  • 9. TROUBLESHOOTING 9-1. Check before and after troubleshooting 9-1-1. Check power supply wiring. ● Check that power supply wires are correctly connected to terminals No. 1 and No. 2 on the 3p terminal plate in the outdoor unit. 9-1-2. Check inter-unit wiring. ● Check that inter-unit wiring is correctly connected to the indoor unit from the outdoor unit. 9-1-3. Check power supp

  • Argo Clima AWR512CL, 15 6-1. Installation Site Selection Maximum Allowable Tubing Length(L) and Elevation Difference(H). The Multi-Split System outdoor unit should be installed as close to the indoor units as possible. Maximum allowable length of the refrigerant tubing and elevation difference between outdoor and indoor units are shown in Fig.1 and Table 1. Table.1 * If total tubing length becomes 7.5 to 20 m (max.), charge additional refrigerant (R407c) by 25 g/m. No additional charge of compressor oil is necessary. 6-2. Place and Space fo

  • 4. REFRIGERANT FLOW DIAGRAM Applicable Indoor Unit : AWR512CL (x2) FCR512CL (x2) Outdoor Unit : AER524DC 10 Outdoor Unit Wide tube O.D. ø12.7 mm (1/2 ") Narrow tube O.D. ø6.35 mm (1/4") Condenser Wide tube service valve Compressor A Accumulator Compressor B B A A Narrow tube service valve Capillary tube Drier B Accumulator Evaporator Indoor Unit A Evaporator Indoor

  • Argo Clima AWR512CL, Indoor Unit FCR512CL Remote control unit 86 74 74 Center of tubing hole ø75 (4 places) Wide tube ø12.7 (1/2") Narrow tube ø6.35 (1/4") Drain hose ø26 74 74 900 86 41 41 190 680 18.5 61 172.5 Unit : mm 9

  • (6) Recharging • Be sure to charge the specified amount of refrigerant in liquid state using the service port of wide tube service valve. The proper amount is listed on the unit's nameplate. When the entire amount cannot be charged all at once, charge gradually while operating the unit in Cooling Operation. ● Never charge a large amount of liquid refrigerant at

  • Argo Clima AWR512CL, 3. DIMENSIONAL DATA 7 Outdoor Unit AER524DC 620130 100 55 20 20 325 835 850 80 138 5887 310 285 178 58 58 1 2 3 4 Narrow tube service valve ø6.35 (1/4") 1 Wide tube service valve ø12.7 (1/2") Power supply wires connection 3 Inter-unit wires connection 2 4 Unit : mm

  • Argo Clima AWR512CL, 11-2. Checking Motor Capacitor Remove the lead wires from the capacitor terminals, and then place a probe on the capacitor terminals as shown in Fig. 5. Observe the deflection of the pointer, setting the resistance measuring range of the multimeter to the maximum value. The capacitor is “good” if the pointer bounces to a great extent and then gradually returns to its original position. The range of deflection and deflection time differ according to the capacity of the capacitor. 34 Multimeter Ω Compressor motor capacitor Fan motor capacitor Fig.5

  • 7-7. Charging additional refrigerant 7-7-1.When tubes are extended • Observe the proper amount of refrigerant as stated in this service manual or the installation manual that came with the indoor unit. Charge additional refrigerant in liquid state. ● Never charge additional refrigerant if refrigerant is leaking from the unit. Follow instructions given in "10-6. In case refrige

  • Argo Clima AWR512CL, Table of Contents Page 1 OPERATING RANGE 1 2 SPECIFICATIONS 2-1 Unit Specification 2 2-2 Major Component Specifications 4 2-3 Other Component Specifications 6 3 DIMENSIONAL DATA 7 4 REFRIGERANT FLOW DIAGRAM 10 5 ELECTRICAL DATA 5-1 Electrical Characteristic 11 5-2 Electric Wiring Diagrams 12 5-3 Performance Charts 14 6 INSTALLATION INSTRUCTION 6-1 Installation Site Selection 15 6-2 Place and Space for Installation 15 6-3 Wi

  • 5-3. Performance Charts 14 Indoor Unit AWR512CL (x1) FCR512 (x1) Outdoor Unit AER524DC 13 12 11 10 9 8 7 6 25 30 35 40 45 50 Outdoor inlet air D.B. temp. (°C) 5 4 3 Indoor inlet air D.B. temp. (°C) ■ Cooling Characteristics Indoor inlet air D.B. temp. (°C) 11 10 9 8 7 6 5 4 3 25 30 35 40 45 50 Outdoor inlet air D.B. temp. (°C) Operating current (A) 12 Low pressur

  • Argo Clima AWR512CL, 35 12-1. Removing Air Intake Grille (1) Hold both ends and pull forward to open the air intake grille. (Fig. 1) (2) Remove the metal clips connecting the unit and the grille. First, with a screwdriver, loosen the * marked screw a little at the right side clip (DO NOT loosen it too much, otherwise, the screw and small metal parts will fall off inside.), then press on the stopper and pull off. (Fig. 2) (3) Do the same procedure for the left metal clip. (4) Unlatch the 2 tabs on the lower part of the grille to take it off completely. 12. DISASSEMBLY PROCEDURE FOR INDOOR UNIT IMPORTANT! Please Read Before Starting Safety precauti

  • Argo Clima AWR512CL, Indoor Unit FCR512CL Controller PCB Part No. POW-K185GS-N Controls Microprocessor Control circuit fuse 250 V 3 A Remote Control Unit RCS-5PS3E Fan & Fan Motor Type Cross-flow Q'ty ... Dia. and length mm 2 ... ø130 / L180 Fan motor model ... Q'ty K48407-M01416 ... 1 No. of poles ... rpm (230 V, High) 4 ... 1,160 Nominal output W 20 Coil resistance (Ambient temp. 20°C) Ω GRY-WHT : 311±7% WHT-VLT : 97.6±7% VLT-YEL : 97.6±7% WHT-PNK : 425±7% —— Safety devices T

  • Argo Clima AWR512CL, 5-2. Electric Wiring Diagram 12 Outdoor Unit AER524DC TO INDOOR UNIT B TO INDOOR UNIT A POWER SUPPLY TERMINAL PLATE (4P)X2 Ground 4 3 2 1 4 3 2 1 2 1 YEL GRN/YEL GRN/YEL GRN/YEL GRN/YEL GRN/YEL RELAY A RELAY B WHT BLK RED WHT BLK RED YEL WHT YEL BLU BRN PNK GRY CAPACITOR C1 CAPACITOR C3 CAPACITOR C2 THERMOSTAT(23S) RED RED BRN BRN BLK RED RED BRN TERMINAL PLATE(3P) GRN/YEL RED RED BRN BRN BLU RED BRN BRN WHT WHT BLK BLK RB RA 0 1 6 8 2 4 6 8 2 4 0 1 OVERLOAD RELAY 3 OVERLOAD RELAY 4 OVERLOAD RELAY 1 OVERLOAD RELAY 2 G GGG COMPRESSOR MOTOR

  • Argo Clima AWR512CL, 2-2. Major Component Specifications DATA SUBJECT TO CHANGE WITHOUT NOTICE. 4 Type Rotary (Hermetic) Compressor model…Q'ty / Code number C-RN110H5B … 2 / 802356-45B Nominal output W 1,100 Compressor oil ... Amount cc FV68S ... 550 Coil resistance (Ambient temp. 25°C) Ω C – R : 1.962 C – S : 5.38 Type External (OLR A) External (OLR T) Safety Overload relay … Q'ty MRA98596-9201 CS–7C115 devices Operating Open °C 145 ± 5 115 ± 3 temp. Close °C 69 ± 11 95 ± 5 Operating amp.(Ambient temp. 25°C) Trip in 6 to 16 sec.

  • Argo Clima AWR512CL, 3 Indoor Unit FCR512CL x 2 Outdoor Unit AER524DC Power Source 220–240V ~ 50Hz Voltage rating 230 V Performance Cooling Max Capacity kW 6.70 BTU/h 22900 Air circulation (High) m 3 /h 700 x 2 Moisture removal (High) Liters/h 1.30 x 2 Electrical Rating Cooling Available voltage range V 198 ~ 264 Running amperes A 12.5 Power input W 2650 Power factor % 93 C.O.P. W/W

  • Argo Clima AWR512CL, Indoor Unit AWR512CL Controller PCB Part No. POW-K8E(A), POW-K8E(B) Controls Microprocessor Control circuit fuse 250 V 3.15 A Remote Control Unit RCS-8PS3E Fan & Fan Motor Type Cross-flow Q'ty ... Dia. and length mm 1 ... ø95 / L617 Fan motor model ... Q'ty KFV4Q-11H5P-S ... 1 No. of poles ... rpm (230 V, High) 4 ... 1,230 Nominal output W 10 Coil resistance (Ambient temp. 20°C) Ω BRN-WHT : 561.8 VLT-WHT : 197.4 VLT-ORG : 63.4 YEL-ORG : 155.7 YEL-PNK : 115.9 Safety devices Type Internal fuse Operating temp. Open °C 145±2 Close — Run capacitor µF 1.0 VAC 440 Flap Motor

  • Argo Clima AWR512CL, 5. ELECTRICAL DATA 5-1. Electrical Characteristics 11 Outdoor Unit AER524DC The values in the table below indicate the sum of indoor and outdoor units which are in running condition. NOTE 230 V Single phase 50Hz Number of Indoor Unit 1-Unit 2-Units Rating Conditions Running Amps. A 6.20 12.50 Power Input kW 1.32 2.65 Full Load Conditions Running Amps. A 7.2 14.5 Power Input kW 1.55 3.15 Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B. Outdoor Air Temperature 35�

  • Argo Clima AWR512CL, TECHNICAL & SERVICE MANUAL Outdoor Unit MULTI-SPLIT SYSTEM AIR CONDITIONER Outdoor Unit AER524DC AWR512CL Ceiling-Mounted Floor-Mounted FCR512CL Indoor Unit FCR512CL AWR512CL AER524DC 0.8180.133.0 04/2001 ®

  • Argo Clima AWR512CL, 11-1 Measurement of Insulation Resistance ● The insulation is in good condition if the resistance exceeds 2MΩ. 11-1-1. Power Supply Wires Clamp the ground wire of the power supply wires with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on either of the power wires. (Fig. 1) Then measure the resistance between the ground wire and the other power wire. (Fig. 1) 11-1-2. Outdoor Unit Clamp a metallic part of the unit with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on each terminal screw where power supply lines are connected on the terminal pla

  • Argo Clima AWR512CL, 10. ARRANGEMENT OF ELECTRICAL COMPONENT 32 2 1 1 2 3 4 1 2 3 4 Terminal plate ( 4P ) ( To indoor unit A ) Terminal plate ( 4P ) ( To indoor unit B ) Relay ( RB ) Relay ( RA ) Compressor moter capacitor C3 Compressor moter capacitor C2 Overload relay 1 Overload relay 3 Fan moter capacitor C1 Terminal plate ( 3P ) ( From power supply ) Outdoor Unit AER524DC ● Electric Parts ● Parts Layout in Unit Compressor A (CMA) Compressor B (CMB) Fan motor Heat exchenger coil

  • Argo Clima AWR512CL, 7-5. In case of compressor malfunction ● Should the compressor malfunction, be sure to replace compressor as quickly as possible. ● Use only the tools indicated exclusively for R407C. ➞ See "7-3. Tools specifically for R407C". 10-5-1.Procedure for replacing compressor (1) Recovering refrigerant • Any remaining refrigerant inside the unit should not be released to the atmosphere, but recovered using the refrigerant recovery unit for R407C. • Do not reuse the recovered refrigerant, since will contain impurities. (2) Replacing compressor • Soon

  • Argo Clima AWR512CL, 38 (3) Remove the 6 screws of the front panel and pull it toward you. (Fig. 9) (4) Remove the 2 screws used to mount the evaporator. (Fig. 10) (5) Remove the rubber cap to pull the thermistor out of the evaporator. (Fig. 10) (6) Cut the plastic clamp securing the drain hose to the front fan casing. (Fig. 10) (7) The evaporator is built into the drain pan. Pull out the drain pan together with the evaporator in the direction of the arrow. (Fig. 10) The foamed polystyrene drain pan is fragile: DO NOT apply excessive force when removing it. (8) The evaporator can be removed by sliding it out from the drain pan in the direction of the arrow. (Fig

  • Argo Clima AWR512CL, 2 Indoor Unit AWR512CL X 2 Outdoor Unit AER524DC Power Source 220–240V ~ 50Hz Voltage rating 230 V Performance Cooling Max Capacity kW 6.70 BTU/h 22900 Air circulation (High) m 3 /h 490 x 2 Moisture removal (High) Liters/h 1.2 x 2 Electrical Rating Cooling Available voltage range V 198 ~ 264 Running amperes A 12.5 Power input W 2650 Power factor % 93 C.O.P. W/W 2.7 Compressor locked rotor amperes A 66 Features Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless

  • Argo Clima AWR512CL, Valve Valve Single valve Charge the liquid refrigerant with the cylinder in the up-side-down position. Single valve (with siphon tube) Charge with the cylinder in the normal position. Liquid Liquid 20 Configurations and characteristics of cylinders Charging cylinder Open Refrigerant cylinder Liquid NO! Fig. 2 Fig. 1 Fig.3 (5) Recharging • Be sure to charge the specified amount of refrigerant in liquid state using the service port of wide tube service valve. The proper amount is listed on the unit's nameplate. When the entire amount cannot be charged all at once, charge gradually while operating the unit in Cooling Operation. ● Never charge a larg

  • Argo Clima AWR512CL, 37 12-4. Removing Flap Motor (1) Remove the 3 screws used to mount the top panel. (Fig. 6) (2) While unlatching the 2 tabs inside the back of the top panel, lift the top panel diagonally in the direction of the arrow.(Fig. 6) (3) Remove the 2 screws to pull off the flap motor. The arm and cam come off together with the motor. (Fig. 7) 12-5. Removing Evaporator (=Indoor Heat Exchange Coil) (1) Remove the 7 screws used to mount the blades. (Fig. 8) (2) Lift the blades in the direction of the arrow.(Fig. 8) Top panel Flap motor Screw Blade Arm Cam Screw Flap motor Screw Blades Fig.6 Fig.7 Fig.8

Related Products and Documents (Air Conditioner):

Comparable Devices:

# Manufacturer Model Document Type File Updated Pages Size
1 CrimeStopper SV-9000 Installation manual crimestopper/sv-9000-89Y.pdf 20 Nov 2023 6 0.25 Mb
2 Dynex DX-TRPFLX Manual d'installation rapide dynex/dx-trpflx-B3S.pdf 01 Oct 2022 1 0.14 Mb
3 Akai MPC 2000XL Operator's manual akai/mpc-2000xl-2JV.pdf 05 Feb 2024 208 1.34 Mb
4 Lennox SLDVT-40 Care and operation instructions manual superior/sldvt-40-5NF.pdf 04 Mar 2023 24
5 Ambient Weather WS-YG313-G Operation & user’s manual ambient-weather/ws-yg313-g-P3A.pdf 04 Feb 2024 5
6 Sony MDR-G75LW Operating instructions sony/mdr-g75lw-93K.pdf 08 Jan 2023 2 0.16 Mb

Similar Resources:

  • Toyotomi

    CFT 35 INV-Ri

    (99 pages)
    Service ManualMODEL: CFT 35 INV-Ri CFT 50 INV-Ri CFT 70 INV-Ri CFT 100 INV-Ri CFT 140 INV-Ri CFT 170INV-Ri …
  • Bard

    CTHAC181-A

    (19 pages)
    Installation InstructionsManual No.: 2100-292Date: 12-19-96Outdoor Condens-ingSectionModels: CTHAC181-A CTHAC181-DCTHAC241-A CTHAC241-DCTHAC301-A CTHAC301-DCTHAC361-A CTHAC361-GCTHAC421-A CTHAC421-ECTHAC421-F CTHAC421-GCTHAC481-A CTHAC481-BCTHAC481-E CTHAC481-ECTHAC481-G CTHAC601-ACTHAC601-B CTHAC601-ECTHAC601-F CTHAC601-GFor Use With:Matching Indoor Blower …
  • Honeywell

    CO25MM

    (40 pages)
    Portable Evaporative Air CoolerEnfriador de Aire Portátil por EvaporaciónOWNER’S MANUALRead and save these instructions before useMANUAL DEL USUARIOLea y guarde estas instrucciones antes de usarModel: CO25MMModelo: CO25MMPower rating: 1.58A/190WMade in P.R.C.Fabricado en ChinaCustomer Support : 1-800-474-2147Centro de servicios al cliente: 1-800-474-2147 …
  • Mitsubishi Electric

    MSZ-HA25VA-E1

    (32 pages)
    CONTENTS1. TECHNICAL CHANGES ····································22. PART NAMES AND FUNCTIONS······················23. SPECIFICATION·················································44. NOISE CRITERIA CURVES·······················� …
  • York

    13 Seer-TCG

    (16 pages)
    Johnson Controls Unitary Products 835964-UIM-A-0112R-410AOUTDOOR SPLIT-SYSTEM AIR CONDITIONINGMODELS: 13 & 14.5 SEER - TCG(D,F)/GCGD/TCJ(D,F)/YCJ(D,F) SERIES1.5 TO 5 TONS – 1 & 3 PHASEINSTALLATION MANUAL®LIST OF SECTIONSGENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ‘1SAFETY . . . . . . . . . . …
  • Panasonic

    CW-N2421EA

    (2 pages)
    When installing air conditioner at glass window or thin partition, fix the vertical and side supporting bar to the concrete wall in order to support the weightof the air-conditioner and reduce the vibration that is being transferred to the glass window or thin partition.This can minimize the noise problem caused by improper installation. Thank you for buying …

Air Conditioner Instructions:

Comments, Questions and Opinions: