mode. The menu is broken down as follows: Menu Submenu Description How to Use 1. Reports Alarm Log View or print the Alarm Log. See page 13. Event Log View or print the Event Log. See page 13. Current Levels View or print the Current Levels. See page 14. Verif. Count View or print the Verified Count. See page 15. Maint Report View or print the Maintenance Report. See page 16. Current PWs View or print Pulse Width Current Report See page 17. Obscuration View or print the obscuration values See page 18. CO Maint Report View or print CO detector Maintenance Report See page 19. Battery Voltage View or print Batte

  • Secutron MMX-2009-12NDS, MMX TM User Guide 23 Unbypassing an active device/circuit When you unbypass a device or circuit that went into alarm while it was bypassed, you will see the following message: If you select “yes” to unbypass this device, the system will immediately go into alarm. To avoid this problem, press the System Reset button before unbypassing a device or circuit. Relay Disconnect This option is useful if you want to disconnect or reconnect the aux relays. At this point the display will vary, depending on your choice: • If you selected “yes”, the display

More Instructions:

DOWNLOAD

Related Products and Documents (Fire Alarms):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 Advantech PPC-3100S Operation & user’s manual advantech/ppc-3100s-CXU.pdf 07 Dec 2023 63
2 Rinnai Brivis StarPro SP623UN Installation manual rinnai/brivis-starpro-sp623un-4V1.pdf 27 Dec 2023 52
3 Ferm FCHT-1800/2 Operation & user’s manual ferm/fcht-18002-Q8D.pdf 27 Jan 2023 32
4 Inter-m DPA-300S Operation manual interm/dpa-300s-R61.pdf 07 Dec 2023 20
5 Laser Products LT-2D3D Operation & user’s manual laser-products/lt-2d3d-6LV.pdf 08 Aug 2022 50
6 ASROCK 990FX Extreme4 Manual  asrock/990fx-extreme4-7NQ.pdf 17 Mar 2024 281

Similar Resources:

  • Faraday

    MPC-6000

    (56 pages)
    Siemens Building Technologies, Inc. 8 Fernwood Road • Florham Park, NJ 07932 Tel: (973) 593-2600 • Fax: (973) 593-6670 Web: www.faradayfirealarms.com P/N 315-049403FA-6 (3.23.06) MPC-6000 / MPC-7000 / RND-2 Fire Alarm System Control Unit Programming Manual …
  • teko

    Astra-45A

    (2 pages)
    Astra-45A Addressable hardwired fire manual call point User guide Manufacturer: ZAO NTC TEKO 420108, Russia, Kazan, Gafuri str., 71 Tel.:+7(843) 528-03-69 [email protected] www.teko.biz Made in Russia Rev. 45А-v2_0_instr_en 1 FUNCTION The addressable hardwired fire manual call point (further “Call Point” or “Ast …
  • Kentec Electronics

    Taktis

    (17 pages)
     !"#$$$$%&'$'� …
  • Tyco Fire Product

    TY-B Series

    (8 pages)
    http://www.tyco-reproducts.comPage 1 of 8 MARCH, 2007 TFP151_ENGeneral Description The Series TY-B, K40, K80 and K115 Upright and Pendent Sprinklers described in this data sheet are standard response - standard coverage, decorative 5 mm glass bulb type spray sprinklers designed for use in light, ordinary, or extra hazard, commerc …
  • Simplex

    4100ES

    (164 pages)
    Fire Australian Installation Manual 4100 ES Fire Indicator Panel Installation & Maintenance Australian Installation & Maintenance Manual LT0350 Iss 1.5 …
  • Wheelock

    ET Series

    (9 pages)
    P82483 E Sheet 1 of 7 273 Branchport Avenue Long Branch, N.J. 07740 (800) 631-2148 Thank you for using our products. www.wheelockinc.com INSTALLATION INSTRUCTIONS SERIES ET SPEAKERS AND STROBE SPEAKERS Use this product according to this instruction manual. Please keep this instruction manual for future reference. GENERAL: Wheel …

Comments, Questions and Opinions: