  • Siemens COMBIMASTER 411, 1 MICROMASTER 411 & COMBIMASTER 411 Getting Started Guide – 07/05 COMBIMASTER 411 & MICROMASTER 411 English This Getting Started Guide allows for easy and efficient commissioning of the Siemens COMBIMASTER 411 and MICROMASTER 411 Inverters. For further technical information, please refer to the Operating Instructions and the Parameter List on the CD-ROM supplied with COMBIMASTER 411 and MICROMASTER 411. Contents 1 Installation 3 1.1 Installation to Motor 3 1.2 Electrical Installation 7 1.3 Avoiding Electro-Magnetic Interference 9 2 Commissioning COMBIMASTER 411/ M

  • 2 MICROMASTER 411 & COMBIMASTER 411 Getting Started Guide – 07/05 WARNINGS  This equipment contains dangerous voltages and controls potentially dangerous rotating mechanical parts. Non-compliance with Warnings or failure to follow the instructions contained in this manual can result in loss of life, severe personal injury or serious damage to property.  Only suitab

  • Siemens COMBIMASTER 411, 3 MICROMASTER 411 & COMBIMASTER 411 Getting Started Guide – 07/05 1 Installation WARNINGS  THIS EQUIPMENT MUST BE GROUNDED.  To ensure safe operation of the inverter, it must be installed and commissioned by qualified personnel in full compliance with the warnings laid down in the COMBIMASTER 411 and MICROMASTER 411 operating instructions.  Take particular note of general and regional installation, and safety regulations regarding work on dangerous voltage installations (e.g. EN 50178), as well as the relevant regulations regarding correct use of tools and personal protective gear.  Use Lifting Eyes provided if a motor has to be lifted. Do not lift m

  • Siemens COMBIMASTER 411, 4 MICROMASTER 411 & COMBIMASTER 411 Getting Started Guide – 07/05 With the product items removed from their packaging carry out the following installation procedure (refer to Figure 3 for location of components): 1. Separate the two halves (Inverter Cover and Terminal Housing). 2. Remove the Filter Module and I/O board. CAUTION Do not knock out cable gland blanking plates unless the inverter ‘electronics’ (Filter & I/O boards) have been removed! 3. Remove the cable gland blanking plates (knockouts) as required. See Figure 1. 4. Fit cable glands to terminal housing, ensuring the O-ri

  • Siemens COMBIMASTER 411, 5 MICROMASTER 411 & COMBIMASTER 411 Getting Started Guide – 07/05 1.1.3 Installation of Cable Glands WARNING MICROMASTER 411/COMBIMASTER 411 is not suitable for connection to rigid conduit systems. Use flexible cables (CY and SY types) for motor output and flexible cables or flexible conduit for mains input or control connections. Before power and control cables can be connected to their respective circuits it will first be necessary to fit the cable glands supplied. Each gland should preferably be located to allow for convenient cable runs to the terminals locate

  • Siemens COMBIMASTER 411, 6 MICROMASTER 411 & COMBIMASTER 411 Getting Started Guide – 07/05 Jumper Fan/Pump M~n 2 DC Brake 24V An i/p Pot = Run 60 Hz Control Potentiometer LED Heatsink Earth Contact Pin Earth Contact Pin Jumper 1 Sec 2 Sec 5 Sec x 10 x 20 Figure 2 MICROMASTER 411 Inverter Cover (Case Size B) Motor Terminals Filter Module Output Relay Terminals Input/Output Board Control Terminals Cable Gland (Control) Cable Gland (Power Supply) Power Supply Terminals (Cable glands shown in preferred positions

  • Siemens COMBIMASTER 411, 7 MICROMASTER 411 & COMBIMASTER 411 Getting Started Guide – 07/05 Serial Comms Port Control Potentiometer Control Cable Gland Power Cable Gland Cable Gland 'Knock-out' Terminal Housing Inverter Cover Figure 4 MICROMASTER 411 General Layout 1.2 Electrical Installation 1.2.1 Power Cable Connections 1. If the Inverter cover (the top-half) has already been fitted unscrew the four M5 cross-head captive screws on the inverter cover. 2. Remove inverter (cover) to access electrical terminals. 3. Feed the power cable into the terminal ho

  • Siemens COMBIMASTER 411, 8 MICROMASTER 411 & COMBIMASTER 411 Getting Started Guide – 07/05 WARNINGS  It is essential that the Inverter be correctly grounded to the motor ground. Severe injury may result if the motor is not correctly grounded.  If the inverter is being installed after a period of storage please refer to Section 2.1 of the Operating Instructions. 1.2.2 Motor Connections for Star/Delta The following information shows the connection of the motor wires to inverter/motor terminals. Motor wires should be connected in either star or delta configuration, in accordance with the motor rating plate.

  • 9 MICROMASTER 411 & COMBIMASTER 411 Getting Started Guide – 07/05 Terminal Inputs Default operation 1 Digital Input 1 [DIN1] ON/OFF1 2 Digital Input 2 [DIN2] Reverse 3 Digital Input 3 [DIN3] Fault Acknowledge Analog Input (-/+) [AIN] 0 – 10 V Analogue Input 6/7 Option: DIN4 8/9 Output Relay Fault identification Figure 6 Control Circuit Input Terminal

  • Siemens COMBIMASTER 411, 10 MICROMASTER 411 & COMBIMASTER 411 Getting Started Guide – 07/05 2.2 Commissioning Procedure Overview COMBIMASTER 411 and MICROMASTER 411 can be commissioned in a variety of ways as explained in sections 2.2.1 to 2.2.6 below. Installation Commissioning Terminal Control Parameter P0700 = 1 Parameter P1000 = 1 Reference Source Fit Potentiometer (setpoint added to Control Pot.) Ramp Times No Jumpers Fit Jumpers (see section 3.2.1.) Mechanical Installation Electrical Installation Command Source BOP BOP setpoint Analogue setpoint Internal (Control Pot.) External Jumpers Parameters (keypad) Set Ramp Parameter Up = P1120 Down = P11

  • Siemens COMBIMASTER 411, 11 MICROMASTER 411 & COMBIMASTER 411 Getting Started Guide – 07/05 2.2.1 Ramp Times Using Jumpers Inverter ramp times can be set using a series of 5 jumpers (fit the jumpers to enable the function). These are as shown below: 1 s 2 s 5 s x 10 x 20 Jumper Figure 8 Ramp Times Using Jumpers Using up to 5 jumpers allows ramp times to be set between 1 to 240 secs. See table below for details of settings: Table 2 Ramp Times Using Jumpers Time 1s 2s 5s X 10 X 20 1s  2s  3s   5s  6s   7s   8s    10s   20s   30s  �

  • 12 MICROMASTER 411 & COMBIMASTER 411 Getting Started Guide – 07/05 In the following table the behaviour of the Jumpers for ramp times are explained: Table 3 Ramp Time Jumpers Status before action(s) Action(s) Reaction(s) of the inverter • No jumper fitted • Ramp times have arbitrary setting • Power down • Fit jumper(s) • Power up • Invert

  • Siemens COMBIMASTER 411, 13 MICROMASTER 411 & COMBIMASTER 411 Getting Started Guide – 07/05 In the following table the behaviour of the Control Jumpers are explained: Table 4 Control Jumpers Status before action(s) Action(s) Reaction(s) of the inverter • Jumper not fitted • Power down • Fit jumper • Power up • Parameters influenced by jumper will have jumper default values • Jumper not fitted • Cycle power • Parameters influenced by jumper are not changed • Jumper not fitted • Power down • Remove jumper • Power up • Parameters influenced by jumper will have “jumper removed” default (normally factory default)

  • Siemens COMBIMASTER 411, 14 MICROMASTER 411 & COMBIMASTER 411 Getting Started Guide – 07/05 2.2.6 Non - Default Modes of Operation Non-default modes of operation require the use of either a Keypad (e.g., Basic Operator Panel or Advanced Operator Panel) or a Commissioning tool (e.g., Drive Monitor) in order to change from the default parameter settings. The Basic Operator Panel (BOP) – Part Number: 6SE6400-0BP00- 0AA0 is housed in an Operator Panel Mounting Kit (6SE6401-1DF00- 0AA0) and connected via the Interface Link Cable to the Inverter serial comms port. This arrangement

  • Siemens COMBIMASTER 411, 15 MICROMASTER 411 & COMBIMASTER 411 Getting Started Guide – 07/05 3 Quick Commissioning 3.1 Commissioning with BOP Motor parameters detailed below are already set for the respective Siemens motor at the factory. In order to change parameter settings, use either a BOP/AOP or a Commissioning Tool (e.g., Drive Monitor). The parameter sequence below ensures optimized and efficient operation of the inverter. Note that P0010 must be set to 1 to allow this procedure to be performed. When fitted, the jumpers override the parameter settings. P0010 Start Quick Com

  • 16 MICROMASTER 411 & COMBIMASTER 411 Getting Started Guide – 07/05 3.2 Reset to Factory Defaults For factory default settings set P0970 to 1 (with P0010 = 30). Where the inverter is integrated with a non-Siemens motor, setting P0970 = 1 restores the default parameter settings for the respective motor. CAUTION  The reset process can take up to 3 minu

  • Siemens COMBIMASTER 411, 17 MICROMASTER 411 & COMBIMASTER 411 Getting Started Guide – 07/05 4.2 COMBIMASTER 411 - Dimensions Motor FRAME SIZE 71M 80M 90S mm 278.6 296.6 314.6 Height inches 11.0 11.7 12.4 mm 132 150 165 Width inches 5.2 5.9 6.5 mm 240 274 331 Length inches 9.4 10.8 13.0 kW 0.37 0.75 1.5 hp 0.5 1.0 2.0 kW 0.55 1.1 Rating 2p hp 0.75 1.5 kW 0.37 0.55 1.1 hp 0.5 0.75 1.5 kW 0.75 1.5 Rating 4p hp 1.0 2.0 1 4 2 3 5 1-Motor Frame 2-CSB Inverter 3-Control Potentiometer 4-Fixing 5-Comms Interface Figure 12

  • Siemens COMBIMASTER 411, 20 MICROMASTER 411 & COMBIMASTER 411 Getting Started Guide – 07/05 Certificates European Low Voltage Directive The MICROMASTER product range complies with the requirements of the Low Voltage Directive 73/23/EEC as amended by Directive 98/68/EEC. The units are certified for compliance with the following standards: EN 60146-1-1 Semiconductor inverters - General requirements and line commutated inverters EN 60204-1 Safety of machinery - Electrical equipment of machine European Machinery Directive The MICROMASTER inverter series does not fall under the scope of the Machinery Directiv

Related Products and Documents (Inverter):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 Sony STR-LV700R Operating instructions manual sony/str-lv700r-4OJ.pdf 22 Oct 2023 100 2.27 Mb
2 Panasonic CSC9BKP - SPLIT A/C SYSTEM Operating instructions manual panasonic/csc9bkp-split-a-c-system-849.pdf 10 Mar 2023 24 3.06 Mb
3 Magic Chef CES1350AAH Owner's manual magic-chef/ces1350aah-WTL.pdf 08 Apr 2023 27
4 Olympus ZUIKO DIGITAL ED 70-300mm F4.0-5.6 Instructions olympus/zuiko-digital-ed-70-300mm-f4-0-5-6-7CA.pdf 18 Jul 2022 2
5 Lenovo ThinkCentre Edge 92z Operation & user’s manual lenovo/thinkcentre-edge-92z-KYW.pdf 12 Apr 2023 116
6 Scotsman FME1200 Service manual scotsman/fme1200-WT4.pdf 19 Jan 2024 32 1.01 Mb

Similar Resources:

  • Keysight Technologies

    E8257N

    (24 pages)
    Notice: This document contains references to Agilent. Please note that Agilent’s Test and Measurement busi-ness has become Keysight Technologies. For more in-formation, go to www.keysight.com.Keysight E8257D/57N/67D and E8663D PSG Signal Generators Add Option UNX (Ultra-Low Phase Noise Performance)Kit Part Numbers: E8251-60417, E8251-60980, and E8251-60991 …
  • Silverline

    444658

    (40 pages)
    www.silverlinetools.com44465812V Inverter 12V Inverter Onduleur 12 VSpannungswandler, 12 VInversor 12 VInvertitore 12V12 V omvormer2000W (2 x 1000W) T-130˚Version date: 23.11.16444658_Z1MANPRO1.indd 2 23/11/2016 10:53 …
  • Brunner

    0826089N

    (8 pages)
    1• Kompakt, handlich, leicht zu transportieren• Einstellbarer Zigarettenanzünder• Bietet Stromversorgung für elektrische und elektronische GeräteHerzlich Willkommen!Jumper Micro 80 W wurde genauestens entwickelt, um größte Sicherheit zu bieten. Bitte lesen Sie vor Gebrauch des Produktes aufmerksam die Gebrauchsanweisung.Sicherheitsmaßnahmen• …
  • Goodwe

    HT Series

    (20 pages)
    HT SERIES USER MANUALPhotovoltaic Grid-Tie InverterSOLAR INVERTERNote: The above contact information is subject to change without notice. For details, refer to thecompany's official website www.goodwe.comSEMS Portal websiteOffical WebsiteSolarGo APP SEMS Portal AppGOODWE (Germany)Fürstenrieder Str. 279a 81377 München, GermanyT: +49 8974120210 +49 421 …
  • Thermal Arc

    ARCMASTER 400TS

    (120 pages)
    400TS400SARCMASTER®INVERTER ARC WELDERSArt # A-07263Service ManualVVVVVersion No:ersion No:ersion No:ersion No:ersion No: AA.03Issue Date:Issue Date:Issue Date:Issue Date:Issue Date: May 22, 2006 Manual NoManual NoManual NoManual NoManual No: 0-4895BOperating FeaturesOperating FeaturesOperating FeaturesOperating FeaturesOperating Features:300TS300S …
  • LS Industrial Systems

    SV-iE5 Series

    (127 pages)
    Right choice for ultimate yield LSIS strives to maximize customers' profit in gratitude of choosing us for your partner. SV-iE5 User Manual 0.1~0.4kW (200V) z Read this manual carefully beforeinstalling, wiring, operating, servicingor inspecting this equipment. z Keep this manual within easy reachfor quick reference. …

Comments, Questions and Opinions: