ESP MAGPRO96 Installation And Programming Manual
|
ESP MAGPRO96, 12 Addressable Fire Panel MAGPRO96 - Installation and Programming Manual The MAGPRO96 re panel operates with MAGPRO96-L250 loop controller (MAGPRO communication protocol). The Loop Controller (Figure 14) realizes the connection between the I/O Module and devices connected to the com- munication line. The Loop Expander has two basic functions: 1. Gathers data from the devices in the communication line and transfers it to the I/O Module; 2. Receives commands from the I/O Module and transfers them to the devices connected in the communication line. Every MAGPRO96-
22 Addressable Fire Panel MAGPRO96 - Installation and Programming Manual 3.3 Devices The addressable re panel MAGPRO96 supports periphery and loop devices. All “functional modules” connected to the control panel conguration are dened as Periphery Devices, and have spe- cial programming and setting. The Main board is not a periphery device. All addr
ESP MAGPRO96, 28 Addressable Fire Panel MAGPRO96 - Installation and Programming Manual MAGPRO-CP - Manual call point Fig. Screen 9(d) - MAGPRO-CP manual call point. On Fig. Screen 9(d) is shown the MAGPRO-CP (manual call point) settings screen. Choose the “MORE” button to enter a screen with additional settings: • - Every pressing of the button alternatively changes the type of the event generated with activation of the manual call point: - EVACUATE – The sounders will be activated immediately, as the set time delays Т1 and Т2 are ignored. - ALARM – The set time delays Т1 and Т2 are active
ESP MAGPRO96, 26 Addressable Fire Panel MAGPRO96 - Installation and Programming Manual MAGPRO-SD1 - Optical-smoke detector Fig. Screen 9(a) - MAGPRO-SD1 re detector. On Fig. Screen 9(a) is shown the MAGPRO-SD1 (addressable optical smoke detector) settings screen. Choose the “MORE” button to enter a screen with additional settings: • ° - Press the “Check” button to enter in a new screen to review the following parameters: -
ESP MAGPRO96, Addressable Fire Panel MAGPRO96 - Installation and Programming Manual 47 4. MAINTENANCE 4.1 Maintenance Menu To enter in the Maintenance Menu the installer has to choose button “Maintenance” – Fig. Screen 1. The general view of the menu is shown on Fig. Screen 25. Fig. Screen 25. 4.2 Time introducing Choose the button “Time” from the Maintenance Menu to set the current time - Fig. Screen 26. Use the APPLY button to conrm the settings. The desired time can be set with the buttons for sele
ESP MAGPRO96, Addressable Fire Panel MAGPRO96 - Installation and Programming Manual 33 MAGPRO-4i0O - Module with 4 inputs Fig. Screen 9(m) - MAGPRO-4i0O module. On Fig. Screen 9(m) is shown the MAGPRO-4i0O (module with 4 inputs) settings screen. Choose the “MORE” button to enter a screen with additional settings: • - Button for changing the LED mode: ON Setting - The LED blinks at every query from the station; OFF Setting - The LED does not show the dialogue cycle. To congure the inputs operation you have to go to menu INPUTS (SYSTEM - PROGRAMMING - INPUTS) - see the description of
ESP MAGPRO96, Addressable Fire Panel MAGPRO96 - Installation and Programming Manual 39 • ZONE - Number of zone and event for activation. Choosing the Zone type of the input will add a new eld Function - Fig. Screen 15. After choosing this eld the pos- sible zone events will be displayed on the screen. Choose the MORE button. Set the zone number, from 1 to 96, in the screen “INPUT Parameters - zone”. Fig. Screen 15 - Menu for zone events introducing. • ALARMS - Enter a number for activated alarms from a zone. Choose the MORE button.
ESP MAGPRO96, Addressable Fire Panel MAGPRO96 - Installation and Programming Manual 19 3.1 Access Codes To access the Programming and Maintenance Menus is necessary to enter a valid access code. Fig. Screens 1. There are 4 access codes programmed by default. The Installer/User can enter 3 access levels in the system. The in- troduced code combinations are visualized with “*“ symbol. Code Number Code Combination Access Level Functions 1 0000 1 Only Silence Buzzer and Delay Override buttons are active. It is not allowed to enter the Programming and Maintenance Menus. 2 111
ESP MAGPRO96, Addressable Fire Panel MAGPRO96 - Installation and Programming Manual 5 • Loops - from 1 to 4 loops • Up to 250 devices (detectors and modules, regardless of the type) per Loop • Zones - 96 displayed zones • Monitored relay outputs - 4 (Sounder, Fire, Fault and Fire Protection) • Non monitored relay outputs - 4 programmable, 230V/ 10A • Display - 320x240 CSTN graphic display (118.8 x 89.38 mm) with a touch panel • Real tim
36 Addressable Fire Panel MAGPRO96 - Installation and Programming Manual The system automatically shows the rst address in the system. You can check the device assigned at this address with pressing the ‘LED ON’ button - the LED(s) of the device will light on permanently. Next pressing of the same button will off the LED. Use the arrow buttons to scroll over addresses a
ESP MAGPRO96, 18 Addressable Fire Panel MAGPRO96 - Installation and Programming Manual 3. PROGRAMMING 3.0 Basic knowledge for operating with LCD touch-screen display The touch-screen display of the re panel MAGPRO96 provides easy moving down the programming menus and entering of system parameters. The access to the programming menus is done with light pressing of the desired button. You can use also and a special pen for touch-screen display. According to the chosen menu and/or the access level there are active and inactive buttons on the screen. Choosing an active button leads to changing of the screen - you can move to a list of additional or submenus for programm
ESP MAGPRO96, 4 Addressable Fire Panel MAGPRO96 - Installation and Programming Manual 1. INTRODUCTION 1.1 General Description MAGPRO96 is an analogue addressable re panel with maximum coverage of 96 zones and connecting 1 to 4 loops. The panel supports communication protocol MAGPRO (MAGPRO96-L250 loop controller). In the conguration of the MAGPRO96 panel can be implemented up to 4 MAGPRO96-L250 loop controllers. An arbitrary number of devices can be added to each zone thus ensuring the easy adaptation of the system to any type of conguration. To avoid or signicantly diminish problems when mounting the system
32 Addressable Fire Panel MAGPRO96 - Installation and Programming Manual MAGPRO-0i4O - Module with 4 outputs Fig. Screen 9(k) - MAGPRO-0i4O module. On Fig. Screen 9(k) is shown the MAGPRO-0i4O (module with 4 outputs) settings screen. Choose the “MORE” button to enter a screen with additional settings: • - But
ESP MAGPRO96, 54 Addressable Fire Panel MAGPRO96 - Installation and Programming Manual 4.10 Display The Installer/User can check and calibrate some parameters of the LCD display. From the general Maintenance Menu you can enter the Display submenu. It is possible that after a certain period of use the parameters of the Touch screen display may change, causing difcul- ties in marking the sites. This would require it to be calibrated periodically, which can be done in access levels 2 and 3. ATTENTION! Calibrating the display must be done with a Touch screen pen (or P
ESP MAGPRO96, 52 Addressable Fire Panel MAGPRO96 - Installation and Programming Manual 4.8 Disable introducing The user/installer can enable or disable the loop devices, zones and the outputs of the re panel. To introduce enabling or disabling a function you can directly choose the respective button and make corrections, or rst by pressing “View” button to look at the current status of the system and after that, if it is necessary, to enter new data – Fig. Screen 35. Fig. Screen 35. T
ESP MAGPRO96, 56 Addressable Fire Panel MAGPRO96 - Installation and Programming Manual 5. INSTRUCTION FOR USE 5.1 Status Line Purpose – Indicates the current status of the re alarm panel, containing detailed information on the access level, the working mode (day/ night time), the status of the re output and re protection, etc - see Fig. Screen 42 and Fig. Screen 43. Fig. Screen 42. Used for accessing the Change Access Level menu. �
ESP MAGPRO96, 8 Addressable Fire Panel MAGPRO96 - Installation and Programming Manual • Analogue-addressable re panel MAGPRO96 is available for ush mounting. The accessory set contains two special hangers (see Figure 7) for ush wall mounting of the re alarm panel on 25 mm thick drywall. • Use given on Figure 6 dimensions to outline and to cut the mounting hole in the drywall. • Fix the hinges on the back side of the g
ESP MAGPRO96, Addressable Fire Panel MAGPRO96 - Installation and Programming Manual 7 2. INSTALLATION 2.1 Mounting • The panel must be installed in a clean dry place and must not be subjected to impact or vibrations (Figure 1). It must be situated far from heating appliances. The temperature must be within -5ºС and + 50ºC. The re panel is not water- proof! • Unscrew the two secret bolts situated above and under the box cover - see Figure 2. • Remove the front cover as rst disconnect the at-cable for panel indication. After that unscrew the hinge bolts on the side of the front panel - Figure 3. (Note: You can unscrew and the hinge bolts on the sid
ESP MAGPRO96, Addressable Fire Panel MAGPRO96 - Installation and Programming Manual 3 4.3 Date introducing .............................................................................................................................................................................................. 47 4.4 Daytime Mode ................................................................................................................................................................................................. 48 4.5 Output Delay Introduction .......................................................................................................................................
ESP MAGPRO96, 14 Addressable Fire Panel MAGPRO96 - Installation and Programming Manual Red LED for indication of V.220 Black Black Yellow-green Black Black Yellow-green Fuse F-Type 2 А Main Power Source LED-indication for the status of Main Power Source. Terminal block for external power supply. 1 2 3 4 5 6 1 2 3 4 Figure 17. General view of the power source and the terminal. LED-indication of the power source LED Function Description 1 AC LOSS Main power supply loss 220V. 2 Charger Fault Problem with th
ESP MAGPRO96, Addressable Fire Panel MAGPRO96 - Installation and Programming Manual 23 3.3.1.3 Adding a new periphery device to the panel Upon detecting a new periphery device (which is missing in the conguration), the following message will be displayed: “NEW PERIPHERY DEVICES FOUND”, and the number of the detected devices will be indicated. Choose the SAVE button to add the new periphery devices to the panel conguration. If a device is not responding you can remove it as choosing the REMOVE button. Fig. Screen 5 PSU Parameters (P
ESP MAGPRO96, Addressable Fire Panel MAGPRO96 - Installation and Programming Manual 55 The Installer/User can also adjust the brightness of the LCD touch screen display. To see the brightness of the display choose the Colours submenu from the Display Menu. To adjust the LCD brightness use a small plain screw-driver and turn the potentiometer on the left or on the right. The Installer/User can switch on
48 Addressable Fire Panel MAGPRO96 - Installation and Programming Manual 4.4 Daytime Mode Choose the button “Day” from the Maintenance Menu to set the daytime schedule for detectors operation. The Daytime operating mode can be enabled (ON), disabled (OFF) or to follow a time schedule (Schedule) Fig. Screens 28. Fig. Screens 28. In this mode the detectors use the
Tyco F4000 Fire Alarms Lcd operator's manual
F4000 |
Honeywell C7076D Fire Alarms Product data
C7076D |
Teletek electronics SensoIRIS MCP150PR Fire Alarms Installation instructions
SensoIRIS MCP150PR |
GST DC-M9415 Series Fire Alarms Installation sheet
DC-M9415 Series |
Notifier AFP-300 Fire Alarms Installation manual
AFP-300 |
Mircom QX-mini Fire Alarms Installation and operation manual
QX-mini |
Siemens FC2005 Fire Alarms Programming manual
FC2005 |
Siemens FC700A Fire Alarms System planning manual
FC700A |
# | Manufacturer | Model | Document Type | File | Updated | Pages | Size |
---|---|---|---|---|---|---|---|
1 | Sanyo | SRT-2400 | Instruction manual | sanyo/srt-2400-O77.pdf | 23 Nov 2023 | 50 | 0.46 Mb |
2 | Epson | PictureMate Show - PM 300 - PictureMate Show Digital Frame | Features and benefits | epson/picturemate-show-pm-300-picturemate-show-digital-frame-UCY.pdf | 26 Nov 2022 | 2 | 0.79 Mb |
3 | GE | JGB281SERSS | Dimensions and installation information | ge/jgb281serss-7EM.pdf | 10 Mar 2024 | 2 | |
4 | Oki | CX2640 | Specifications | oki/cx2640-968.pdf | 11 Apr 2023 | 8 | |
5 | CEL | 10.8v Li-ion | Operation & user’s manual | cel/10-8v-li-ion-3TU.pdf | 03 Sep 2022 | 16 | |
6 | Gaggenau | BS 274/275 | Instruction manual | gaggenau/bs-274-275-46S.pdf | 27 Oct 2022 | 52 | 0.8 Mb |
Faraday
INSTALLATION INSTRUCTIONS FORMPC-6000, MPC-7000 AND RND-2 DISPLAY BOARDSInstallation is to be done by qualified personnel whohave thoroughly read and understood this instructionsheet.Step 1.) Upload the panel configuration to the CIS-4 software.Step 2.) Disconnect BATTERY and AC prior to working onequipment.Step 3.) Remove cable connection from the keypad on …
RND-2(2 pages) |
Bosch
Automatic DetectorSeries FCP-320, FAP-420, AVENAR detector 4000 Painting Guide | Lackieranleitung | Руководство по окраске deutschenglishрусский
…
FCP?320(20 pages) |
Panasonic
Technical/Programming Manual FT1020G3 Rev 2.2.1 For Software V2.2.x FT1020G3 CIE M435 February 2016
…
Firetracker FT1020G3 CIE(192 pages) |
Siemens
FS20/FS720Fire Detection SystemLightning protection and voltage surgeprotectionApplication GuidePlanningBuilding Technologies2016-04-04 Control Products and Systems
…
FS20(42 pages) |
Brooks
Heat Alarmfor Residential PanelsEIB603CXRead and retain carefully for as long as the product is being used. It contains vital information on the operation and installation of your Smoke Alarm. The leaet should be regarded as part of the product.If you are just installing the unit, the leaet must be given to the householder. The leaet is to be given …
Electronics EIB603CX(30 pages) |
Ziton
ZP700 Series Addressable Detector Installation Sheet 1 2 3 4 EN: Installation Sheet Description ZP700 Series Addressable Detector models are shown in Table 1. Table 1: Models Number Description ZP720-3P Addressable Thermal Sensor, Polar White ZP730-2P ZP730-2B ZP730-2S30 Addressable Optical Smoke Sensor, Polar White Addressable Optical Smoke Senso …
ZP700 Series(3 pages) |
Philips Flat Panel TV 46PP8621Philips Flat Panel TV Specification (File: philips-46pp8621-brochure-2, 09/12/2023) 46PP8621, 2 |
DreamGEAR Docking Station U Concept Dock Pro DGWIU-4318DreamGEAR Product User Guide: U Concept Dock Pro DGWIU-4318 PDF Operation & user’s manual - 552926 U Concept Dock Pro DGWIU-4318, 12 |
Toshiba Laptop A105-S4014A105-S4014 Specifications - 71I28L A105-S4014, 11 |
Yamaha Receiver RX-V595aYamaha Product User Manual: RX-V595a PDF Service manual - 7Y84Y4 RX-V595a, 20 |
HP Desktop Pavilion 403PDF Guide (@79AE72), HP Pavilion 403 Desktop (09.01.2024) Pavilion 403, 16 |
Audiolab Amplifier 8000S#1G81DM 8000S: Audiolab Amplifier Owner Documentation 8000S, 1 |
Toshiba DVD VCR Combo MW26H82Toshiba Product User Manual: MW26H82 PDF Owner's manual - R8423N MW26H82, 84 |
Apple Computer Hardware iMac G5 Inverter, 17-inchApple iMac G5 Inverter, 17-inch User Guide (Replacement instructions manual), @1739DI iMac G5 Inverter, 17-inch, 19 |
Triarch Indoor Furnishing Indoor Lighting 33201Indoor Furnishing PDF Assembly instructions Indoor Lighting 33201, 1 |
Nikon Digital Camera One TouchNikon One Touch Digital Camera Instruction manual One Touch, 2 |
MTX Amplifier RT251DOwner's manual for MTX RT251D Amplifier RT251D, 19 |
Husqvarna Lawn Mower Rider Pro 15Rider Pro 15 (Lawn Mower ePDF User Guide, #7WRH4Y) Rider Pro 15, 68 |