MPC-6000/MPC-7000/RND-2 PROGRAMMING MANUAL 45 APPENDIX B: REFERENCES • NFPA 72: National Fire Alarm Code (National Fire Protection Association) • NFPA 70: National Electrical Code (Delmar Publishers) • MPC-6000 / MPC-7000 / RND-2 Faraday Fire Alarm Control Panel Owner's Manual, P/N 315-447309 • Faraday web site: http://www.faradayfirealarms.c
Faraday MPC-6000, MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL 5 Entering Alphanumeric Characters Entry of alphanumeric data using the keypad is as follows: • Each character is entered using a two-keystroke sequence on the keypad. • Numerals are entered using the sequence 0x, where x is the numeral to be entered. • Letters are entered using 1x, 2x, 3x, and 4x sequences, based on the letters appearing above the numbers on the keypad, where the first digit (1, 2, 3 or 4) is the position of the letter and the sec
Faraday MPC-6000, MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL 39 Setting the Total Number of Nodes Follow the steps below to set the total number of nodes (panels, RNDs and printers) in the network. Action Result 1. Select “Edit”. 2. Select “Manual Pgm”. 3. Press “Cmor” twice to select “Network Setup”. 4. Select “Dnxt”. 5. Select “Dnxt”. 6. Select “Dnxt”. The setting for the Total Number of Nodes displays. 7. Type in the Total Number of Nodes. Be certain to enter leading zeros if the total number of nodes is from 1-9. A maximum of 99 nodes can be entered. 8. Select “Dnxt” to contin
Faraday MPC-6000, MPC-6000/MPC-7000/RND-2 PROGRAMMING MANUAL 47 APPENDIX D: TYPICAL PROGRAMMING MODEL One Hazard (Releasing Zone) Area and One Fire (Building Fire Protection) Area Input Devices Manual Release Switch Abort Switch Releasing Input Group 1 Output Zone 1 Output Zone 2 Input Devices Manual Pull Stations General Alarm Group NAC1 1st Alarm/ Pre-Discharge NAC2 Discharge NAC3 Alarm NAC4 Alarm or Trouble Coded or Steady Only Steady-On or Strobe Only Steady-On or Strobe Only Steady-On or Strobe Only NOTE: The General Alarm Input Group must have an audible NAC A
Faraday MPC-6000, MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL 1 Introduction The MPC-6000/7000/RND-2 Fire Alarm Control Panels are completely field programmable. Although programming requires no special software skills, a thorough working knowledge of Fire Alarm Control Panels and devices is assumed. There are two ways to program an MPC-6000/7000/RND-2 fire alarm system control unit from the front panel keypad: 1. Auto Program. Using Auto Program will quickly configure the FACP in a General Alarm configuration. 2. Manual Program. Editing the program manually using the ke
Faraday MPC-6000, MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL 34 Installing the DACT Setting the System Reporting Type must be selected before installing the DACT. See page 36. Following are the steps that need to be followed to install the DACT. Action 1. Select “Edit”. 2. Select “Manual Pgm”. 3. Select “Outputs”. 4. Use “Cmor” and select “Option Mods”. 5. Select “ DACT CFG”. 6. Follow the screen prompts to set up the DACT. These are the parameters that need to be set when installing the DACT. Test Time The time that the DACT will regularly call in to the central station to check the connection.
Faraday MPC-6000, MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL 10 The programming model of the system The following diagram shows the programming model of the MPC-6000 and MPC-7000 systems. 22 1 32 12 T T T T Input group Output Zones up to 255 An input group can activate any or all Output Zones. Releasing Circuit, NACs and Audible bases can connect to one and only one output Zone. Input devices can belong to one local input group. Monitor modules and detector base relays can connect to one and only one output zone. Remote relays and remote LEDs connect to output zones. Each input device can be configured for ty
Faraday MPC-6000, MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL 37 Printing the Primary/Backup Configuration (For Diagnostics Test Only) The primary/backup configurations may be printed via the printer port on the panel. Action Result 1. Select “Print Configs”. 2. Select “Print”. 3. Select “Print Primary” or “Print Backup”. The configuration will be printed on the printer connected to the panel printer port. Validating the Backup Configuration The validation process will check to see that the c
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL 24 Configuring NAC sound time for Quick Test The period of time that the NACs will be active after each event in Quick Test is set as follows: Action Result 1. Press “Quick Test”. 2. Press “Configure”. 3. Press “NAC time”. The display will indicate the time in seconds that the NACs wil
Faraday MPC-6000, MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL 44 Signaling Line Circuit (SLC). A circuit to which intelligent devices are connected. Also called a detection loop. A detection loop in the case of the MPC-6000 and MPC-7000 may contain up to 252 detectors or devices, all of which may have outputs. Each detection loop will be driven by an FDLC (Faraday device loop card). Supervisory Alarm. A signal indicating the operation of a supervisory device. Supervisory Device. A device that monitors the condition of a sprinkler system
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL 17 Maintenance Level Following are the details of the Maintenance level functions. Enabling/Disabling Devices The disable / enable screens allow the operator to disable or enable devices and components of the system. System Inputs, Outputs, etc., can be disabled / enabled. NOTE: When a device is already enabled, the disable option is dis
Faraday MPC-6000, MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL 8 Step Number Configure Description 4 Devices Set the address and other parameters for each of the devices that will be installed into the system. Configure the input group of each device. Note that devices must be connected to an input group for any output to be activated. If the panel is networked, also setup the network group that this device will activate. 5 Notifications appliance circuits Configure the behavior of the NACs and the output zone that will activate each NAC. Note that a NAC must be configured as
Faraday MPC-6000, MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL 12 Monitor Modules with relay and single input Parameter Description Label Generic label identifying the detector by loop number and address. Led off LED will be defaulted to ON. Input Usage Input usage will be defaulted to alarm. Input Group Inputs will be defaulted to input group 241 (General Alarm). Network Group This will not be set and will need to be set manually. (Future use) Output Type Will be defaulted to non-silenceable. Output Zone Will be defaulted to 1. Intelligent LEDs Parameter Description Label Generic label identifying the d
Faraday MPC-6000, MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL 9 Programming Concepts Program Memory The program memory consists of two components, the PRIMARY (active) configuration and the BACKUP (editable) configuration. The primary configuration is the active (running) configuration that determines the current function of the FACP. The backup configuration is the configuration that is edited to make changes or additions to the existing active panel program. This allows the program to be edited while the FACP operates normally. Before the backup configuration is activated, it first must be val
Faraday MPC-6000, MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL 4 Interface for the Technician Level When the Technician Level is accessed using the password, the LCD display and the keypad are used to program the panel, and to view the programming if desired. The display acts as a menu and the keypad allows the user to navigate through the menu of functions and change or print the programming. The following figure describes the navigation used in this context: A-esc: will backup to previous screen B-fn1: will perform function 1 C-fn2: will perform function 2 D-Nx
Faraday MPC-6000, Table Of Contents Introduction............................................................................................................................. 1 The Access levels ..................................................................................................................... 1 User Level ..............................................................................................................1 Maintenance Level..................................................................................................2
Faraday MPC-6000, MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL 38 Enabling the Network Connection to the Panel This setting is used when the control panel is to be connected to a network. The networking communications in the panel must be enabled as follows: Action Result 1. Select “Edit”. 2. Select “Manual Pgm”. 3. Press “Cmor” twice to select “Network Setup”. 4. Select “1” to install the network or “0” to remove the network setting. When “1” is selected, Dnxt appears so other network settings can be made. Setting the Node Nu
Faraday MPC-6000, MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL 13 Not included in auto-program The following devices cannot be detected automatically: • Bell Codes • Serial Remote Processor LEDs • Serial Remote Processor Relays • DACT • City Tie • Releasing Module Programming of these points is not changed by Auto-Program and must be done manually in the panel's Technician Level.
Faraday MPC-6000, MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL 21 Setting the Time Format The time and the time format are adjustable. Action Result 1. Press “More”. 2. Press “More”. 3. Press “More”. 4. Press “Time/Date”. 5. Press “Time”. 6. Press “Set Time Format”. The display will show the current time format. 7. Use the “12 hour”, “24 hour” buttons to set the time format. Enabling Daylight Savings Time Adjustment The MPC-6000/MPC-7000/RND-2 can adjust for daylight savings automatically. Follow the steps below to enable or disable the
Faraday MPC-6000, MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL 3 The Operator Interface Interface for User and Maintenance Levels The operator interface for configuring and programming the MPC-6000/7000 uses the 4 line by 20 character LCD display, the M1 through M4 buttons on the left and right of the display and sixteen push buttons at the bottom of the interface. User Level and Maintenance Level utilize the LCD display and the four buttons (two on each side of the display) to navigate and alter the basic opera
MPC-6000/MPC-7000/RND-2 PROGRAMMING MANUAL 46 APPENDIX C: COMPATIBLE DEVICES FOR SIGNALING LINE CIRCUITS (FDLC) Model Description 8700-S Single action pull station 8700-D Dual action pull station 8700-M Metal manual pull station 8701 Single input mini monitor module 8702 Single input monitor module 8703 Dual input monitor module 8704 Monitor module with s
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL 11 The basic concept is that loop devices are configured and grouped into input groups. The input groups are set to have a certain behavior and activate output zones. The output devices―whether relay bases, audible bases, NACs, serial LEDs or Serial relays―are configured and connected to Output Zones.
ST STM32 Fire Alarms Operation & user’s manual
STM32 |
bolid SIGNAL-20P Fire Alarms Operation & user’s manual
SIGNAL-20P |
Faraday MPC-1500 Plus Fire Alarms Owner's manual
MPC-1500 Plus |
Faraday LW401 Fire Alarms Operation, installation, and maintenance manual
LW401 |
Faraday MPC-6000 Fire Alarms Programming manual
MPC-6000 |
Faraday MPC-6000 Fire Alarms Installation, operation and maintenance manual
MPC-6000 |
ZyXEL Communications 2WG Fire Alarms Operation & user’s manual
2WG |
SOMFY TaHoma serenity Fire Alarms Installation and user manual
TaHoma serenity |
# | Manufacturer | Model | Document Type | File | Updated | Pages | Size |
---|---|---|---|---|---|---|---|
1 | VTech | Giggle Lion | Operation & user’s manual | vtech/giggle-lion-3MR.pdf | 01 Jan 2023 | 7 | 0.24 Mb |
2 | BlueTree | BT-5600v2 | Quick start manual | bluetree/bt-5600v2-3I2.pdf | 23 Dec 2022 | 2 | |
3 | ATS | CC186 | Operation & user’s manual | ats/cc186-7S5.pdf | 31 May 2023 | 7 | |
4 | Toshiba | 19DV615Y | Owner's manual | toshiba/19dv615y-881.pdf | 29 Mar 2023 | 65 | 7.66 Mb |
5 | Denver | DSS-200 | Instruction manual | denver/dss-200-EKN.pdf | 22 Apr 2023 | 11 | 1.12 Mb |
6 | Miranda | SDA-122 | Manual to installation and operation | miranda/sda-122-946.pdf | 01 Aug 2022 | 12 |
First Alert
IMPORTANT! PLEASE READ CAREFULLY AND SAVE.This user’s manual contains important information about your Smoke Alarm’s operation. If you are installing this Smoke Alarm for use by others, you must leave this manual—or a copy of it—with the end user.USER’S MANUALPrinted in Mexico M08-0466-003 K1 11/14INTRODUCTIONThank you for choosing First Alert …
SMOKE AND FIRE ALARM(2 pages) |
Pittway
12 Clintonville Road,Northford, CT 06472(203) 484-7161FAX: (203) 484-7118ADocument # 5058112/9/96 Revision:P/N 50581:A ECN 96-356The LED-10NRemote Fire Annunciatorfor use with the NotifierSFP-1024Fire Alarm Control Panelwww.PDF-Zoo.com
…
NOTIFIER LED-10N(24 pages) |
Simplex
Features Remote LCD annunciator for use with Simplex® model: 4100ES and 4100U fire alarm control panels Legacy products 4100, 4120, and 4020 fire alarm control panels, and 4100/4120 Universal Transponders Information display features: Maintained display of first alarm is available with 4100ES and with 4100U at software revision 11.11 or h …
4603-9101(4 pages) |
Notifier
NORMALACTIVATED4 3 2 10010111213141511223344TENSONES6677889955UL Approved Label Here12345678901231234567890123123456789012312345678901231234567890123ADDRESSLOOP01234567890123456789101112131415LED OPERATIONAlarm:Steady REDNormal CLIP Systems:Flash REDNormal FlashScanTM:Flash GREENNote: LED is visiblethrough translucenthandle.Setting the NBG-12LX A …
NBG-12LX(2 pages) |
Kidde
© 2017 United Technologies Corporation 1 / 2 P/N P-047550-1819-EN • REV 005 • ISS 22MAR17 GSA-M278 Double Action Fire Alarm Station Installation Sheet Description The GSA-M278 Double Action Fire Alarm Station is an addressable, normally-open, dry contact signal initiating device that requires two user actions to initiate an alarm. First, the upper …
GSA-M278(2 pages) |
Simplex
Features Releasing control using the Simplex® 4100ES (or 4100U) Fire Alarm Control Panel to provide**: Coverage for multiple areas of Automatic Extinguishing Release and/or Deluge and Preaction Sprinkler System Release including audible escalation of events Control of compatible Listed/Approved 24 VDC automatic control actuators, one per circuit …
4100ES(8 pages) |
Vulcan-Hart Kettle VELT100Replacement parts catalog for Vulcan-Hart VELT100 Kettle VELT100, 8 |
Philips Other HP350/11Other PDF Manual HP350/11, 2 |
Singer Other 152W1Other PDF Instructions for using and adjusting 152W1, 11 |
Life Fitness Stepper Machine LS-9500HRPDF Guide (@HFM5EJ), Life Fitness LS-9500HR Stepper Machine (Saturday 02-12-2023) LS-9500HR, 3 |
Avaya IP Phone 3701Avaya IP Phone Operation & user’s manual (File: avaya-3701-cordless-telephone-46, Sat 10.2023) 3701, 46 |
Aruba Wireless Access Point AP-100 SeriesAruba AP-100 Series User Guide (Doc Type: Wireless Access Point Installation manual) AP-100 Series, 2 |
Linksys Network Router RV082Linksys Product User Guide: RV082 PDF Operation & user’s manual - 69VGJF RV082, 105 |
Metrologic Scanner MS6130Metrologic Scanner MS6130 Installation and user manual MS6130, 45 |
TERK Technologies TV Antenna TV44#9OMS81 TV44: TERK Technologies TV Antenna Owner Documentation TV44, 9 |
Panasonic Flat Panel TV TY-WK32LX20WFlat Panel TV #Q966PO TY-WK32LX20W, 24 |
Ricoh Disc Duplicator UC5Operator's manual for Ricoh UC5 Disc Duplicator UC5, 44 |
Uniden Two-Way Radio GMR535-2Uniden GMR535-2 User Guide (Reference manual), @A7ROZA GMR535-2, 2 |