  • Simplex 4007-9101, Page 23 579-1102 Rev H 4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual Table 17: Compatible devices and appliances Addressable device appliance description TrueAlert ES appliance model numbers TrueAlert appliance model numbers Visible only (VO) notification appliances 49VO-WRF 49VO-WWF 49VO-WRA-A 49VO-WRA-A-BA 49VO-WWA-A 49VO-WRA-BA 49VO-WRF-BA 49VO-WRQ-BA 49VO-APPLC 49VO-APPLC-BA 49VOH-APPLC 49VOH-APPLC-BA 49VOH-APPLCA 49VOH-APPLCA-BA 49VOH-APPLCB 49VOH-APPLCB-BA 49VO-WRS-BA 49VO-WWS-BA 49VO-WWF-BA 49VO-WWA-BA 49VO-W

  • Page 29 579-1102 Rev H 4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 6 4007ES power supplies This chapter describes the common sections of both the 4007ES Hybrid NAC power supply and the 4007ES IDNAC power supply. 6.1 Power supplies specifications Table 21: Operating conditions Operating conditions: Operating temperature range 32 °F - 120 �

  • Page 9 579-1102 Rev H 4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual Fig 7: EOL relay diagram • In areas of high lightning activity, or in areas that have large power surges, use the 2081- 9027 or the 2081-9044 Transient Suppressor on monitor points. • Wires must not be run through elevator shafts. • Only system wiring can be run together in the same conduit.

  • Simplex 4007-9101, Page 33 579-1102 Rev H 4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 6.8 Auxiliary power selection AUX PWR/SNAC overview The AUX PWR/SNAC terminal block is located on the top left corner of the power supply. Using the ES Panel Programmer, this point can be configured as either a 24V Auxiliary (AUX) power or as a simple reverse polarity Notification Appliance Circuit (NAC). This circuit does not support TrueAlert addressable devices nor non-addressable SmartSync appliances. The AUX PWR/SNAC is rated 2 A maximum. The current u

  • Simplex 4007-9101, Contents CONTENTS 1 Cautions, Warnings, and Regulatory Information.......................................................................................................3 2 Overview...........................................................................................................................................................................4 2.1 4007ES product list.............................................................................................................................................................................................. 4 2.2 Glossary............................................................

  • Simplex 4007-9101, Page 8 579-1102 Rev H 4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 3.3 Wiring Wiring guidelines Follow these guidelines when connecting power-limited (PL) systems. For more information about these guidelines, contact your authorized Simplex product supplier. • Non-power limited (NPL) field wiring (AC power, batteries, City connection, DACT) must be installed and routed in the shaded areas shown in Figure 6: Field wiring guidelines (NAC power supply shown as reference) on page 8 • You must maintain a minimum of 0.25 in. (6.35 mm) space betw

  • Simplex 4007-9101, Page 12 579-1102 Rev H 4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 4.1 NAC power supply specifications The NAC power supply can supply 6 A of 24 V power in addition to the base draw of the CPU/ Power Supply cards. The current draw taken from optional cards, IDNet Devices, Aux Power, and NACs must be subtracted from 6 A. IMPORTANT: See the 4007-9801 8-Point Zone/Relay Card Installation Instructions 579-1103, to determine the draw of the pre-installed Zone/Relay card. Table 5: 4007ES hybrid system current draw Maximum AC i

  • Simplex 4007-9101, Page 6 579-1102 Rev H 4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 3 Installation Introduction This chapter describes how to install the 4007ES panel. It can be semi-flush or surface mount. 3.1 Mounting the 4007ES panels • Due to the danger of metal fragments falling into electronics when drilling the holes for the conduits, remove the electronics in the system: - To remove the electronics, unscrew the ten screws. Remove the power supply and store it in a safe, clean, and dry location until the panel installation is comp

  • Simplex 4007-9101, Page 5 579-1102 Rev H 4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 2.2 Glossary Table 3: Glossary Term Definition Aux Abbreviation for Auxiliary; typically used to describe Auxiliary Power. EOL End-of-Line, typically in reference to and end-of-line resistor or EOL resistor. FACP Fire Alarm Control Panel. Hybrid In this document, “Hybrid” the 4007ES Hybrid models that provide both addressable and conventional initiation with conventional non addressable Notification Appliance Circuits. IDC Initiating Device Circuit. IDNet Addressable SLC for up to 250 addressable devices. IDNet+ IDNet which is electrically isol

  • Page 30 579-1102 Rev H 4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 6.3 IDNet Section overview The power supply provides an isolated IDNet channel. This section is compatible with IDNet communicating initiating devices and enables the system CPU to communicate with up to 250 peripheral devices, such as smoke detectors and pull stations. Fig 23: IDNET on the power su

  • Simplex 4007-9101, Page 36 579-1102 Rev H 4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 6.10Troubleshooting The code produced by the illuminated indicator LEDs corresponds to a trouble occurring on the system. See Table on page 36 for the IDNet LED definitions, and see Table on page 36 for the 4007ES trouble messages. Table 28: LEDs on the 4007ES power supplies Comm trouble Normally off. Turns on steady if the IDNet is not communicating with the FACP CPU. IDNet trouble Normally off. Illuminates to indicate a problem with the IDNet channel: • Channe

  • Simplex 4007-9101, Page 10 579-1102 Rev H 4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 3.3.3 Battery guidelines A fused harness is required to connect the backup batteries. Use harness 734-304 for a NAC power supply, and harness 734-303 for an IDNAC power supply. The harness is shipped with the panel. The mating spade lug on the battery should be 0.250 in. X 0.032 in. (6.35 mm X 0.81 mm). If another size is needed, you need to replace the battery terminal connectors on the supplied battery harness. • The 4007ES battery charger supports up to 33 Ah batteries (maximum) within UL864

  • Simplex 4007-9101, Page 13 579-1102 Rev H 4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 4.3 Specifications Table 6: Specifications Maximum appliances 70 per circuit.* * Each 49CMT series appliance counts as 5 regular appliances for the maximum 70 appliances that can be supported per NAC. As the earth fault sensitivity with thirteen MT appliances drops from 10 K to 9.6K ohms, no more than thirteen 49CMT series appliances may be placed on one circuit. Electrical specifications: Voltage 24 VDC nominal. Alarm current The maximum alarm current is 3 A per circuit. Supervisory current Refer to Table on page 13. Special application appl

  • Simplex 4007-9101, Page 25 579-1102 Rev H 4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 5.8 Auxiliary relays section overview Table 18: Electrical specifications for Auxiliary relays Electrical specifications: Relay circuit rated to switch: 2 A at 30 VAC or 30 VDC, resistive load. Contacts: Relay contacts are Form C dry contacts. Transorbs provide suppression to earth. Do not switch voltages greater than rating, or damage may result. Table 19: Power specifications for auxiliary relays Power When power through auxiliary contacts is provided by the power supply, the wiring is power-

  • Simplex 4007-9101, Page 15 579-1102 Rev H 4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual Fig 12: Class A NAC wiring 3. Route the wire from the last appliance to the A+ and A- inputs on the same NAC circuit of the power supply. 4. Repeat steps 1 through 3 for each NAC output you want to use. 5. Leave the 10 KOhms, 1/2 W, brown/black/orange resistor (378-030) on each unused circuit. No external end-of-line resistor is needed for circuits in use. 4.3.4 Class B wiring NOTE: The Class B wiring s

  • Simplex 4007-9101, Page 26 579-1102 Rev H 4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 5.9 Troubleshooting The code produced by the illuminated yellow indicator LEDs corresponds to a trouble that is either occurring on the system, or on the SLC channels. See Table on page 26 for the 4007ES LED definitions, and see Figure 21: SLC channel trouble LED codes on page 27 for the 4007ES LEDs and their codes. IDNAC channel troubles are indicated by yellow LEDs labeled IDNAC TBL and letters A to D. When the IDNAC TBL LED illuminates, the IDNAC channel is experiencing a trouble. Refer to Figure 22: System trouble LED codes on page 28

  • Simplex 4007-9101, Page 19 579-1102 Rev H 4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 5.3 Specifications Table 14: IDNAC specifications Supports • Up to 12 4905-9929 remote TrueAlert Addressable Isolators per IDNAC Circuit. • Up to 30 devices connected directly to any isolator terminal pair*. • Up to six isolators between any appliance and the IDNAC SLC terminals. All wiring is 20 AWG to 12 AWG. *For more information on the isolator, refer to the 4905 Isolator+ Installation Instructions, 574-769. Electrical specifications: Chan

  • Simplex 4007-9101, Page 4 579-1102 Rev H 4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 2 Overview The 4007ES fire alarm control panel provides audible and visible indication of alarms, troubles, and supervisory conditions. The 4007ES panels supports addressable notification and initiating devices and the 4007ES Hybrid panels supports non-addressable notification devices and addressable initiating devices*. The panel can be configured by using a panel programmer. *From this point on, the 4007ES and the 4007ES hybrid is referred to as 4007ES, unless stated otherwise. 4007ES operator instructions are described in the 4007ES Operator’s Ma

  • Simplex 4007-9101, 4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual Page 3 579-1102 Rev H 1 Cautions, Warnings, and Regulatory Information READ AND SAVE THESE INSTRUCTIONS Follow the instructions in this installation manual. These instructions must be followed to avoid damage to this product and associated equipment. Product operation and reliability depend upon proper installation. DO NOT INSTALL ANY SIMPLEX™ PRODUCT THAT APPEARS DAMAGED Upon unpacking your Simplex product, inspect the contents of t

  • Simplex 4007-9101, Page 17 579-1102 Rev H 4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 5 IDNAC power supply An IDNAC power supply is used in the 4007ES panel, the non-hybrid panel. It provides 4 A and can support the following: • Addressable notification devices. • Addressable initiating devices. See Figure 15: IDNAC power supply on page 17 and Table on page 17 for the main components of the IDNAC power supply. Fig 15: IDNAC power supply Table 12: Main components information P1 RUI Class A/B jumpers P2 IDNet Class A/B jumper TB4 Battery connection TB2 IDNAC P10 AC Power Connection TB3 Aux Relay 1 and 2 J15 DCAI Zone/Relay Connection J10 IDN

  • Simplex 4007-9101, Page 31 579-1102 Rev H 4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 6.5 Wiring parameters Table on page 31 identifies the IDNet wiring parameters that you must consider when installing this card. For additional wiring information, see Simplex Addressable Fire Alarm Panels Field Wiring Specifications (900-408). Table 23: IDNet wiring parameters IDNet wiring capacitance parameters Parameter Value Maximum supported channel capacitance The sum of line-to-line capacitance, plus the capacitance of either line-to- shield (if shield is present) = 0.6 µF IDNet wiring Class A and Class B limits Channel loading Up to 125 dev

  • Simplex 4007-9101, Page 21 579-1102 Rev H 4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 5.6 IDNAC Class B wiring To connect the power supply to appliances using Class B wiring: 1. Route the wire from the + and the - outputs on the IDNAC terminal block (TB2) to the appropriate inputs on a peripheral notification appliance. 2. Route the wire from the first appliance to the next. T- tapping is permitted. Repeat this for each appliance. 3. Repeat steps 1 and 2 for each IDNAC output you want to use. Fig 18: Class B wiring NOTE: 1. Notification appliances are rated using an individual nameplate label. Maintain the correct polarity on terminal connections. 2. Each IDNAC + and - terminal is r

  • Simplex 4007-9101, Page 22 579-1102 Rev H 4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 5.7 Compatible devices and appliances The devices and appliances listed in Table on page 22 are compatible with the IDNAC power supply. Notification devices are synchronized within the 4007ES system, including any attached 4009 series NAC extenders. Table 16: Compatible devices and appliances Addressable device description Model numbers 4009 IDNAC Repeater 4009-9601 (platinum) 4009-9602 (red) Dual Class A Isolator (DCAI) 4007-9804 TrueAlert Addressable Isolator+ module 4905-9929 Table 17: Compatible devices and appli

  • Simplex 4007-9101, Page 11 579-1102 Rev H 4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 4 NAC power supply A conventional reverse polarity NAC power supply is used in a 4007ES hybrid panel. It provides 6A and can support the following: • Non-addressable notification devices. • Addressable initiating devices. See Figure 10: NAC power supply on page 11 and Table on page 11 for the main components of the NAC power supply. Fig 10: NAC power supply Table 4: Main components information P1 RUI Class A/B jumpers P2 IDNet Class A/B jumper TB

Related Products and Documents (Fire Alarms):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 Konica Minolta bizhub C654 Operation & user’s manual konica-minolta/bizhub-c654-W9C.pdf 12 Nov 2023 50
2 AAxeon STW-602C Operation & user’s manual aaxeon/stw-602c-YD1.pdf 07 Aug 2022 74
3 Peavey Messenger Series Pro Sub P Operating instructions peavey/messenger-series-pro-sub-p-ILN.pdf 10 Apr 2023 4
4 Ford Flex 2016 Owner's manual ford/flex-2016-RYZ.pdf 30 Sep 2022 417
5 Tecumseh HSK840 Technician's handbook tecumseh/hsk840-6WY.pdf 15 Aug 2023 36
6 Icom IM323 Instruction manual icom/im323-EL4.pdf 06 Nov 2022 100

Similar Resources:

  • Faraday

    MPC-6000

    (76 pages)
    Siemens Building Technologies, Inc. 8 Fernwood Road • Florham Park, NJ 07932 Tel: (973) 593-2600 • Fax: (973) 593-6670 Web: www.faradayfirealarms.com P/N 315-447309-5 MPC-6000 / MPC-7000 / RND-2 Fire Alarm System Control Unit Installation, Operation and Maintenance Manual …
  • FireClass

    MCP200CS

    (4 pages)
    ISTISBL2MCP200CS 1.0 130212Conforme / Complies with / Cumple: EN54 part 11Il contenuto di questo manuale può essere soggetto a modifiche senza preavviso e non rappresenta un impegno da parte del CostruttoreI ITALIANODESCRIZIONE GENERALEIll pulsante di segnalazionemanuale MCP200CS (MCP di seguito) èappositamente progettato per l'utilizzo con i Sistemi …
  • Global Fire Equipment

    ORION

    (17 pages)
    Global Fire Equipment // globalfire.pt ma_orion_01_020000_en_200102 ORION 2 / 4 / 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION & MAINTENANCE MANUAL GENERAL DESCRIPTION The ORION is a 2, 4 and 8 Zone microprocessor controlled conventional Fire Alarm Control Panel with all the functions necessary to control small and medium size fire d …
  • DSC

    PC1550

    (12 pages)
    INSTRUCTION MANUAL DSC 1550 A WORD ABOUT YOUR SYSTEM The PC1550 Security System has been designed to give you the greatest possible flexibility and convenience. Read this manual carefully and become familiar with the operation of your Security System. Your installer will tell you which commands listed in this manual apply to your system. Fill out the SY …
  • INIM Electronics

    PREVIDIA MAX

    (24 pages)
    IFM4R 1 1 - IFM4R 2 - PRCAB + IFMABDECEN 54-2EN 54-4EN 54-21EN 12094-108320832-CPR-F1342cert. N.991KIFM4RModulo interno 4 uscite relèInternal module with 4 relay outputsMódulo interno 4 salidas reléModule interne 4 sorties relaisMódulo interno 4 saídas reléInterne module 4 relaisuitgangen …
  • VENTCROFT

    FIRETRAX FT2BS

    (5 pages)
    Ventcroft Ltd.Goddard Road,Astmoor, Runcorn,Cheshire WA7 1NQ,Great Britain.Phone: 01928 581098Fax: 01928 581099E-Mail: [email protected]://www.ventcroft.co.ukManufacturing Global Security in Great Britain.....with PrideManufacturing Global Security in Great Britain.....with PrideVI40.1 Created 05/11/2001 Issue 1.3SPEClFlCATlONSIf you experience any d …

Comments, Questions and Opinions: