  • Galleon 1K, 2 1-5. Maintenance, service and faults  The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel.  Caution - risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous.  Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacit

  • Galleon 1K, 14  09: Bypass frequency range setting Interface Setting Parameter 1 & 2:Set the acceptable high frequency point and acceptable low frequency point for Bypass mode by pressing the Down key or Up key. HLS: Bypass high frequency point For 50Hz output frequency models: 51-55Hz: setting the frequency low loss point from 51Hz to 55HZ(Default: 53.0Hz) For 60Hz output frequency models: 61-65Hz: setting the frequency low loss point from 61Hz to 65Hz(Default: 63.0Hz) LLS: Bypass low Frequency point For 50Hz output frequency models: 45-49Hz: setting the frequency low

  • Galleon 1K, 15  13: Battery total AH setting Interface Setting Parameter 2: Set up the battery total AH of the UPS. 7-999: setting the battery total capacity from 7-999 in AH. Please set the correct battery total capacity if external battery bank is connected.  14: Maximum charger current setting Interface Setting Parameter 2: Set up the maximum charger current. When the UPS is equipped with additional charger, the available setting options are 2/3/4. 2/3/4: setting the maximum charger curre

  • Galleon 1K, 18 4. Troubleshooting If the UPS system does not operate correctly, please solve the problem by using the table below. Symptom Possible cause Remedy No indication and alarm even though the main is normal. The AC input power is not connected well. Check if input power cord firmly connected to the mains. The AC input is connected to the UPS output. Plug AC input power cord to AC input correctly. The icon and the warning code flashing on LCD display and alarm is sounding every 2 second

  • 5 Step 3: Communication connection Communication port: USB port RS-232 port Intelligent slot To allow for unattended UPS shutdown/start-up and status monitoring, connect the communication cable one end to the USB/RS-232 port and the other to the communication port of your PC. With the monitoring software i

  • 11 3-3. Audible Alarm Battery Mode Sounding every 5 seconds Low Battery Sounding 2 seconds Overload Sounding every second Fault Continuously sounding 3-4. LCD display wordings index Abbreviation Display content Meaning ENA Enable DIS Disable ESC Escape HLS High loss LLS Low loss BAT Battery BAH Bat

  • Galleon 1K, 4 7. USB communication port 8. RS-232 communication port 9. SNMP intelligent slot 10. External battery connector (only available for long-run models) 11. Output circuit breaker 2-2. Install the UPS For safety consideration, the UPS is shipped out from factory without connecting battery wires. Before install the UPS, please follow below steps to re-connect battery wires first. Step 1 Step 2 Step 3 Remove front panel. Connect the AC input and re-connect battery wires. Put the front panel back to the unit. This UPS can be either displayed on the desk or mounted in the 19” rack chas

  • Galleon 1K, 1 1. Important Safety Warning Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully 1-1. Transportation  Please transport the UPS system only in the original package to protect against shock and impact. 1-2. Preparation  Condensation may occur if the UPS system is moved directly from cold to warm environment. The UPS sy

  • Galleon 1K, 3 2. Installation and setup NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use. NOTE: There are two different types of online UPS: standard and long-run models. Please refer to the following model table. Model No. Type Model No. Type 1K Standard 1KL Long-run 1.5K 1.5KL 2K 2KL 3K 3KL 2-1 Rear panel view 1K/1.5K IEC 2K IEC 3K IEC 1K NEMA 1.5K NEMA 2K NEMA 3K NEMA 1. Programmable outlets: connect to non-c

  • Galleon 1K, 19 Symptom Possible cause Remedy Fault code is shown as 43 and The icon is lighting on LCD display and alarm is continuously sounding. The UPS shut down automatically because of overload at the UPS output. Remove excess loads from UPS output and restart it. Fault code is shown as 14 and alarm is continuously sounding. The UPS shut down automatically because short circuit occurs on the UPS output. Check output wiring and if connected devices are in short circuit status. Fault code is shown as 01, 02, 03, 11,

  • Galleon 1K, 12  01: Output voltage setting Interface Setting Parameter 3: Output voltage For 200/208/220/230/240 VAC models, you may choose the following output voltage: 200: presents output voltage is 200Vac 208: presents output voltage is 208Vac 220: presents output voltage is 220Vac 230: presents output voltage is 230Vac (Default) 240: presents output voltage is 240Vac For 100/110/115/120/127 VAC models, you may choose the following output voltage: 100: presents output voltage is 10

  • Galleon 1K, 17 3-8. Warning indicator Warning Icon (flashing) Alarm Low Battery Sounding every 2 seconds Overload Sounding every second Battery is not connected Sounding every 2 seconds Over Charge Sounding every 2 seconds Site wiring fault Sounding every 2 seconds EPO enable Sounding every 2 seconds Over temperature Sounding every 2 seconds Charger failure Sounding every 2 seconds Battery fault Sounding every 2 seconds (At this time, UPS is off to remind users something wrong with battery) Out of bypass voltage range S

  • Galleon 1K, 7 2-5 Battery Kit Assembly (option) NOTICE: Please assemble battery kit first before installing it inside of UPS. Please select correct battery kit procedure below to assemble it. 2-battery kit Step 1: Remove adhesive tapes. Step 2: Connect all battery terminals by following below chart. Step 3: Put assembled battery packs on one side of plastic shells. Step 4: Cover the other side of plastic shell as below chart. Then, battery kit is assembly well. 3-battery kit Step 1: Remove adhesive tapes. Step 2: Connect all battery terminals by following below chart. Step 3: Put assembled battery packs on one side of plastic shells as be

  • Galleon 1K, 9 3. Operations 3-1. Button operation Button Function ON/Mute Button  Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to turn on the UPS.  Mute the alarm: After the UPS is turned on in battery mode, press and hold this button for at least 3 seconds to disable or enable the alarm system. But it’s not applied to the situations when warnings or errors occur.  Up key: Press this button to display previous selection in UPS setting mode.  Switch to UPS self-test mode: Press ON/Mute buttons for 3 seconds to enter UPS self-testing while in AC mode, ECO

  • Galleon 1K, 10 Display Function Backup time information Indicates the estimated backup time. H: hours, M: minute, S: second Configuration and fault information Indicates the configuration items, and the configuration items are listed in details in section 3-5. Indicates the warning and fault codes, and the codes are listed in details in section 3-7 and 3-8. Mute operation Indicates that the UPS alarm is disabled. Output information Indicates the output voltage and output frequency. Vac: AC voltage, Vdc: DC voltage, Hz: frequenc

  • Galleon 1K, Table of Contents 1. Important Safety Warning ....................................................................... 1 1-1. Transportation ................................................................................. 1 1-2. Preparation ..................................................................................... 1 1-3. Installation ..................................................................................... 1 1-4. Operation ....................................................................................... 1 1-5. Maintenance, service and faults ......................

  • Galleon 1K, 16 3-6. Operating Mode Description Operating mode Description LCD display Online mode When the input voltage is within acceptable range, UPS will provide pure and stable AC power to output. The UPS will also charge the battery at online mode. ECO mode Energy saving mode: When the input voltage is within voltage regulation range, UPS will bypass voltage to output for energy saving. The UPS will also charge the battery at ECO mode. AECO mode (Advanced Efficiency Co

  • Galleon 1K, 20 MODEL 1K 1.5K 2K 3K Capacity* VA/W 1000 VA / 900 W 1500 VA / 1350 W 2000 VA / 1800 W 3000 VA / 2700 W INPUT Voltage Range Low Line Transfer 80 VAC/70 VAC/60 VAC/55 VAC ± 5 % or 160 VAC/140 VAC/120 VAC/110 VAC ± 5 % (based on load percentage 100%-80% / 80%-70% / 70%-60% / 60%-0) Low Line Comeback 85 VAC/75 VAC/65 VAC/60 VAC ± 5 % or 170 VAC / 150 VAC / 130 VAC / 120 VAC ± 5 % High Line Transfer 150 VAC ± 5 % or 300 VAC ± 5 % High Line Comeback 140 VAC ± 5 % or 290 VAC ± 5 % Freque

  • 6 2-4 Battery Replacement NOTICE: This UPS is equipped with internal batteries and user can replace the batteries without shutting down the UPS or connected loads.(hot-swappable battery design) Replacement is a safe procedure, isolated from electrical hazards. CAUTION!! Consider all warnings, cautions, and notes before replacing batteries. Note: Upon battery discon

  • Galleon 1K, 13  06: ECO voltage range setting Interface Setting Parameter 1 & 2: Set the acceptable high voltage point and low voltage point for ECO & AECO mode by pressing Down key or Up key. HLS: High loss voltage in ECO & AECO mode in parameter 2. For 200/208/220/230/240 VAC models, the setting range in parameter 3 is from +7V to +24V of the nominal voltage. (Default: +12V) For 100/110/115/120/127 VAC models, the setting range in parameter 3 is from +3V to +12V of the nominal voltage. (Default: +6V) LLS: Low loss voltage in ECO & AECO mode

Related Products and Documents (UPS):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 NorthStar VHF Marine Explorer 721EU Operation and installation manual northstar/vhf-marine-explorer-721eu-EZ9.pdf 14 Sep 2023 61
2 McCulloch MS1432 Operation & user’s manual mcculloch/ms1432-E94.pdf 11 May 2023 42
3 RCA L42FHD37 - LCD HDTV Specifications rca/l42fhd37-lcd-hdtv-G9K.pdf 19 May 2023 2 0.57 Mb
4 Fluke 5700A Series II Service Operator's manual fluke/5700a-series-ii-service-4JS.pdf 14 Dec 2022 336 3.49 Mb
5 Pro-Form PFEL54932 Operation & user’s manual proform/pfel54932-T5K.pdf 28 Mar 2023 24
6 Haier AE072FCBKA Operation and installation manual haier/ae072fcbka-711.pdf 20 Mar 2023 10 1.6 Mb

Similar Resources:

  • Minuteman

    ED6200RM

    (27 pages)
    Para Systems, Inc. 1455 LeMay Drive Carrollton, TX 75007 Phone: 1-972-446-7363 Fax: 1-972-446-9011 Internet: minutemanups.com UPS Sizing: sizemyups.com PN – 34000315 R5 ED6200RM Parallel Redundant ON-LINE SERIES User’s Manual …
  • GE

    Match

    (11 pages)
    Match 19"Uninterruptible Power Supply700 - 1500 VAManufactured by:GE Digital EnergyGeneral Electric Company Telephone +41 (0)91 / 850 51 51CH – 6595 Riazzino (Locarno) Fax +41 (0)91 / 850 51 44Switzerland Website www.gedigitalenergy.comGE Digital EnergyTechnology for the Digital World.ver 3.0 - GBMatch 19" UPSg …
  • GE

    300

    (2 pages)
    Max.Hp For AC Motors Max. Volt- age Max. Continous Amp Rating AC Volts Single-Phase Poly- Phase 600 90 115 200 230 460/575 7½ - 15 - - 25 30 50 CAUTION: Before installing in a nuclear application, determine that the product is intended for such use. WARNING: Disconnect power before Installing or …
  • CyberPower

    600ELCD

    (2 pages)
    Value 600ELCD/800ELCD/1000ELCD User’s Manual Rev.A SAFETY WARNINGS (SAVE THESE INSTRUCTIONS) This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate your UPS. T …
  • Eaton

    93PM 150 kW SIAC-B Three-Wire

    (102 pages)
    p/n: P-164000387Revision 08150 kW SIAC-B Three-Wire150 kW SIAC-B Four-Wire200 kW SIAC-B Three-Wire200 kW SIAC-B Four-WireInstallation and Operation ManualEaton®®93PM Sidecar Integrated Accessory Cabinet-Bypass …
  • BPC

    5000VA

    (22 pages)
    PowerPrem Line-interactive UPS User’s Manual 5000VA 5K-02 0 …

Comments, Questions and Opinions: