Siemens FDS229-A Technical Manual
|
1 Technical terms 7 Building Technologies 010095_j_en_-- Fire Safety 2013-02-22 1.2 Technical terms Term Explanation AI Alarm indicator FDnet/C-NET Addressable detector line ES Product version MC link Maintenance and commissioning link (proximity interface) 1.3 History of changes The reference document's modification index a
Siemens FDS229-A, 5 Mounting / Installation Base attachment FDB291 28 Building Technologies 010095_j_en_-- Fire Safety 2013-02-22 5.1 Base attachment FDB291 Use the base attachment FDB291 for surface-mounted cable entry and cable diameters between 6 mm and 21 mm. 1. Break out the required cable entries on the base attachment FDB291. 2. Insert the cables through the break-outs in the base attachment FDB291. Installation of detector base on base attachment FDB291 1 Identification 3
Siemens FDS229-A, 5 Mounting / Installation Detector locking device FDBZ293 34 Building Technologies 010095_j_en_-- Fire Safety 2013-02-22 5.6 Detector locking device FDBZ293 A detector or alarm sounder can be protected against theft with the detector locking device FDBZ293. Installation of detector locking device FDBZ293 A Sounder base or detector base acc. to 'Accessories' chapter C Detector locking device B Detector or alarm sounder 1. Insert the grub screw with a hexagon socket into
Siemens FDS229-A, 1 Applicable documents 6 Building Technologies 010095_j_en_-- Fire Safety 2013-02-22 Document identification The document ID is structured as follows: ID code Examples ID_ModificationIndex_Language_COUNTRY -- = multilingual or international A6V10215123_a_de_DE A6V10215123_a_en_-- A6V10315123_a_--_-- Conventions for text marking Markups Special markups are shown in this document as follows: Requirement for a behavior instruction Intermediate result of a behavior instruction End result of a behavior instruction �
Siemens FDS229-A, Annex technical data 9 Beam characteristics of the additional optical indicator 43 Building Technologies 010095_j_en_-- Fire Safety 2013-02-22 Tone No. 10: Slow-whoop Sweep-up, linear Sound intensity Horizontal Vertical 15° 45° 75° 105° 135° 165° 15° 45° 75° 105° 135° 165° 0 (max.) 90 97 100 100 97 91 90 97 99 99 96 90 1 (mid.) 82 88 92 92 88 82 81 88 90 90 86 82 2 (low) 70 77 79 79 76 71 70 76 79 78 76 70 Tone No. 11: Intermittent Sound intensity Horizontal Vertical 15° 45° 75° 105° 135° 165° 15° 45° 75° 105° 135° 165° 0 (max.) 90 9
Siemens FDS229-A, Mounting / Installation 5 Sealing kit FDBZ295 31 Building Technologies 010095_j_en_-- Fire Safety 2013-02-22 3. Push the connection wires through the rubber base from the rear. 4. Install the detector base. 5. Place a point detector or alarm sounder in the detector base. 6. Turn the point detector or alarm sounder to the right to screw it firmly into the detector base. 7. Screw the supplied set screw into the point detector or alarm sounder until it no longer protrudes. This step is not needed when using detector locking device FDBZ293. 8. Fold the folded-back sealing lip over the point detector or alarm sounder.
Siemens FDS229-A, 7 Maintenance / Repair Status query 36 Building Technologies 010095_j_en_-- Fire Safety 2013-02-22 7 Maintenance / Repair 7.1 Status query The alarm sounder with additional optical indicator FDS229 has a proximity interface (MC link). Using this interface, it is possible to read out data from the device in a proximity method over short distances with the detector exchanger and tester FDUD292 or the intelligent detector tester FDUD293. You will find more information in documents 007227 and 009718. Status queries with detector exchanger and tester FDUD292 or i
Siemens FDS229-A, 5 Mounting / Installation Configur ation 26 Building Technologies 010095_j_en_-- Fire Safety 2013-02-22 5 Mounting / Installation The alarm sounder with additional optical indicator FDS229 requires an addressed detector base. The detector base is mounted on the wall or on the ceiling. The device must be easily accessible for commissioning and maintenance so that it can communicate with the detector exchanger and tester FDUD292 or the intelligent detector tester FDUD293 via the interface (MC link). The alarm sounder with additional optical indicator FDS22
Siemens FDS229-A, 3 Structure and function Function 16 Building Technologies 010095_j_en_-- Fire Safety 2013-02-22 3.2.2 Line separator All FDnet/C-NET devices are equipped with a line separator. The FDnet/C-NET device is equipped with electronic switches which isolate the defective part in case of a short-circuit on the detector line. The rest of the detector line remains serviceable. On a loop line all FDnet/C-NET devices remain fully functional after a simple error. 3.2.3 Behavior in degraded mode Applicable for the FDnet/C-NET: When the main processor of the fire control panel fai
Siemens FDS229-A, Annex technical data 9 Beam characteristics of the additional optical indicator 45 Building Technologies 010095_j_en_-- Fire Safety 2013-02-22 9.2.2 FDS229-A, orange (32 VDC) Azimuth 0° 30° 60° 90° Elevation [°] [cd/60 s] [cd/pulse] [cd/60 s] [cd/pulse] [cd/60 s] [cd/pulse] [cd/60 s] [cd/pulse] -60 10 0.9 11 1.1 12 1.2 13 1.2 -30 16 1.5 19 1.8 16 1.5 19 1.8 0 14 1.3 14 1.3 14 1.3 13 1.3 30 15 1.4 19 1.8 15 1.4 18 1.7 60 11 1.0 13 1.2 11 1.0 8.5 0.8
Siemens FDS229-A, Commissioning 6 35 Building Technologies 010095_j_en_-- Fire Safety 2013-02-22 6 Commissioning The devices are commissioned via the control panel. The exact procedure is described in the control panel documentation. Conduct a performance check once commissioning is complete.
Specifications 8 Technical data 37 Building Technologies 010095_j_en_-- Fire Safety 2013-02-22 8 Specifications 8.1 Technical data Detector line Operating voltage DC 12…33 V Operating current: Standby 250 A Sound activated 3,5 mA Additional optical indicator activated 3,5 mA Sound and additional
1 Applicable documents 5 Building Technologies 010095_j_en_-- Fire Safety 2013-02-22 1 About this document Goal and purpose This document contains all necessary information on the alarm sounder with additional optical indicator FDS229. Following the instructions consistently will ensure that the product can be used safely and without any problems. Targ
Siemens FDS229-A, 2 Safety Safety regulations for the method of operation 10 Building Technologies 010095_j_en_-- Fire Safety 2013-02-22 How risk of injury is presented Information about the risk of injury is shown as follows: WARNING Nature and origin of the danger Consequences if the danger occurs Measures / prohibitions for danger avoidance How possible damage to property is presented Information about possible damage to property is shown as follows: NOTICE Nature and origin of the danger Consequences if the danger occurs Measures / prohibitions for danger avoidance 2.2 Safety regulat
Siemens FDS229-A, Structure and function 3 Function 15 Building Technologies 010095_j_en_-- Fire Safety 2013-02-22 3.2 Function 3.2.1 Escalation levels and volume The alarm sounder with additional optical display can be activated for the following selectable escalation levels: Warning (Alert) Evacuation (EVAC) The tone can be configured individually for the two selectable escalation levels; the sound intensity can be configured by device. Different tones are available, each with three sound intensities.
Siemens FDS229-A, 5 Mounting / Installation Sealing kit FDBZ295 30 Building Technologies 010095_j_en_-- Fire Safety 2013-02-22 5.3 Sealing kit FDBZ295 The sealing element FDBZ295 is used in conjunction with detector bases FDB2x1/FDB2x1-AA. The sealing element provides the device with protection against dirt and spray water. Installation of sealing kit FDBZ295 Installation The kit is installed by hand 1. Fold the sealing lip back. 2. Insert the detector base into the sealing kit. Make sure that the opening in the detector base lines up with the marking and opening on the rubber base. NOTICE Risk when piercing the rubber base wi
Siemens FDS229-A, Structure and function 3 Accessories 21 Building Technologies 010095_j_en_-- Fire Safety 2013-02-22 3.3.9 Detector locking device FDBZ293 For protection against theft Compatible with: – Point detectors from the 'Sinteso' product line – Alarm sounder FDS221 – Alarm sounder with additional optical indicator FDS229 – Sounder interbase FDSB221 – Sounder interbase with additional optical indicator FDSB229 Order no.: A5Q00005035 S
Siemens FDS229-A, Annex technical data 9 Tones and sound intensities of the alarm sounder (32 VDC) 41 Building Technologies 010095_j_en_-- Fire Safety 2013-02-22 9 Annex technical data 9.1 Tones and sound intensities of the alarm sounder (32 VDC) Sound intensity measured in dBA/1 m with -0/+4 dBA (32 VDC) Tone No. 1: Continuous Sound intensity Horizontal Vertical 15° 45° 75° 105° 135° 165° 15° 45° 75° 105° 135° 165° 0 (max.) 90 93 96 96 93 90 90 93 97 97 93 91 1 (mid.) 80 84 87 87 82 80 80 89 87 87 84
Siemens FDS229-A, Safety 2 Safety regulations for the method of operation 11 Building Technologies 010095_j_en_-- Fire Safety 2013-02-22 Route mains connections to products separately and fuse them with their own, clearly marked fuse. Fit an easily accessible disconnecting device in accordance with IEC 60950-1 outside the installation. Produce earthing as stated in local safety regulations. Assembly, installation, commissioning and maintenance If you require tools such as a ladder, these must be safe and
Siemens FDS229-A, 4 Project engineering Configuration 24 Building Technologies 010095_j_en_-- Fire Safety 2013-02-22 4.5 Configuration The following chapters contain the specifications of the different tones and optical indicators. 4.5.1 Alarm sounder No. Tone Frequency pattern Sweep from to Pulse pattern Adjustable sound intensity levels (typ. values in [dBA/1m] 1 ) Norm at 12 V at 32 V 1 Continuous 970 Hz 98 88 81 101 92 82 'evacuate' BS 5839 Par
DOWNLOAD |
Siemens SINAMICS S120 Security System Manual
SINAMICS S120 |
Siemens SINUMERIK 840D sl Security System Operating manual
SINUMERIK 840D sl |
Siemens SINUMERIK 802D sl Security System Programming and operating manual
SINUMERIK 802D sl |
Siemens SINUMERIK 840D sl Security System Configuration manual
SINUMERIK 840D sl |
Siemens SINAMICS S120 Security System Function manual
SINAMICS S120 |
Siemens SINAMICS S120 Security System Getting started
SINAMICS S120 |
Siemens MI291A Security System Maintenance manual
MI291A |
Siemens RB-6 L-801A Security System Manual
RB-6 L-801A |
# | Manufacturer | Model | Document Type | File | Updated | Pages | Size |
---|---|---|---|---|---|---|---|
1 | Makita | 9005B | Instruction manual | makita/9005b-OO1.pdf | 17 Jun 2023 | 16 | |
2 | Texas Instruments | RI-RU1-001A-00 | Reference manual | texas-instruments/ri-ru1-001a-00-H55.pdf | 03 Aug 2022 | 26 | |
3 | Honeywell | Quantum T 3580 | Operation & user’s manual | honeywell/quantum-t-3580-J12.pdf | 12 Nov 2023 | 60 | 2.15 Mb |
4 | Chrysler | Dodge Challenger 2011 | Specifications | chrysler/dodge-challenger-2011-8YC.pdf | 05 Jan 2024 | 8 | 0.29 Mb |
5 | Oki | C7300 | Specifications | oki/c7300-IA7.pdf | 15 Nov 2023 | 2 | |
6 | Amana | ASD2275BR | Energy manual | amana/asd2275br-XS2.pdf | 05 May 2023 | 2 | 0.41 Mb |
Brooks
EIB3028 / 3018AlarmsInstruction ManualRead and retain carefully for as long as the product is being used. It contains vital information on the operation and installation of your Alarm. The leaflet should be regarded as part of the product.If you are just installing the unit, the leaflet MUST be given to the householder. The leaflet is to be given to any s …
EIB3028(60 pages) |
ACR Electronics
Product Support ManualMini B300 ™ ILS Emergency Position Indicating Radio Beacon Product No. 2766.6 ETSI Type Approved to ETS 300 152 Y1-03-0167 Rev. B ACR Electronics, Inc.5757 Ravenswood RoadFort Lauderdale, Fl 33312Tel : +1(954) 981-3333Fax: +1 (954) 983-5087www.acrelectronics.comEmail: [email protected]
…
Mini B300 2766.6(13 pages) |
Honeywell
IS335 Passive Infrared Motion Sensor – Installation Instructions 1 Select the Mounting Location IS335-010-V01≤ 80 lbs / 36 kg6' 9" - 8' 9"(2.1 - 2.7 m)7' 6"(2.3 m)Optimal Mounting location guidelines: • The optimal range is obtained at a mounting height of 7’ 6” (2.3 m). • …
IS335(4 pages) |
Soundstream
FCC ID NOTICEThis device complies with Part 15 of the FCC rules. Operation is subject to the following conditions:1. This device may not cause harmful interference, and2. This device must accept any interference received, including interference that may cause undesired operation.CAUTION: Changes or modifications not expressly approved by the part responsibl …
Tarantula AL.3(16 pages) |
Cisco
Cisco Systems, Inc. www.cisco.comCisco has more than 200 offices worldwide. Addresses, phone numbers, and fax numbers are listed on the Cisco website at www.cisco.com/go/offices.Cisco Nexus 7000 Series NX-OS System Management Command ReferenceAugust 2013Text Part Number: OL-25806-03
…
Nexus 7000 Series(746 pages) |
Step-Hear
1 CALL HEAR ODU (CH-100/101/104) CALL HEAR IDU (CH-105-IDU) CH-215, CH-315, CH-415 User Guide ALERT AND ASSISTANCE SYSTEM Another quality product from E n g l i s h
…
CH-100(19 pages) |
Konica Minolta All in One Printer BIZHUB 420Konica Minolta BIZHUB 420 Guide (Operation & user’s manual), @8CZ471 BIZHUB 420, 412 |
Hama Keyboard SL100Keyboard PDF Operating instruction SL100, 10 |
SevenStar Measuring Instruments D07–60BSevenStar D07–60B User Manual (Doc Type: Measuring Instruments Instruction manual) D07–60B, 30 |
Rollei Digital Camera dt3200Digital Camera #NMXCP7 dt3200, 26 |
Signametrics Multimeter SM2060#L2842A SM2060: Signametrics Multimeter Owner Documentation SM2060, 152 |
Definitive Technology Speakers Mythos GemSpeakers Operation & user’s manual (Definitive Technology Mythos Gem) Mythos Gem, 8 |
Sanyo Air Conditioner KS1251Sanyo Product User Manual: KS1251 PDF Instruction manual - 8T9362 KS1251, 24 |
Bristan Kitchen & Bath Fixtures Acute AE 1/2 CBristan Kitchen & Bath Fixtures Acute AE 1/2 C Installation instructions manual Acute AE 1/2 C, 32 |
Parkside Performance Cordless Saw PHKSAP 20-Li A1PHKSAP 20-Li A1 Operation and safety notes - 2IJ97D PHKSAP 20-Li A1, 98 |
Redcat Racing Motorized Toy Car VOLCANO-18Motorized Toy Car PDF Operation & user’s manual VOLCANO-18, 32 |
McIntosh Amplifier MCC302MAmplifier PDF Owner's manual MCC302M, 16 |
Carrier Heat Pump SYNERGY 2000 38YDA#PZSDQ5: SYNERGY 2000 38YDA Heat Pump Product data SYNERGY 2000 38YDA, 32 |