Text of Fire-Lite Alarms Fire-Watch 411UDAC User Guide:

  • Fire-Lite Alarms Fire-Watch 411UDAC, Document #51073 Rev. A 1/19/99 P/N 51073:A 65 Programming Sheets ❏ 68 Input Channel 4 Function Selection. Enter '1' for pull station; '2' for normally open contact; '3' for host panel trouble; '4' for supervisory; '5' for supervisory autoresettable; '6' for waterflow silenceable; '7' for waterflow nonsi- lenceable; '8' for process monitoring; '9' for process monitoring autoresettable. ❏ 69 ❏ 70 ❏ 71 Input Channel 1 Delay Timer. Enter 0 - 179 seconds delay. Factory default is '000' for no delay. Does not delay Input Chann

  • Fire-Lite Alarms Fire-Watch 411UDAC, Document #51073 Rev. A 1/19/99 P/N 51073:A 51 Troubleshoot Mode Battery Pressing B followed by the [ENTER/STORE] key will display the battery voltage. Note that the battery voltage display does not automatically update with a change in battery voltage. The [ENTER/STORE] key must be pressed each time a display update is desired. Shown below are the critical battery threshold conditions: Battery Voltage Normal Low Battery No Battery 13.7 VDC 10.4 VDC 8.0 VDC 12 Volt Resettable Power Pressing the Lamp Test switch will display the Resettable Power voltage. No

  • Fire-Lite Alarms Fire-Watch 411UDAC, Document #51073 Rev. A 1/19/99 P/N 51073:A 19 Operating Power 2.3 Operating Power CAUTION: Several different sources of power can be connected to the 411UDAC. Disconnect all sources of power before servicing this unit. The communicator and associated equipment may be damaged by removing and/or insert- ing modules or cables with power applied. Primary Power Source (AC) and Earth Ground Connections AC power connections are made inside the 411UDAC cabinet. The primary power source is 120

  • Document #51073 Rev. A 1/19/99 P/N 51073:A 15 Telephone Requirements and Warnings 1.9.4 For Canadian Applications The following is excerpted from CP-01 Issue 5: “NOTICE: The Industry Canada (IC) label identifies certified equipment. This certification means that the equipment meets certain telecommunications network protective, operational and safety req

  • Fire-Lite Alarms Fire-Watch 411UDAC, Telephone Requirements and Warnings 14 Document #51073 Rev.A 1/19/99 P/N 51073:A 1.9 Telephone Requirements and Warnings 1.9.1 Telephone Circuitry - PH1 & PH2 AC Ringer Equivalence Number (REN) = 1.2B DC Ringer Equivalence Number (REN) = 0.0B Mates with RJ31X Male Connector Supervision Threshold: less than 4.0 volts for 2 minutes The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all a

  • Fire-Lite Alarms Fire-Watch 411UDAC, Document #51073 Rev. A 1/19/99 P/N 51073:A 53 Central Station Communications The digital communicator is capable of reporting detailed messages depending upon the Format in use. Table 4-1 shows the data reporting structure for each of the pulsed formats as well as the Ademco Express Formats. Ademco Express Formats allow a typical data message to be transmitted to the Central Station in under 5 seconds. Pulsed for- mats typically require 15 to 20 seconds in comparison. Table 4-2 defines each letter code used in Table 4-1 . See “Ademco Contact ID Format Event Code Description” on page 56 for a description of the data r

  • Fire-Lite Alarms Fire-Watch 411UDAC, Document #51073 Rev. A 1/19/99 P/N 51073:A 63 411UDAC Power Supply 6.1 411UDAC Power Supply The 411UDAC provides filtered power for operating the digital communicator, external devices and the battery charger. The power for operating external devices is limited. Use Table 6-2 (standby or nonalarm) and Table 6-3 (alarm) to determine if external loading is within the capabilities of the power supply. Notes: 1. Refer to the Device Compatibility Document for compatible listed power supervision relays. 2. Refer to Device Compatibility Document for 2-wire and 4-wire smoke detector standby current. Notes: 1. Use compat

  • Fire-Lite Alarms Fire-Watch 411UDAC, WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause inte

  • Fire-Lite Alarms Fire-Watch 411UDAC, Input Channels 22 Document #51073 Rev.A 1/19/99 P/N 51073:A FIGURE 2-6: Fire•Lite MS-9200 Connection to 411UDAC 411UDAC Note: The M300 monitor module input, which is being used to monitor the 411UDAC Relay Output programmed for DACT Trouble (requires optional 411RK Relay Kit), must be programmed as 'DACT Trouble' at the Fire•Lite MS-9200. The 411UDAC must be programmed as a Slave Communicator (programming address 64 set to ‘2’) Fire•Lite MS-9200 411UDAC Relay 2 Output (DACT Trouble) Channel 2/Zone 2 Channel 1/Zone 1 Channel 3/Zone 3 2.2K EOL Channel 4 2.2K EOL 4.7K EOL

  • Fire-Lite Alarms Fire-Watch 411UDAC, Document #51073 Rev. A 1/19/99 P/N 51073:A 9 Specifications 1.2 Specifications AC Power - TB3 120 VAC, 60 Hz, 0.3 amps Wire size: minimum 14 AWG (2.00 mm 2 ) with 600V insulation Battery (lead acid only) - J3 Maximum Charging Circuit: Normal flat charge - 13.7V @ 0.6 amps Maximum Charger Capacity: 14 Amp Hour battery Channels/Inputs - TB2 Terminals 1 through 10 Programmable Channels 1 through 4 Power-limited circuitry Fully supervised (monitored for opens, shorts and earth fault) Normal Operating Voltage: 12.0 VDC (ripple = 100 mV maximum

  • Fire-Lite Alarms Fire-Watch 411UDAC, Remote Site Upload/Download 58 Document #51073 Rev.A 1/19/99 P/N 51073:A CHAPTER 5 Remote Site Upload/Download The 411UDAC may be programmed off site via the public switched telephone network. Any personal computer with Windows ® 3.1 or greater or Windows ® 95, with a 1200 Baud Hayes compatible modem and Upload/Download soft- ware P/N PK-411UD, may serve as a Service Terminal. For details on the remote site upload/download software package, refer to the PK-411UD Manual. The Upload/Download software allows the following

  • Fire-Lite Alarms Fire-Watch 411UDAC, Program Mode 44 Document #51073 Rev.A 1/19/99 P/N 51073:A Secondary Central Station Number Account Code (51 - 54) The four locations at addresses 51 - 54 default to all '0's. Valid entries are 0 - 9 and A - F. The number of digits entered must match the format selection. If programming '2, 3, 4 or 5' into address 50, enter three digits (one digit each in locations 51, 52 and 53 - location 54 is ignored). If programming '0, 1, 6, 7, 8, 9, A, B, C, D or E' into address 50, enter four digits (one each in locations 51, 5

  • Fire-Lite Alarms Fire-Watch 411UDAC, Program Mode 40 Document #51073 Rev.A 1/19/99 P/N 51073:A Secondary Central Station Number Communication Format (50) One location is needed to select the Communication Format to the secondary phone number. Address 50 is used for this purpose. The factory default setting for this address is 'E', which is Contact ID Format. You may enter '0' through 'D' in place of the default, then press [ENTER/STORE]. Choose from the list of formats

  • Fire-Lite Alarms Fire-Watch 411UDAC, Document #51073 Rev. A 1/19/99 P/N 51073:A 41 Program Mode Ademco Contact ID Format Secondary Central Station Event Codes If ‘E’ is entered for address 50, the following data is automatically programmed for the Secondary Central Station phone number event codes. Enter '000' for the Setting to disable the report to the Central Station. TABLE 3-4: Ademco Contact ID Format - Secondary Address Description Setting Channel/ Input # 229 - 231 Secondary # Input Channel 1 Active Event Code 111 001 232 - 234 Secondary # Input Channel 2 Active Event Code 115 002 235 - 237 Secondary # Input Channel 3 Active Event Code 111 003 2

  • Fire-Lite Alarms Fire-Watch 411UDAC, Document #51073 Rev. A 1/19/99 P/N 51073:A 69 Event Codes/Transmission Format Programming Sheets Appendix B Event Codes/Transmission Format Programming Sheets --To enter Programming Mode, press the MODE key, 7764 and then the [ENTER/STORE] key. B.1 4+2 Standard & 4+2 Express Formats Primary Central Station ❏ 145 ❏ 146 ❏ 147 ❏ 148 ❏ 149 ❏ 150 ❏ 151 ❏ 152 ❏ 153 ❏ 154 ❏ 155 ❏ 156 ❏ 157 ❏ 158 ❏ 159 ❏ 160 ❏ 161 ❏ 162 ❏ 163 ❏ 164 ❏ 165 ❏ 166 ❏ 167 ❏ 168 ❏ 169 ❏ 170 ❏ 171 ❏ 172 ❏ 173 ❏ 174 ❏ 175 ❏ 176 ❏ 177 ❏ 178 ❏ 179 ❏ 180 ❏ 181 ❏ 182 ❏ 183 ❏ 184 ❏ 185 ❏ 186 ❏ 187 ❏ 188

  • Document #51073 Rev. A 1/19/99 P/N 51073:A 59 General With program address location 64 set to '1' in Program Mode, anytime a contact with callback is initiated, the commu- nicator will first either contact the primary Central Station or contact both the primary and secondary Central Stations or contact the first available

  • Fire-Lite Alarms Fire-Watch 411UDAC, Document #51073 Rev. A 1/19/99 P/N 51073:A 37 Program Mode 4+2 Standard and 4+2 Express Formats Primary Central Station Event Codes If ‘1, A or C’ is entered for address 20, the following data is automatically programmed for the Primary Central Station phone number event codes. Enter '00' for the Setting to disable the report to the Central Station. TABLE 3-2: 4+2 Standard and 4+2 Express Formats - Primary Address Description Setting 145 - 146 Primary # Input Channel 1 Active Event Code 11 147 -

  • Fire-Lite Alarms Fire-Watch 411UDAC, Document #51073 Rev. A 1/19/99 P/N 51073:A 75 Ademco Contact ID Format Event Code Description EVENT MESSAGE General Alarms - 140 140 General Alarm ALARM - General Alarm - # 141 Polling loop open ALARM - Polling Loop Open - # 142 Polling loop short ALARM - Polling Loop Short - # 143 Expansion module failure ALARM - Exp. Module Fail - # 144 Sensor tamper ALARM - Sensor Tamper - # 145 Expansion module tamper ALARM - Exp. Module Tamper - # 24 Hour Non-Burglary - 150 and 160 150 24-Hour Non-Burg ALARM - 24-Hr. Non-Burg - # 151 Gas detected ALARM - Gas Detected - # 152 Refrigeration ALARM - Refrigeratio

  • Circuits 10 Document #51073 Rev.A 1/19/99 P/N 51073:A 1.3 Circuits The 411UDAC circuit board utilizes surface mount technology and contains a MicroController Unit (MCU), dual modular phone line jacks, piezo sounder, two sockets for optional programmable relays and connectors for input, out- put and pow

  • Fire-Lite Alarms Fire-Watch 411UDAC, Document #51073 Rev. A 1/19/99 P/N 51073:A 47 Program Mode Alarm Verification Enable (91) Alarm verification works only on zones programmed as 2-wire smoke detector zones (i.e. zones 1 and 3). After detecting an alarm, the panel removes power from two-wire smoke zones for 6 seconds, resetting all 2-wire smoke detectors. Power is reapplied and a 12 second retard period allows detectors to stabilize. During the retard/reset period of 18 seconds, subsequent alarms by the same initia

Related Products and Documents (Fire Alarms):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 Audiovox FLO TV Installation manual audiovox/flo-tv-VYQ.pdf 14 Sep 2023 72
2 AWS Bioweight Manual  aws/bioweight-G95.pdf 27 May 2023 10
3 DLO Transcast FM M92007-060601-J Operation & user’s manual dlo/transcast-fm-m92007-060601-j-E6U.pdf 17 Oct 2022 8 0.12 Mb
4 RCA 32v432T Operation & user’s manual rca/32v432t-XS8.pdf 07 Aug 2022 40 1.65 Mb
5 Nikon D610 Operation & user’s manual nikon/d610-JZ1.pdf 21 Oct 2022 368
6 Precor S3.15 Assembly instructions manual precor/s3-15-H7O.pdf 27 Dec 2023 16

Similar Resources:

  • Notifier

    AVL-1

    (95 pages)
    AVL-1 Audio VoiceLink Operation and Installation Manual One Firelite Place Northford, CT 06472-1653 Telephone: 203-484-7161 Fax: 203-484-7118 Document 50120 Revision HManual Assembly) Part Number P82867 Revision H Assembly Number A82633-002 Revision E www.PDF-Zoo.comfirealarmresources.com …
  • Ziton

    ZR432-2P

    (2 pages)
    Ziton Wireless Multisensor Detector Installation GuideGeneralThe Ziton wireless mutisensor detector and ancillary equipment are available under the following part numbers:PART NO VARIANT TYPEZR432-2P Ziton multisensor wireless detector ZR401-3P Ziton wireless module only (no detector head)ZX432-2P …
  • olympia electronics

    BSR-2104/MAR

    (74 pages)
    BSR-2104/MAR, BSR-2114/MAR Addressable fire detection panel with 2 or 4 loops and expansion capabilities Operation and installation manual …
  • Advanced

    MxPro4 Series

    (72 pages)
    Installation & Commissioning The operation and functions described in this manual are available from Software Version Mx4200V-023 and Mx4400V-023 onwards. www.acornfiresecurity.comwww.acornfiresecurity.com …
  • Fike

    TWINFLEXpro

    (26 pages)
    26-1192 Issue 1 Fire Detection & Alarm System Repeater Panel (Suitable for TWINFLEX®pro control panels from V2.00) Repeater Panel Engineering and Commissioning Manual (TO BE RETAINED BY THE COMMISSIONING ENGINEER) …
  • Evonicfires

    DOUBLE SIDED E810 DS

    (18 pages)
    1EVONIC - 104 INSTRUCTION MANUAL ISS. 11EVONIC - 104 INSTRUCTION MANUAL ISS. 11DOUBLE SIDEDDOUBLE SIDEDEvoflame & E-SmartEvoflame & E-SmartINSTRUCTION MANUALINSTRUCTION MANUALE810 DSE810 DSE1030 DSE1030 DSStora DSStora DSLindstrom DSLindstrom DSEnglishEnglish …

Comments, Questions and Opinions: